THOMASBORO ACADEMY

538 BRADFORD DR, Charlotte, NC 28208
School Building · NC permit/State ID 2060440138
Latest result95 / 100
Last inspectedApr 1, 2026
Inspections on record12
On record sinceJan 13, 2014

Score history

7085100 Jan 13, 2014: 86.5Aug 18, 2014: 89.5Jan 27, 2016: 82Sep 1, 2016: 87Jul 27, 2017: 88.5Aug 27, 2018: 95.5Oct 9, 2020: 97Oct 12, 2021: 97Mar 15, 2023: 95.5Feb 26, 2024: 89Feb 5, 2025: 94Apr 1, 2026: 95
Jan 13, 2014Higher is betterApr 1, 2026

Inspections & violations

Apr 1, 2026 95 / 100 · 2 violations
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Observed water stained ceiling tiles in rooms A4, A5, B1, B6, A-Hall and B-Hall, and the Media Center. **Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed dead bugs in the light shields in the gym, A4, B9, B10 and boys restroom on B-Hall. **All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).

View this inspection on the county portal ›

Feb 5, 2025 94 / 100 · 2 violations
Inspector comments: Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed water fountains outside gym and one in science hall with broken push buttons. Needs repair. Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c). Observed no paper towels in boys science hall bathroom. Dispenser needs repair.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained ceiling tiles in hallways and classrooms throughout facility. Needs to be checked for leaks and repaired. REPEAT.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b). Observed aerosol Lysol, aerosol air fresheners, aerosol hand sanitizers, lysol wipes, and chlorox wipes stored accessible to children in several classrooms. Needs to be stored inaccessible to children, as directed on label, to avoid health hazards. REPEAT.

View this inspection on the county portal ›

Feb 26, 2024 89 / 100 · 4 violations
Inspector comments: No points deducted. All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b). Observed missing light cover in c-13 bathroom. Observed cracked light cover in MC1180. Needs repair. Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b). Observed door to large stall in gym girls bathroom separating from hinges. Needs repair.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Drinking fountains shall be provided with adequate water pressure and be properly regulated (i.e. water pressure should be regulated so that an individual’s mouth does not come in contact with the nozzle and so that the water does not splash on the floor). 15A NCAC 18A 2406 (b). Observed low pressure at tall water fountain in C hall bathrooms. Observed middle B hall water fountain with low pressure. Needs to be adjusted.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). Observed rust accumulation under spring loaded hand washing faucets throughout school building. Needs cleaning/repair. REPEAT.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained ceiling ties in MC314, A-5, B-4, B-hallway, A-hallway, and C-2. EHS advises school to ensure no active leak is occurring and to have stained ceiling tiles replaced. REPEAT.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b). Observed aerosol Lysol, aerosol air fresheners, aerosol hand sanitizers, lysol wipes, and chlorox wipes stored accessible to children in several classrooms. Needs to be stored inaccessible to children, as directed on label, to avoid health hazards.

View this inspection on the county portal ›

Mar 15, 2023 95.5 / 100 · 2 violations
Inspector comments: NO POINTS FOR THE FOLLOWING VIOLATIONS: #3. Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b). Observed outside mobile drinking fountains with build up on drinking nozzles. These water fountains are currently turned off and not being used however they should still be kept cleaned. #4. Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d). Observed 1 toilet out of order in girls restroom on “A” hallway. Per head custodian, a work order has been submitted to have toilet repaired. *NOTE: Head Custodian Mr. Hall was present during time of inspection. Report emailed to him and Principal at the following: Staceyd.hall@cms.k12.nc.us R.parkins@cms.k12.nc.us
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b). Observed rust accumulation under spring loaded hand washing faucets throughout school building.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. Observed stained ceiling tiles sporadically throughout school building. EHS advises school to ensure no active leak is occurring and to have stained ceiling tiles replaced.

View this inspection on the county portal ›

Oct 12, 2021 97 / 100 · 1 violation
Inspector comments: Mr. Howell (Head Custodian) present during the inspection. Report emailed to him and the Principal.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Repeat: -Observed stained ceiling tiles in the hallways of the main building and in MC108. -Observed the paint peeling from the wall- "C Hall Bottom" -Observed the floor tiles chipped in the boy's mobile restroom- RR869. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.

View this inspection on the county portal ›

Oct 9, 2020 97 / 100 · 2 violations
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Observed several spring loaded faucets with a short run time. Regulate to provide a minimum of 15 second run time to facilitate proper handwashing.
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
-Observed stained ceiling tiles- "A" hallway, in classes, media center, front office, etc. Repair issue and replace tile. -Observed tissue wads on the wall in a hall restroom on the "C" hall. Clean. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410. *NOTE: Ensure all hazardous items are stored out of reach of the students when they start back in person learning. Report emailed to: jan.mciver@cms.k12.nc.us; sharrone.powell@cms.k12.nc.us; howellj.montgomery@cms.k12.nc.us

View this inspection on the county portal ›

Aug 27, 2018 95.5 / 100 · 2 violations
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −15
Observed floors needing to be cleaned in B hall and C hall boys restrooms. Food and debris on floor. Floors of toilet facilities shall be impervious and kept clean. 15A NCAC 18A .2408 (c).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed lysol out in class B7. No students in class at time, but door was open. Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).

View this inspection on the county portal ›

Jul 27, 2017 88.5 / 100 · 5 violations
Inspector comments: General Comment: #8. Tighten and secure loose handles on cabinet doors in classrooms where needed. Clean ceiling ventilation in MC1180. Replace missing vent cover in MC740. Remove damaged chair in B7. Replace broken/damaged window blind in classroom.****All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b). #10. Clean grounds behind and in dumpster corral area. Replace trash and card board dumpster. Dumpster lids are damaged and folded in on both dumpsters.***Solid waste containers shall be kept clean, in good repair, and emptied when full, but not less than once a week. 15A NCAC 18A .2414 (b). #11. Clean vegetative growth along walkway to modular units and under modular unit. Cut thorny vegetative growth from fence line on playground area. Address wasp and wasp nest over cover area of walk walk leading into school building and cover area at end of C hall leading out to playground area. Replace missing door to crawl space under gym area. Remove old desk, tables and pallets from behind dumpster area.****Waste material, unnecessary articles, rubbish, litter, or garbage shall not be allowed to accumulate on the premises. 15A NCAC 18A .2415 (a).There shall be no fly or mosquito breeding places, rodent harborages, or undrained areas on the premises. 15A NCAC 18A .2415 (a). #6 continued:WIpe/clean walls throughout in classroom where pencil sharpeners were located and near trash can storage area. Replace water stained ceiling tile in C15. Clean rug in C-6 or replace. Properly repair flooring in classroom beside C9 and remove metal raised flashing along expansion joint--> raised metal flashing along flooring is a serious trip hazard. Monitor and repaint lower section of wall under window in B2. Moisture is wickering through bricks and blocks under window---> address drainage issue outside of classroom. Patch hole in janitorial closet where washer and dryer was going to be installed or install washer and dryer. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Thoroughly clean mouth guards on water fountain. Observed mouth guards on water fountains soiled throughout on different hallways. Replace missing handle on side of water fountain on C hall or provide a blank plate to cover hole on water fountain. Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −35
Continue to repair wall in bathrooms on C hall along back side of school building from where building was settling/shifting. Repair upper section of walls and repair bathroom doors so doors will properly close! Thoroughly clean stall fixtures throughout in gang bathrooms on C, A and art/music/gym hall. Observed stall fixtures and doors soiled. Observed a lot of writing and stains on stall fixtures. Clean base of toilet in boys bathroom on A hall. Modular unit bathrooms are in the process of being remodeled. Repair or replace damaged wall tile in girls gang bathroom on A hall. Secure loose hanging metal strip or remove metal strip on base of stall fixture in boys gang bathroom on C hall. Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b). Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −15
Thoroughly clean area around faucet fixtures on hand washing sinks in boys and girls gang bathrooms on A, C and art/music/gym hall. Observed build-up around faucet fixtures on hand washing sinks. Modular unit bathrooms are in the process of being remodeled. Repair light fixture in boys gang bathroom on short A hall. Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed sheet rock tape coming loose on ceiling in hallway area on C hall. Observed moisture on flooring entering into the cafeteria. Address issue causing moisture on flooring near entrance to cafeteria. Continue to repair floor and wall in classrooms on C hall on back side of school building. Replace broken/damaged floor tiles in classrooms on back side of C hall near exit door and along expansion joint. Replace broken floor tiles in modular unit classrooms. ADDRESS MOISTURE ISSUE IN MODULAR UNIT MC1180. OBSERVED MOISTURE AND MICROBIAL GROWTH ON WALLS, CEILING TILE, CEILING TILE GRID RAILING VENTS, ETC. Connect dehumidifier to help address moisture issue in classroom! Repair hole on exterior siding of MC 740, then repair lower section of wall in MC740. Thoroughly clean wall in science room. WIpe/clean walls throughout in classroom where pencil sharpeners were located and near trash can storage area. Replace water stained ceiling tile in C15. Clean rug in C-6 or replace. Properly repair flooring in classroom beside C9 and remove metal raised flashing along expansion joint--> raised metal flashing along flooring is a serious trip hazard. Monitor and repaint lower section of wall under window in B2. Moisture is wickering through bricks and blocks under window---> address drainage issue outside of classroom. Patch hole in janitorial closet where washer and dryer was going to be installed or install washer and dryer. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed cleaning products not properly stored throughout in classroom areas. Observed cleaning products(carpet cleaner, disinfectant spray, disinfectant wipes and unidentified cleaning product. wipe stored under hand wash sink in classroom area, top of filing cabinet and on desks within classroom area. Store cleaning products out of reach of children! Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).

View this inspection on the county portal ›

Sep 1, 2016 87 / 100 · 4 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed mouth guard on water fountains soiled throughout on A, B and C Hall. Thoroughly clean mouth guards on water fountains. Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −50
General wiping/cleaning of walls in bathrooms on A, B and C hall and bathrooms within classrooms on A, B and C hall (boys and girls). MONITOR AND REPAIR WALLS IN BATHROOMS WITHIN CLASSROOMS ON C HALL( CLASSROOMS/BATHROOMS ON BACK SIDE OF SCHOOL BUILDING). Observed exterior of school wall pulling away from bathroom wall. Observed gap along base of flooring and wall in several to many bathrooms on C hall. (C-11, C-12, C-13, etc.) Repair damaged base tile cove molding in bathrooms within classrooms on C hall. Repair damaged wall tile in girls bathroom on B hall. Repair walls in outside modular unit bathrooms and repaint. Repair floor tiles in modular unit bathroom 505. Paint or stain bare wood bathroom stall door in girls bathroom located on C hall. General cleaning base of toilets where toilets bolts to the floor throughout in bathrooms. Repair stall door in modular unit 505 boys bathroom. Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b). Floors of toilet facilities shall be impervious and kept clean. 15A NCAC 18A .2408 (c). Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
General cleaning needed on hand washing sink behind faucet fixtures throughout in bathrooms on C and B hall. Repair handle on hand washing sink in girls bathroom located on B hall. Repair base of hand washing sink counter in outside modular unit. Repair hand washing sink counter top in girls bathroom in RR869. Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
General wiping/cleaning of walls throughout in classroom and hallway area. REPAIR FLOOR IN WALL ISSUE THROUGHOUT IN CLASSROOMS ON C HALL. OBSERVED EXTERIOR WALL SEPARATING FROM OTHER WALLS! OBSERVED GAPS BETWEEN FLOOR IN CLASSROOMS ON C HALL. ENTIRE FLOOR SLAB HAS SHIFTED AND SINKED THROUGHOUT IN CLASSROOMS ON C HALL. OBSERVED BUCKLING AND SINKING FLOORING IN GYM AREA. Observed damaged flooring throughout in many modular units. Repair flooring throughout in modular units! Address issue causing moisture to get into flooring and cause floor tiles to come up. Monitor and repair ceiling and wall in hallway area of C hall. Contacted Mrs. Robin Slade to address floor and wall issue on C hall. Replace missing metal trim on door framing on main school building leading out to modular units. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. Patch holes in wall on outside of classroom doors on C hall and repaint 15A NCAC 18A .2410. General Comments: Wipe/dust ventilation covers and return ventilation covers in classroom areas. Mr. Montgomery present at time of inspection.

View this inspection on the county portal ›

Jan 27, 2016 82 / 100 · 6 violations
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed mouth guards on water fountain soiled throughout on hallways near cafe/media center and gym hallway. Thoroughly clean mouth guards on water fountains. Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −50
Observed walls soiled in bathrooms throughout main school building and modular units. Thoroughly clean walls in bathrooms. Observed damaged wall in outside modular boys bathroom and damaged flooring/floor tiles in far back modular unit bathrooms. Wall damaged under wall urinal and floor tiles in bathroom loose and urine got under tiles in plywood and entire boys bathroom smell like urine. Thoroughly clean base of toilets within classroom between wall and toilet. Thoroughly clean underside of wall urinals in boys gang bathroom. Tighten loose seats on toilets. Wipe/clean stall fixtures in main school building. Thoroughly clean stall fixtures in outside modular units and repair stall door. Replace or repair loose metal trim on base of stall fixture in boys bathroom near cafeteria. Clean walls in bathrooms within classrooms around light switch. Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b). Floors of toilet facilities shall be impervious and kept clean. 15A NCAC 18A .2408 (c). Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −30
Observed area around faucet fixture in all bathrooms soiled. Thoroughly clean area around faucet fixtures in bathrooms. Observed damaged hand washing sink counter and base of counter in outside girls modular unit. Repair damaged counter tops in bathrooms. Replace missing back splash behind hand washing sink. Thoroughly clean base of sinks in room. Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −30
Tightly secure loose rubber cove base moulding near ESL room. Repair floor near top of ramp near stage. Replace broken/damaged floor tiles in hallway. General cleaning of walls throughout in classroom. Repair floor in outside modular units! ****Repair floor and floor tiles at entrance to modular unit MC740. Floor tiles are missing and floor board is soft at entrance. DO NOT WANT STAFF OR A CHILD TO FALL THROUGH FLOOR! Repair floor as soon as possible. Please do not cover damaged spot on floor with a rug like at other schools! Repair any roof leaks, then replace water stained ceiling tiles and ceiling tiles with microbial growth present. Touch-up paint throughout in classrooms.Secure loose base cove moulding in outside modular unit. Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#8 · LIGHTING AND VENTILATION: Fixtures, grills, vents, blinds, drapes, etc., clean and in good repair 40# (.2412) −20
Observed light not properly operating throughout in many classrooms. Either replace blown light bulbs or repair light fixtures in classrooms. Tightly secure strip on counter top in B-7. Wipe/dust top of high fixture(smart board brace and projector, cabinet storage). Replace torn/damaged chairs in B-7. Tighten loose handles on cabinet doors within classrooms. All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Observed hand sanitizer, disinfectant wipe, disinfectant spray, cleaning products and bug spray not properly stored within classrooms. Store toxic substance/cleaning products locked away or out of reach of children. Store bug spray locked away! Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b). General Comment: #11.Repair hole in exterior wall on back side of school building! Mr. Ellis present at time of inspection.

View this inspection on the county portal ›

Aug 18, 2014 89.5 / 100 · 4 violations
Inspector comments: General Comment: #8.Repair light fixtures throughout in different classrooms or replace blown ligth bulbs.**All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b). #11. Observed protruding pins in black border around playground equipment. Nail down protruding pins on playground equipment. Clean up trash from on playground area. Repair fence on playground area.
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Observed mouth guard on water fountain soiled throughout on different hallways. Thoroughly clean mouth guards on water fountains.Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −35
Observed wall and base board damaged in boy bathroom located in modular unit. Repair wall and base board in boy bathroom modular unit. Observed brokne toilet in boys bathroom located near cafeteria. Repair broken toilet in boys bathroom. Clean base of boys toilet in bathroom near gym. Repair broken base tile moulding in boys bathroom located near gym.Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −35
Observed several hand washing sink throughout in bathrooms and classroom missing soap and paper towels. Provide soap and paper towels at all hand washing sink at all times. Observed several hand washing sink with spring loaded faucets with short run time. Repair spring loaded faucet fixtures with short run time. Faucet fixtures shall operate on spring loaded faucets fixtures for at least fifiteen seconds. Repair handsink counter in boys and girls bathroom located in modular units.Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed several water stained ceiling tiles and ceiling tiles with microbial growth present on c hall. Repair any roof or air handler leaks, then replace water stained ceiling tiles. Replace damaged floor tiles in C-11 and MC740. Replace damaged electrical outlet in MC439. Repair base of wall and floor in c12.

View this inspection on the county portal ›

Jan 13, 2014 86.5 / 100 · 5 violations
Inspector comments: Mr. Hamer was present during the inspection.#8 - Observed some lights were not working in RR869 (boys), boys and girls restrooms. **All windows and fixtures (grills, vents, blinds, drapes, lighting fixtures, etc.) shall be kept clean and in good repair. 15A NCAC 18A .2412 (b).
#3 · DRINKING FOUNTAINS: Clean and in good repair 40#; adequate pressure, properly regulated 40# (.2406) −20
Repeat Non- compliance: Observed the water fountains with pink build-up on A Hall.**Drinking fountains shall be kept clean and in good repair. 15A NCAC 18A .2406 (b).
#4 · TOILET FACILITIES: Walls and ceilings clean, nonabsorbent, washable, and in good repair 30#; fixtures clean and in good repair 40#; floors impervious, kept clean 30# (.2408) −35
Observed the walls and base baseboards were dirty in the girls and boys restrooms.**Walls and ceilings of toilet facilities shall be constructed of non-absorbent, washable materials and shall be kept clean. 15A NCAC 18A .2408 (b).Observed a urinal in the gym boys restroom was not working; Observed a loose toilet seat in the handicap stall in the Mens C Hall restroom.**Toilet fixtures shall be kept clean and in good repair. 15A NCAC 18A .2408 (d).Note: Observed the water was turned off for water pipe repair in R505. Lock restrooms so that they are not used until the repairs are complete.
#5 · LAVATORY FACILITIES: Fixtures clean and in good repair 30#; soap and individual towels or approved hand-drying devices provided 40# (.2409) −35
Observed the sink counters with worn surface damage in RR869 boys and girls restrooms; laminate damage/exposed wood in RR869 girls, and one spring loaded faucet in RR869 girls with short run time. **Adjust water run times so that the water runs for at least 15 seconds at all spring loaded faucets.**Fixtures shall be kept clean and in good repair. 15A NCAC 18A .2409 (b).Observed no soap/towels in SR1190 restrooms; and no soap in gym boys restroom, A5, and A Hall boys and girls restrooms.**Soap and individual towels or approved hand-drying devices shall be provided. 15A NCAC 18A .2409 (c).
#6 · FLOORS: WALLS: AND CEILINGS: Floors, walls, and ceilings clean and in good repair 30# (.2410) −15
Observed the floor was dirty in room A2, B5(under sink), the carpet was stained in the media center, the old school entrance, and ISS classroomObserved wall damage in room C5, and missing ceiling tiles in B Hall and A Hall restroom (boys); observed a water stained ceiling tile in room A2.**Floors, walls, and ceilings of all areas shall be kept clean and in good repair. 15A NCAC 18A .2410.
#11 · PREMISES: MISCELLANEOUS: Premises neat, clean 30#; no vector breeding or harborage 20#; pesticides and other toxic materials properly handled and stored 30* (.2415) −30
Repeat Non-Compliance: Observed Lysol Wipes on the sink counter in room B5 and LCorox wipes on the counter in room C14.**Pesticides and other toxic materials shall be used as directed on the label and handled and stored as to avoid health hazards. 15A NCAC 18A .2415 (b).

View this inspection on the county portal ›