91/ 100
MYERS PARK HIGH SCHOOL
2400 COLONY RD, Charlotte, NC 28209
School Building · NC permit/State ID 2060440089
Latest result91 / 100
Last inspectedDec 8, 2025
Inspections on record10
On record sinceApr 11, 2014
Score history
Apr 11, 2014Higher is betterDec 8, 2025
Inspections & violations
Dec 8, 2025 91 / 100 · 3 violations
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −30
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d). Observed missing flush buttons on multiple urinals throughout school. Observed several toilets out of order throughout school. Observed no toilet seat on one toilet in Men’s 2nd floor SET bathroom.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). Observed no push buttons on sinks in various bathrooms throughout facility.
Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c). Observed missing soap dispensers and non-functioning hand-drying devices in bathrooms throughout facility. Repair.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained and/or missing ceiling tiles in gym building and SS building. Repair/replace.
Sep 25, 2024 88 / 100 · 5 violations
Inspector comments: Inspection led by Casey Aitcheson.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b). Observed various drinking fountains throughout facility in need of pressure increase.
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed various drinking fountains throughout facility with black buildup inside nozzles and missing push buttons. Keep clean and repair missing pieces.
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −15
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d). Observed missing flush buttons on multiple urinals throughout facility. Observed missing toilet seat in boys locker room bathroom.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). Observed no push buttons on sinks in various bathrooms throughout facility.
Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c). Observed missing soap dispensers and non-functioning hand-drying devices in bathrooms throughout facility. Repair.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained ceiling tiles throughout facility. Observed large holes and missing ceiling tiles in room MA 1. Repair. Observed torn padding on wall in old gym. Observed cracked wall tile in girls gym bathroom. Observed loose/missing floor tiles throughout visual arts building. Observed damaged/missing floor tiles in various rooms in mobile units. Repair.
#9 · DRESSING ROOMS AND SHOWERS: Floors, walls, and ceilings clean, in good repair, washable, non-absorbent 30#; fixtures clean, in good repair 40#; facilities for storage of clothes provided, kept clean 20#; soap and towel 10* (.2413) −55
Floors, walls, and ceilings of dressing rooms and showers shall be kept clean and in good repair. 15A NCAC 18A .2413 (a). Observed stained carpet in need of cleaning in locker room #1. Observed baseboards peeling from walls in locker rooms and wrestling room.
All fixtures shall be kept clean and in good repair. 15A NCAC 18A .2413 (d). Observed broken shower seat in boys locker room and shower seat in girls locker room in need of cleaning. REPEAT
Jun 13, 2023 94.5 / 100 · 3 violations
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b). - Observed dead insects in the light shield in SC-17 and SEC building.
#9 · DRESSING ROOMS AND SHOWERS: Floors, walls, and ceilings clean, in good repair, washable, non-absorbent 30#; fixtures clean, in good repair 40#; facilities for storage of clothes provided, kept clean 20#; soap and towel 10* (.2413) −20
All fixtures shall be kept clean and in good repair. 15A NCAC 18A .2413 (d). - Observed rusted shower in dressing room # 3.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −15
There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a). - Observed dead insects in the locker rooms.
Oct 20, 2021 94 / 100 · 3 violations
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Observed water stained ceiling tiles in the Band bldg, rooms S11 and S1 in Social Studies bldg, and in the Gym bldg. Ensure that leaks are not ongoing and have ceiling tiles replaced. In room S1, ensure that window is properly sealed. Signs of leaking around the top of the window.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −10
Observed boxes stored on the floor in the data closet in the SET bldg and in the storage closet in the LA bldg.
**All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411.
#9 · DRESSING ROOMS AND SHOWERS: Floors, walls, and ceilings clean, in good repair, washable, non-absorbent 30#; fixtures clean, in good repair 40#; facilities for storage of clothes provided, kept clean 20#; soap and towel 10* (.2413) −20
Observed rusting in the shower stall in the football locker room. Needs to be repaired.
**Floors, walls, and ceilings of dressing rooms and showers shall be kept clean and in good repair. 15A NCAC 18A .2413 (a).
Sep 30, 2020 93.5 / 100 · 4 violations
Inspector comments: NO POINTS FOR THE FOLLOWING:
#7. All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411. Observed boxes/containers of storage on the floor located in Performing Arts building storage rooms.
*NOTE: Head Custodian Mr. Darryl was present during time of inspection. Report emailed to him and Principal at the following:
darryl1.witherspoon@cms.k12.nc.us
mark.bosco@cms.k12.nc.us
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed water fountains throughout SET building with residue build up. Clean.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). Observed spring loaded faucet bells missing from handsink in the following restrooms: LA building first floor boys restroom, SET building third floor girls restroom, and gym ground floor boys restroom.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained ceiling tiles in lobby of main gym on second floor. Observed minor stained ceiling tiles in Student Center building on main hallway. Observed hole in wall in boys football locker room.
#9 · DRESSING ROOMS AND SHOWERS: Floors, walls, and ceilings clean, in good repair, washable, non-absorbent 30#; fixtures clean, in good repair 40#; facilities for storage of clothes provided, kept clean 20#; soap and towel 10* (.2413) −15
Floors, walls, and ceilings of dressing rooms and showers shall be kept clean and in good repair. 15A NCAC 18A .2413 (a). Observed heavy rust accumulation on wall of last shower in boys football locker room.
All fixtures shall be kept clean and in good repair. 15A NCAC 18A .2413 (d). Observed shower fixtures throughout all locker rooms with minor rust accumulation.
May 15, 2019 88.5 / 100 · 4 violations
Inspector comments: NO POINTS WERE TAKEN FOR THE FOLLOWING:
#1 - Observed missing back flow prevention device from hose bib in girls performing arts restroom. **Backflow connections and cross-connections with unapproved water supplies are prohibited. 15A NCAC 18A 2405 (c).
#9 - Observed cleaning/touch-up paint needed on walls in male P.E., dressing room #3, and dressing room #4. Observed peeling ceiling in dressing room #4. Observed showers in need of cleaning in dressing room #3. Observed cracked wall tile in male P.E. **Floors, walls, and ceilings of dressing rooms and showers shall be kept clean and in good repair. 15A NCAC 18A .2413 (a). **All fixtures shall be kept clean and in good repair. 15A NCAC 18A .2413 (d).
NOTE: School concession stand is not allowed to handle, cook or serve food without a food service permit from Mecklenburg County Environmental Health. School concession stand need to cease the handling, cooking and serving of food products until permit is obtained. School can only serve and sell prepackaged foods until permit is obtained. The LFSE permit will allow school concession stands to cook food on the grill.
EHS emailed LFSE application along with inspection.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed major improvement on the cleaning of water fountain nozzles. Observed water fountains with too high of pressure in AG building, 1st & 2nd floor of SS building, performing arts building, and female P.E.
**Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −15
Observed cleaning needed on the base of toilets in several restrooms throughout buildings. Observed cleaning/touch-up paint needed on walls under rr hand dryers. Observed stall wall partition with peeling peeing in the boys VA building rr. Observed large crack in the corner of the wall in the last stall and cracked wall tile in the girls gym lobby rr.
**Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).
**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −50
Observed spring loaded faucet bells missing from hand sinks in boys SC restroom #2, boys 1st floor rr LA building, boys 326 rr LA building, and 1st & 3rd floor boys rrs SET building. Observed no paper towels present in boys math building rr, boys SC13 rr, or girls 1st floor SS building rr. Observed re-caulking needed around the backs of hand sinks in girls SC building rr, boys SC rr #2, boys performing arts rr, and boys gym lobby rr. Observed spring load faucet running less than 15 secs in girls SC11 rr and boys performing arts rr. Observed paper towel dispenser broken in boys performing arts rr. Observed faucet handles not working on hand sink in girls 1st floor LA building rr. Observed no soap in boys 226 rr LA building. **Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). **Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Repeat Observed water stained ceiling tiles in room 28 of SC building, S-18, stairwell of LA building, and VA building. Observed baseboard detached from hallway ramp in SC building. Observed stains on the carpet in the media center. Observed cleaning/touch-up paint needed on walls in V-2 of VA building. Observed cleaning needed on the stairs in the stairwell of the gym leading from locker rooms to main gym. Observed cracked tile floor in the gym lobby.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
Oct 2, 2017 90 / 100 · 3 violations
Inspector comments: No Points Deducted:
4. Observed a clogged leaking urinal in the boy's restroom in the SS Building (1st floor).
Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
*School-wide movie was being filmed today. Every building was not able to be entered.
*Mr. Lance Osborne present during inspection.
Report emailed to Principal: mark.bosco@cms.k12.nc.us; lancel.osborne@cms.k12.nc.us & pam.bartel@cms.k12.nc.us
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −40
Repeat: Observed pink and black buildup on and around the water fountain mouthpieces. Clean.
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
-Observed a faucet knob missing in the boy's restroom in the SC Building, a paper towel dispenser on the floor in the girl's room, and a loose faucet in the boy's restroom in the SS Building.
-Repeat: Observed discolored build up around faucet areas and bowl of multiple handsinks in each building. Clean.
-Repeat: Observed handsinks with spring loaded handles with short run time. Ensure spring loaded faucets operate for at least 15 seconds to facilitate in proper handwashing.
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Repeats:
-Observed water stained ceiling tiles and pink & black microbial growth present throughout several buildings (classes, halls, etc.). Repair leak and replace tiles.
-Observed broken floor tiles in hallway of multiple buildings.
-Observed the paint on the wall in the hall of Tech Building peeling off.
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
Apr 4, 2016 81.5 / 100 · 7 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −40
Repeat Non-Compliance: Observed pink and black buildup on and around the water fountain mouthpieces. Clean.
Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −45
Repeat Non-Compliance:
-Observed the ceiling not constructed of approved finish in the Auditorium restroom and P boys and girl and T building.
Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).
-Observed walls, stall doors, and the floor area around the toilets soiled/dirty and along baseboards. Clean.
-Observed chipped floor tiles in the girl's Math building restroom.
Floors of toilet facilities shall be impervious and kept clean. 15A NCAC 18A .2408 (c).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
Repeat Non-Compliance:
-Observed discolored build up around faucet areas and bowl of multiple handsinks in each building. Clean.
-Observed handsinks with spring loaded handles with short run time. Ensure spring loaded faucets operate for at least 15 seconds to facilitate in proper handwashing.
-Observed a sink in the boy's restroom CB building-Top falling from the wall. Prop up and recaulk.
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Repeat Non-Compliance:
-Observed water stains and pink & black microbial growth present and missing ceiling, broken, or falling ceiling tiles throughout several buildings (classes, halls, storage, etc.). Repair leak and replace tiles.
-Observed broken floor tiles in hallway of multiple buildings and the green rubber flooring on the ramps in the SC building lifting and splitting in areas.
-Observed chipping baseboard paint in M6 & chipping paint around and near the windows in LA Building.
-Observed chipping paint on the shelves in B2.
**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15ANCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed the lights not working in the Baseball Locker room and a storage room in the gym area. Repair.
Lighting and ventilation shall be provided and installed as required by the N.C. State Building Code. 15A NCAC 18A .2412 (a).
#10 · SOLID WASTE DISPOSAL: Impervious, cleanable containers with lids, approved type 20*; clean and in good repair 20#; empties as needed, properly disposed of 40# (.2414) −10
-Observed the middle dumpster rusted out with holes in it (garbage can be seen through the holes.)
-Observed the door open on the 1st dumpster. Keep closed.
Solid waste containers shall be kept clean, in good repair, and emptied when full, but not less than once a week. 15A NCAC 18A .2414 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −10
Observed roaches in the Culinary class- T4. Provide pest control.
There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a).
Mr. Lance Osborne present during inspection
Report emailed to Principal: mark.bosco@cms.k12.nc.us & lancel.osborne@cms.k12.nc.us
Apr 22, 2015 79 / 100 · 7 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −60
Observed build-up, microbial growth and discoloration around and on mouthpiece of water fountains throughout different school buildings. Also observed water pressure low on several water fountains throughout in different school buildings. THOROUGHLY CLEAN ALL WATER FOUNTAINS THROUGHOUT IN DIFFERENT BUILDINGS. Increase water pressure on water fountains with low water pressure. Observed water fountain with missing siding. Replace missing siding on water fountain. Clean water fountains at and near push bar/button and nozzle bases **Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b)**. Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −70
Observed the ceiling not constructed of approved finish in the Auditorium restroom and P boys and girl and T building. Observed floor under, beside and behind toilets soiled/dirty and along baseboards. Thoroughly clean floor in all bathrooms. Observed toilet seat loose or broken in several bathrooms. Tighten or replace loose or broken seats on toilets. Observed build-up of old urine on underside of men wall urinal and on upper interior rim of urinals. Thoroughly clean toilets and wall urinals!**Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b)**Floors of toilet facilities shall be impervious and kept clean. 15A NCAC 18A .2408
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Observed build up around faucet areas of hand sink and base of handsink. Observed hand sink with spring loaded handles with short run time and missing/damaged handle on other hand sinks. THOROUGHLY CLEAN HAND SINKS! Repair/replace spring loaded handles on hand sink with short run time. Spring loaded handles should operate for at least 15 seconds. Replace damaged/corroded and missing handles on hand sink.**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stains, pink and black microbial growth present on ceiling tile throughout different buildings. Lots of missing ceiling tiles throughout campus. Repair any and all roof leaks then replace water stained/ ceiling tiles! Observed broken floor tiles in hallway of V-building. **Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15ANCAC 18A .2410.
#7 · STORAGE SPACES: Clean 20#; storage off floor 20# (.2411) −10
Observed storage (cardboard boxes) on floor in storage rooms, mainly in SC bldg.**All storage shall be at least 15 inches above the floor or otherwise arranged so as to permit thorough cleaning. 15A NCAC 18A .2411.Mr. Lance Osborne present during inspection
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dusty and dirty blinds, loose/damaged blinds Dusty/dirty window sills. Cracked windows in exterior door of P-blg and girls bathroom, P-blg. Very loose handrail in SS bldg.**All windows and fixtures(grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#9 · DRESSING ROOMS AND SHOWERS: Floors, walls, and ceilings clean, in good repair, washable, non-absorbent 30#; fixtures clean, in good repair 40#; facilities for storage of clothes provided, kept clean 20#; soap and towel 10* (.2413) −20
Thoroughly clean floors and fixtures in shower stalls in dressing rooms. **Floors, walls, and ceilings of dressing rooms and showers shall be kept clean and in good repair. 15A NCAC 18A .2413 (a).**All fixtures shall be kept clean and in good repair. 15A NCAC 18A .2413 (d).
Apr 11, 2014 72 / 100 · 8 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −60
Observed build-up, microbial growth and discoloration around and on mouthpiece of water fountains throughout different school buildings. Also observed water pressure low on several water fountains throughout in different school buildings! THOROUGHLY CLEAN ALL WATER FOUNTAINS THROUGHOUT IN DIFFERENT BUILDING! Increase water pressure on water fountains with low water pressure! Observed water fountain with missing siding. Replace missing siding on water fountain. Clean water fountains at and near push bar/button. **Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b)**. Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −55
The ceiling not constructed of approved finish in the Auditorium restroom and P boys and girl and T building. Observed holes in wall around plumbing fixture to wall urinal and near clean out. Patch/seal holes in wall and provide a cover plate to cover clean out piping. Observed floor under, beside and behind toilets soiled/dirty. Thoroughly clean floor in all bathrooms. Observed toilet not secured to the floor in math building and toilet seat loose throughout in different bathrooms. Tightly secure and seal toilet to the floor. Tighten loose seats on toilets. Observed build-up of old urine on underside of men wall urinal and on upper interior rim of urinals. Thoroughly clean toilets and wall urinals!**Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).**Floors of toilet facilities shall be impervious and kept clean. 15A NCAC 18A .2408 (c).**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −70
Observed build up around faucet areas of hand sink and base of handsink. Observed hand sink with spring loaded handles with short run time and missing/damaged handle on other hand sinks. THOROUGHLY CLEAN HAND SINKS! Repair/replace spring loaded handles on hand sink with short run time. Spring loaded handles should operate for at least 15 seconds. Replace damaged and missing handles on hand sink. Observed several handsinks in classrooms and bathrooms with no soap and paper towels. PROVIDE SOAP AND PAPER TOWELS AT ALL HANDSINKS AT ALL TIMES!**Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed water stains, pink and black microbial growth present on ceiling tile throughout different building (classroom, storage area and office areas). Repair any and all roof leaks then replace water stained/ ceiling tiles! Observed wall damage throughout in different modular unit. Repair walls in modular units!**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dusty and dirty blind, loose/damaged blinds, dusty fixtures(top of lockers, border ledges, projection screens and cabinets). Thoroughly clean window blinds. Remove broken/damaged blind to prevent blinds from falling onto students. Dust/clean fixtures throughout in different rooms. Repair damaged light fixtures in class rooms or replace blown light bulbs.**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#9 · DRESSING ROOMS AND SHOWERS: Floors, walls, and ceilings clean, in good repair, washable, non-absorbent 30#; fixtures clean, in good repair 40#; facilities for storage of clothes provided, kept clean 20#; soap and towel 10* (.2413) −15
Thoroughly clean floors, toilets, hand sink and shower stalls in dressing rooms. **Floors, walls, and ceilings of dressing rooms and showers shall be kept clean and in good repair. 15A NCAC 18A .2413 (a).**All fixtures shall be kept clean and in good repair. 15A NCAC 18A .2413 (d).Replace damaged padding on athletic trainer table and weight lifting equipment!
#10 · SOLID WASTE DISPOSAL: Impervious, cleanable containers with lids, approved type 20*; clean and in good repair 20#; empties as needed, properly disposed of 40# (.2414) −20
Replace dumpster with broken/missing lids!**Solid waste containers shall be kept clean, in good repair, and emptied when full, but not less than once a week. 15A NCAC 18A .2414 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −25
Observed old desk and boards near back of sc building. Remove old desk and boards from behind building area. Observed ant mounds throughout along side walk and in social studies building. Address ant issue! Observed bee/wasp issue near modular units. Provide caps on metal railing leading to modular units. Tightly secure loose boards and railing leading to modular units. Highly recommend cutting trees from under modular unit and walkway to modular units.**Waste material, unnecessary articles, rubbish, litter, or garbage shall not be allowed to accumulate on the premises. 15A NCAC 18A .2415 (a).