97.5/ 100
CHARLOTTE DETOX CENTER
7349 STATESVILLE RD, SUITE B, Charlotte, NC 28269
Orphanage, Children's Home · NC permit/State ID 2060470032
Latest result97.5 / 100
Last inspectedMay 14, 2026
Inspections on record2
On record sinceNov 19, 2025
Score history
Nov 19, 2025Higher is betterMay 14, 2026
Inspections & violations
May 14, 2026 97.5 / 100 · 3 violations
#7 · Facilities provided, accessible, clean, good repair −1
REPEAT
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair.- Observed pink and brown mildew at the drain in several hand sinks in restrooms. Observed several hand sink on the hall way with slowly draining. Need repair and clean. Keep clean.
#16 · Hot water between 105°F and 116°F −1.5
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities.- Observed suite B water temperature measured at 86F. Provides water temperature between 105-116F at anytime.
#17 · Back-up water supply plan available and complete
General Comment:
.1313 (e) The institution shall have a written plan to obtain a backup water supply in the event that the institution's primary water supply is interrupted for more than four consecutive hours. The written plan shall identify a backup water supply or alternate source of water that provides two liters of potable water per day per resident and institution employee for drinking and potable water for food preparation, hand washing, bathing, cleaning, dishwashing, laundry, and disposal of bodily waste. This may include a plan for relocating residents to a facility with a water supply that satisfies Paragraph (a) of this Rule. If an institution's primary water supply or backup water supply becomes unsafe for human consumption, then the water sources within the institution, such as sink faucets, shall be labeled or hooded to prevent their use, and the administrator shall provide potable water for use by the institution's residents and employees.- Observed the facility with an incomplete water back up supply plan. EHS discussed in detail what needed in a complete plan and email PIC the guide checklist. The facility shall obtain a complete written plan and have available upon request.
Nov 19, 2025 98 / 100 · 4 violations
Inspector comments: NOTE:
- PIC: Russell Guccio and Ryan Ledoux present during inspection.
#7 · Facilities provided, accessible, clean, good repair −1
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair.- Observed soiled basin drain of several hand sinks in restrooms. Detail cleaning needed. Keep clean.
#11 · EPA registered disinfectants used according to manufacturers' instructions; approved testing methods and devices used −1
.1312 (e) EPA registered disinfectants shall be used in accordance with the manufacturer's instructions. When EPA registered disinfectants are mixed and prepared by institution employees, a measuring device, chemical testing device, or the methods and devices prescribed by the chemical manufacturer shall be used to prepare the concentration of chemicals in accordance with the disinfectant's label and the manufacturer's instructions.- Observed the facility is using household cleaning products for cleaning. The facility shall use an approved EPA registered cleaning products to clean/sanitize/disinfectant purposes.
#17 · Back-up water supply plan available and complete
General Comment:
.1313 (e) The institution shall have a written plan to obtain a backup water supply in the event that the institution's primary water supply is interrupted for more than four consecutive hours. The written plan shall identify a backup water supply or alternate source of water that provides two liters of potable water per day per resident and institution employee for drinking and potable water for food preparation, hand washing, bathing, cleaning, dishwashing, laundry, and disposal of bodily waste. This may include a plan for relocating residents to a facility with a water supply that satisfies Paragraph (a) of this Rule. If an institution's primary water supply or backup water supply becomes unsafe for human consumption, then the water sources within the institution, such as sink faucets, shall be labeled or hooded to prevent their use, and the administrator shall provide potable water for use by the institution's residents and employees.- Observed the facility starts working on water back up supply plan. EHS discussed in detail what needed in a complete plan. The facility shall obtain a complete written plan and have available upon request.
#34 · Linens provided by the institution properly cleaned and sanitized
General Comment:
.1319 (c) Linens provided by the institution that are not clean shall be cleaned and sanitized in accordance with this paragraph. When hot water in washing machines is used to sanitize linens provided by the institution, the washing machines shall be operated in accordance with the manufacturer's instructions. When chemicals are used to sanitize linens provided by the institution, linens shall be washed in accordance with the following:
(1) using a solution of at least 50 parts per million chlorine; or
(2) using laundry sanitizer that is registered in accordance with 40 C.F.R. 152 and that is used in accordance with the manufacturer's instructions.
- Observed the facility is using a commercial washers and dryers to clean linens in-house. PIC stated the machine utilizes heat to sanitize linens. The specification fact sheet will be sent to EHS for review to determine how the sanitizer elements work.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “CHARLOTTE DETOX CENTER” or State ID 2060470032). Inspection type (routine vs. follow-up) is not published in the county's data.