95/ 100
ELIZABETH TRADITIONAL ELEMENTARY
1601 PARK DR, Charlotte, NC 28204
School Building · NC permit/State ID 2060440051
Latest result95 / 100
Last inspectedApr 1, 2026
Inspections on record12
On record sinceFeb 28, 2014
Score history
Feb 28, 2014Higher is betterApr 1, 2026
Inspections & violations
Apr 1, 2026 95 / 100 · 2 violations
Inspector comments: *NOTE: Ms. Carolyn was present during time of inspection. Report emailed to:
laportiar.miller@cms.k12.nc.us (Head Custodian)
patrick.brann@cms.k12.nc.us (Principal)
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed water fountains on hallway 3R out of order. Observed black build up on drinking fountain nozzles on 1st grade hallway.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained ceiling tiles sporadically throughout school building to include, auditorium, media center, and near elevator on level “2”.
Mar 13, 2025 96.5 / 100 · 2 violations
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stained ceiling tiles in room B1.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −20
Observed mouse droppings in the cabinets in the auditorium area between the bathrooms.
**There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a).
Apr 10, 2024 95.5 / 100 · 3 violations
Inspector comments: No points were deducted for the following:
4. Observed urinal out of order in the boys restroom on the 3rd floor. Work order already in place.
**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stained ceiling tiles on 3R hall and room C6. Observed exterior ceiling leading to back entrance in need of repair.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dead insects in the light shield in the girls room on the 2nd floor.
**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
Observed light out in room A2. Work order already in place.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −10
Observed mouse droppings in the cabinets in the auditorium area between the bathrooms.
**There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a).
Apr 28, 2023 95 / 100 · 3 violations
Inspector comments: No points were deducted for the following:
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d). Observed deteriorating caulking around toilets in boys and girls restrooms (Main and 3R, 3, 2R). Recaulk.
Aimee Lee conducted the inspection.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Observed water stained ceiling tile on the 3 storage room, 3 boys restroom, Custodian office. Observed wall damage in the boys restroom on the 3rd floor, women’s restroom 3rd floor, and women’s restroom 2nd floor. Observed wall damaged under the boys urinal 2nd floor.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −10
All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411. Observed boxes of storage/supplies on the floor in Main- B2, 3R, 2.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −10
There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a). Observed mouse droppings in the cabinets in the auditorium area between the bathrooms. Clean the droppings.
Jan 19, 2022 97 / 100 · 1 violation
Inspector comments: No points were deducted for the following:
11. Observed droppings under the sink in room C5. Ensure that there is effective pest management.
**There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Observed water stained ceiling tile on the 3rd floor, the auditorium and classroom C6. Observed wall damage in the boys restroom on the 1st floor.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
Jan 15, 2021 97.5 / 100 · 2 violations
Inspector comments: *NOTE: Custodian Ms. Shauna was present during time of inspection. Report was emailed to Principal and head custodian at the following:
susan.spencer-smith@cms.k12.nc.us
nataliep.hayes@cms.k12.nc.us
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed ceiling stain in auditorium near stage. Observed minor ceiling stains in rear of cafeteria. Observed wall damage behind water fountains located in cafeteria. Observed wall damage in auditorium on far right aisle.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −10
All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411. Observed boxes of storage/supplies on the floor in gymnasium and in library teacher work room.
Sep 18, 2019 92.5 / 100 · 4 violations
Inspector comments: No Points Deducted:
3. Observed fountains by C11 with high pressure. Follow the rule below.
Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b).
4. Observed out of order toilet in the hall restroom by A1. Toilet is overflowing leaving a puddle of water on the floor. Repair.
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
5. Observed one spring loaded faucet in B1 and one in G306 restrooms with short run time. Regulate to provide a minimum of 15 seconds run time to facilitate proper handwashing.
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
Report emailed to: susan.spencer-smith@cms.k12.nc.us & nataliep.hayes@cms.k12.nc.us
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed stained ceiling tiles in the hall by C5, and in the storage room of 302. Replace tiles and repair the leaks.
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −10
Observed storage (pillows, books, etc) on the floor in room C6. Organize.
All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411.
#10 · SOLID WASTE DISPOSAL: Impervious, cleanable containers with lids, approved type 20*; clean and in good repair 20#; empties as needed, properly disposed of 40# (.2414) −10
Observed a lid missing from the dumpster, the door open, and drain plug missing. Replace whole dumpster.
Solid waste containers shall be kept clean, in good repair, and emptied when full, but not less than once a week. 15A NCAC 18A .2414 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −40
-Observed rodent droppings in the auditorium restrooms and cabinet, in the cabinet in room B1, and in the gym storage. Clean droppings, supervise the areas, and provide pest control if more droppings are present. *There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a).
-Observed aerosol spray in the restroom in B1, C4, and bulk sanitizer in A1. Store out of reach of the children. *Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Jan 16, 2018 92 / 100 · 4 violations
Inspector comments: **No Points **
4. Teacher in room number 251 stated a toilet leak was under repair. teacher stated issue had persisted for past 4 weeks. Ensure issue is resolved.
15A NACA 18A .2408 (d) Toilet fixtures shall be kept clean and in good repair
7. Observed closets such as the media storage closet with storage directly on the floor, as well as in art room.
15A NCAC 18A .2410 Storage spaces... shall be at least 15 inches above the floor or otherwise so as to permit thorough cleaning.
8. Observed dust on majority of blinds throughout school.
15A NCAC 18A .2412 (b) All window and window fixtures shall be kept clean and in good repair.
Inspection was part of authorization process.
M. Adame accompanied by Stacey Robins REHS #1219
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed majority of drinking fountains with broken handles throughout the school.
15A NCAC 18A .2406 (b) Fountains shall be.. kept clean and in good repair.
Ensure handles on fountains are on good repair.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Observed leaking faucet in room 251 and in room A3.
15A NCAC 18A .2409 (b) Fixtures shall be kept clean and in good repair.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed build up of dead bugs in utility storage rooms and up stairs portion of auditorium. Ensure adequate cleaning is performed
to avoid build up of bugs. observed heavily stained ceiling tiles on 3rd floor near room 321. Observed damaged walls in auditorium.
15A NCAC 18A .2410 Floors, walls, and ceilings of all areas shall be kept clean and un good repair.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed disinfectant wipes, dry ease board cleaner, and air fresheners in aerosol cans, stored at children reach in art room (A3),
unlocked bathroom 118, room 110, b3, bathroom 214.
15A NCAC 18A .2415 (b) Pesticides and other toxic materials shall be used as directed on the label and handled and stored to avoid
health hazards.
If products are labeled "keep out of reach of children" store accordingly.
Sep 7, 2016 89.5 / 100 · 4 violations
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −40
Repeat Non Compliance: Observed broken toilet seat in room 305, 205, 109. Replace toilet seats.
**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −20
Observed spring loaded faucets with short run time in Men's 313, 214, and 215.
**Provide 15 seconds at spring loaded faucets for adequate hand wash.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stained ceilings in nurse's office, media center, data closet 232
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed disinfectant wipes stored out in reach of children in rooms: B1, B2, C9, B6, A4.
**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Mar 24, 2016 91 / 100 · 3 violations
Inspector comments: (NO POINTS DEDUCTED)
#6. Observed 1 water stained ceiling tile located in nurses office.
Ms. Natalie was present during inspection.
Ms. Susan Spencer-Smith was present during inspection
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed water fountain outside of C5 with residue build up around base of water fountain.
**Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −40
Observed 2 loose toilet seats located in 2nd grade girls restroom.
Observed 1 broken toilet seat in boys 2nd grade hall restroom.
**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
Repeat: Observed spring loaded faucets with short run times in most girls/boys restrooms, nurses station, and mens staff 3rd floor.
Observed 1 sink faucet continually running in 2nd grade girls restroom.
**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
Feb 4, 2015 87.5 / 100 · 5 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed many water fountains with broken push buttons. Pink residue around fountain fixture, 2nd floor.**Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −20
Observed toilets with rings around bowls and urine lines down fronts of urinals, most bathrooms throughout school. Broken toilet seat in 1st floor boys bathroom.**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −35
Observed no soap dispensers (broken) in boys bathroom 3R. Broken soap dispenser and toilet paper dispenser in girl's bathroom 3R. No paper towels in C4, C3. Missing faucet handle in A-5. Corroded faucet fixtures 3rd floor girl's. No soap 3rd floor boys.**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).**Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c).
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −20
Repeat: Observed storage on floor in hallway storage and custodial closets.**All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed unlabeled spray bottles in main hall custodial closet. Cleaners stored within reach of children (below hand sink) in some classrooms.**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).
Feb 28, 2014 85 / 100 · 7 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Repeat: Observed: Most water fountains with dirty mouthpieces, broken buttons, and dirty exteriors.Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −15
Observed: Walls dirty and damaged in restrooms (3/4 grade hall, 2/3 grade hall). Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
Repeat: Observed: Most spring tension faucets with broken buttons, short tun times, and/or not functioning. A loose sink backsplash in the Art Room. Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). ~provide at least a 15 second run time~
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed: Water damaged ceiling tiles throughout a few classrooms. Damaged walls and baseboards throughout walls and classrooms. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −20
Repeat: Observed: Excessive storage on the floor in the supply room near the Auditorium, Health Room shower stall, and HDC restroom. Storage spaces and custodians' closets shall be kept clean and arranged so as to facilitate cleaning. 15A NCAC 18A .2411.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed: Light fixtures and Gym ventilation fixtures collecting dust.All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Repeat: Observed: Cleaners, disinfecting wipes, and aerosols stored within reach of children in classrooms and some staff restrooms. Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).Susan Spencer-Smith and Ms. Blackwell present.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “ELIZABETH TRADITIONAL ELEMENTARY” or State ID 2060440051). Inspection type (routine vs. follow-up) is not published in the county's data.