97/ 100
CLEAR CREEK ELEMENTARY
13501 ALBEMARLE RD, Charlotte, NC 28227
School Building · NC permit/State ID 2060440031
Latest result97 / 100
Last inspectedOct 8, 2026
Inspections on record14
On record sinceMar 14, 2014
Score history
Mar 14, 2014Higher is betterOct 8, 2026
Inspections & violations
Oct 8, 2026 97 / 100 · 2 violations
Inspector comments: *NOTE: Head Custodian, Mr. Cloud, was present during time of inspection. Report emailed to:
Julianl.cloud@cms.k12.nc.us
joyce.fullington@cms.k12.nc.us
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed water fountain near main office and water fountain near student restrooms by cafeteria with black build up inside of drinking fountain nozzles. Clean.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −10
Waste material, unnecessary articles, rubbish, litter, or garbage shall not be allowed to accumulate on the premises. 15A NCAC 18A .2415 (a). Observed litter and dilapidated furniture surrounding dumpster area. Clean/remove.
Oct 10, 2025 96.5 / 100 · 2 violations
Inspector comments: *NOTE: Head Custodian, Mr. Cloud, was present during time of inspection. Report emailed to the following:
Julianl.cloud@cms.k12.nc.us (head custodian)
joyce.fullington@cms.k12.nc.us (principal)
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). Observed 2 spring loaded faucets not operating in modular unit. Per head custodian, a work order will be submitted to have issue repaired.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b). Observed dead insects in light shields sporadically throughout school building. Clean.
Oct 1, 2024 95 / 100 · 2 violations
Inspector comments: NOTE: The school’s roof is in need of repairs. Leaks are ongoing and ceiling tiles are subject to staining from water.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Observed water stained ceiling tiles in the cafe, media center, main hallway and kindergarten classroom at the end of the hall. Continue to replace water stained ceiling tiles throughout and ensure leaks are not ongoing.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dead insects in light shields near the boys and girls restroom near the cafeteria and the main hallway. Remove dead insects from light shields.
**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
Apr 3, 2024 95.5 / 100 · 3 violations
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stained ceiling tiles in rooms 1, 5, 8, 66 and 71. Continue to replace water stained ceiling tiles throughout and ensure leaks are not ongoing.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dead insects in light shields in the boys and girls restroom near the cafeteria. Remove dead insects from light shields.
**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −10
Observed droppings in the cabinet in room 1.
**There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a).
Apr 25, 2023 93.5 / 100 · 3 violations
Inspector comments: Julian Cloud present during inspection
#10-Solid waste containers shall be kept clean, in good repair, and emptied when full, but not less than once a week. 15A NCAC 18A .2414 (b). Observed dumpster missing half its lid. Replace dumpster.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b). Observed fountains throughout need regulating. Some had water pressure too high, some too low and some water was hitting mouth guard.
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed fountains in modular classrooms and gym need cleaning around fixtures.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed water stained ceiling tiles in media center, computer room (080) and hallway. Ceiling tiles in computer room appeared to have microbial growth. Repair what is leaking, then change out ceiling tiles.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b). Observed several classrooms with hazardous items in reach of children.
Oct 18, 2021 95.5 / 100 · 3 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed water fountain in mobile unit hall not working. PIC stated that she will request a work order for it
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −15
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d). Observed loose toilet seats in girls toilet. Tighten or replace loose toilet seat to prevent children from falling while using the restroom.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −10
All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411. Observed storage in gym closet in disarray. Organize storage to facilitate cleaning.
Mar 17, 2021 95 / 100 · 2 violations
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Observed water stained ceiling tiles on rooms 005, 008, Computer Room and the hall leading to the boys' restroom near the cafeteria.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed paper towels thrown in the lightshields in the boys restroom near the cafeteria.
**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
Jan 17, 2020 93 / 100 · 3 violations
Inspector comments: No points were taken for the following:
6. Observed water stained ceiling tile in room 001. Ensure leak is not ongoing and replace tile. Improvement from previous inspection.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −20
Observed droppings in the cabinets in rooms 001 and 011. Needs to be cleaned. Increase pest maintenance.
**Storage spaces and custodians' closets shall be kept clean and arranged so as to facilitate cleaning. 15A NCAC 18A .2411.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dead insects in the light shields in the gym. Needs to be cleaned.
**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed wipes and sprays stored within children's reach in rooms 001, 005, 011 and 085. Ensure that hazardous items are stored out of reach of children or within cabinets.
**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Jan 18, 2019 94 / 100 · 3 violations
Inspector comments: No points were deducted for the following:
7. Observed boxed items stored on the floor during the inspection in classrooms, flex rooms and some storage closets. Ensure that items are stored above the floor to help facilitate cleaning.
**All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411.
8. Observed dead insects inside the light shields in the gym and various light shields in the modular unit. Needs to be cleaned.
**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Observed faucet handles missing at the handwashing sink in the boys and girls restroom in the modular units. Observed sinks in need of recaulking in the boys and girls restroom in the modular units. Needs to be repaired.
**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stained ceiling tiles during inspection. Ensure that leaks are not ongoing and have tiles replaced.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed disinfectant wipes and sprays stored within reach of children in room 11 and 95. Ensure that wipes are stored out of reach of children or within cabinets so that they're out of sight.
**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Nov 13, 2017 95.5 / 100 · 2 violations
Inspector comments: No Points Deducted:
5. Observed sink in boy's restroom in modular unit rusted around the outer edge and in need of recaulking.
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
11. Observed disinfectant wipes out accessible to students in rooms 063, 026 and in modular room 7. Essential oil refills were also accessible to students on room 063. Warning label states should be out of reach of children.
Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −30
Observed toilets in need of recaulking in boys bathroom in modular units. Observed loose toilet seat in Mr. Grant's classroom restroom.
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed stained ceiling tile in room 026 and modular room 7. Observed wall damage in boys restroom in modular unit. Observed linoleum floor in boy's restroom in modular unit cracked near the entrance.
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
Sep 22, 2016 95 / 100 · 2 violations
Inspector comments: (NO POINTS DEDUCTED)
5. Observed pitted faucets present in boys bathroom across from cafeteria. Keep faucet fixtures clean and in good reapir.
8. Observed ceiling light about to fall from ceiling in classroom 3.
Ms. Dulce was present during inspection.
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −20
Observed one urinial with black bag over it (out of order boys 69)
**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Repeat Non Compliance: Observed water stained ceiling tiles present in the media center, room 08, room 71, computer lab room 80, gym hall and MC140.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
Mar 10, 2016 92.5 / 100 · 3 violations
Inspector comments: (NO POINTS DEDUCTED)
5. Observed soap not present in boys restroom near 3rd grade hall, as well as paper towel dispenser jammed in same restroom. Soap was stocked on site. Provide soap and accessible paper towels at all times.
7. Observed several areas where storage placed in class restrooms as well as 3 sets of cabinets in girls mod. restroom. Recommend keeping storage out of restrooms.
8. Observed 1 rusted A/C vent in boys restroom at cafeteria. Keep ventilation equipment clean and in good repair.
Ms. Dulce was present during inspection.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Observed short run time at spring loaded faucet in boys Mod restroom. Run time shall be at least 15 seconds to provide for adequate hand wash.
**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Repeat Non Compliance: Observed water stained ceiling tiles in media center, 075, cafeteria, and room 1 in modular.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Repeat: Observed: Cleaners, aerosol sprays, disinfecting wipes, etc., stored within reach of students (i.e. counter tops, low cabinets, under sinks) in most rooms inspected.
**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
May 4, 2015 88.5 / 100 · 6 violations
Inspector comments: #7: Observed: Closet floors inaccessible for routine cleaning in rooms 017 and 001. **Keep storage spaces accessible for cleaning and organized with storage off the floor.Ms. Dulce present.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed: Small white water fountains in rooms 062 and 065 with low pressure and the sink mounted water fountain in room 017 with low pressure.Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −15
Observed: Absorbent ceiling tiles in the restrooms in classrooms 062 and 065. Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).Observed: Flooring damaged in the MOD22 restrooms.Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Repeat: Observed: Some spring tension faucets with short times (under 15 seconds) in 093 and MOD22 Girl's restroom. Several sink faucets and sink drain areas dirty.Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Repeat: Observed: Minor water damaged ceiling tiles throughout some classrooms and halls.Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed: Most ventilation in classrooms collecting dust.All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Repeat: Observed: Cleaners, aerosol sprays, disinfecting wipes, etc., stored within reach of students (i.e. counter tops, low cabinets, under sinks) in most rooms inspected. Custodial closets not locked in the MOD22 Boy's restroom and Cafeteria Boy's restroom.Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Mar 14, 2014 94 / 100 · 3 violations
Inspector comments: Dulce Delgadillo (custodian) was present during the inspection.#7 - Observed excess items/supplies were stored on the floor in room 005. **All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411.#10 - Observed the dumpster lid was left open. **Keep all garbage in covered containers. **Impervious, cleanable containers with lids, approved by the Department, shall be provided for the storage of solid waste. 15A NCAC 18A .2414 (a).***Observed the turtle tank needed cleaning in room 005.***Observed a microwave and coffee maker set up for use in the womens restroom (modular unit) with electrical cords running near the hand washing sink. Recommend moving the food appliances to a more a sanitary/safe location.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Observed some spring-loaded sink faucets with run times less than 10 seconds. **Adjust all spring-loaded faucets so that water runs for at least 15 seconds.Observed the cabinet under the sink with mold/moisture in room 095.**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed some areas with wet and water damaged ceiling tiles: kindergarten/1st grade hallway, room 005, and the hallway near the cafeteria.**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
(Repeat Non-compliance) Observed Lysol wipes, Clorox wipes, aerosols and other chemical cleaners were stored withing reach of the students: rooms 005, MCR472, 097, 095, 017. Observed the janitor closet in the cafeteria boys restroom was left open, and contained commercial cleaners. **Store all chemical hazards according to labeled instructions, out of reach of children or behind lock and key.**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “CLEAR CREEK ELEMENTARY” or State ID 2060440031). Inspection type (routine vs. follow-up) is not published in the county's data.