8demerits

CARRIAGE HOUSE

6330 OLD PINEVILLE RD, Charlotte, NC 28217
Seasonal Swimming Pool · NC permit/State ID 2060500077
Latest result8 demerits
Last inspectedJul 10, 2026
Inspections on record12
On record sinceJun 13, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

02040 Jun 13, 2014: 26May 27, 2015: 16Mar 31, 2016: 12Jun 8, 2018: 6May 15, 2019: 10Apr 20, 2021: 14Apr 21, 2022: 22Apr 20, 2023: 18May 23, 2024: 8Jul 10, 2025: 40Jul 8, 2026: 18Jul 10, 2026: 8
Jun 13, 2014Lower is betterJul 10, 2026

Inspections & violations

Jul 10, 2026 8 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Exterior pump room built in 1967.

View this inspection on the county portal ›

Jul 8, 2026 18 demerits · 4 violations
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator.Chlorine observed at .7. Pool does not pass inspection.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. At beginning of inspection pH was 6.9, tested 20 min later, 7.2
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Gate was not self closing self latching upon arrival, PIC repair, was self closing self latching.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Pump room is not enclosed. Pool built in 1967.

View this inspection on the county portal ›

Jul 10, 2025 40 demerits · 11 violations
Inspector comments: Conducted seasonal pool inspection with CPO Eric. Pool surface still acceptable but in disrepair. Health department recommends resurfacing prior to the 2026 pool season or pool may not pass next year. 2025 permit issued and pool place on A status. Pool may open. No permit restrictions Construction Date 12/1/1967 Rope Length 38 ft No night swimming
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. One out of three weirs missing. Replace. No permit action.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. 10FT depth marker missing at deep end of inside of pool. Operator corrected and replaced. No permit action.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of a two inch wide contrasting color band across the pool bottom at breakpoint. Breakpoint floor line fading/in poor repair. EHS recommends repainting.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Fitting missing from deep end of pool. Operator corrected and replaced. No permit action.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Two ring buoy ropes observed with too long ropes. Operator removed one and corrected the other to approved rope length. No permit action.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. EHS observed new looking knob less than 54” from the ground with openings greater than 1/2” surrounding it. Operator covered openings with chicken wire that satisfies the no greater than 1/2" within 18" of latch mechanism requirement. No permit action. Gate hinge protrudes 4” on the outside from the fence and is less than 48” in height, creating a foothold. Outside knob protrudes 2.5” and is less than 40” in height, creating a foothold hold. Operator corrected by moving hinge higher than 48” and installing slanted metal piece above knob to mitigate foothold. No permit action.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed several cracks in deck with foliage growing through it. Deck is in need of repair to decrease any cracks. No permit action. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed 1” offsets on shallow end of pool deck. Operator grouted and corrected. No permit action.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. No sign indicating emergency phone on the outside of the phone. Operator corrected and posted emergency phone signage. No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Pump room is not enclosed. Pool built in 1967.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap provided to discharged for backwashing. Pool built in 1967.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(j) Provide soap and soap dispenser, no glass, at each sink. There was not any soap present in both restrooms.

View this inspection on the county portal ›

May 23, 2024 8 demerits · 3 violations
Inspector comments: No issues noted with pool at time of inspection. Permit and sticker issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed several cracks in deck with foliage growing through it. Deck is in need of repair to decrease any cracks.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Pump room is not enclosed.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap provided to discharged for backwashing.

View this inspection on the county portal ›

Apr 20, 2023 18 demerits · 6 violations
Inspector comments: 100 GPM Pool will be open from sunrise til sunset. **Equalizer drain covers will be changed before they expire on 6/2023. CPO is aware that updated Pdsc sheet will be provided for changes.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed an opening in the gate near the right corner of pool deck that is greater than 4”x4”. CPO closed opening during inspection with repair.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed several cracks in deck with foliage growing through it. Deck is in need of repair to decrease any cracks.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Pump room is not enclosed. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Observed chemical bags on floor of chemical room. Place bags on the shelf.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap provided to discharged for backwashing.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(j) Provide soap and soap dispenser, no glass, at each sink. There was not any soap present in both restrooms.

View this inspection on the county portal ›

Apr 21, 2022 22 demerits · 8 violations
Inspector comments: Paint for depth markers need to be touched up before next inspection. Pool not permitted for night swimming.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint. No safety top initially during arrival to inspection to show breakpoint in pool.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Observed ladder at a distance of 7 inches away from pool wall.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Decks in need of repair throughout. .2522(a) Provide 6 ft of clear walking space around the pool at all times. Deck chairs within 6 ft walking space around pool.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) All pool signage shall be visible upon entrance to the pool and permanently affixed. No pool signage present upon arrival to inspection. CDI- CPO provided appropriate signage during the inspection.
#19 · Premises: signs prohibit glass containers or pets in pool area −4
.2530(d) Provide a sign prohibiting pets and glass containers in the pool area. No signs posted upon arrival to inspection. CDI- CPO provided during the inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Observed chemicals stored on the floor during the inspection. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Pump room isn’t enclosed.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap provided to discharged for backwashing
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Post a shower sign visible upon entrance to the pool. Observed no shower sign posted upon arrival to inspection. CDI-Shower sign provided during the inspection.

View this inspection on the county portal ›

Apr 20, 2021 14 demerits · 3 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Facility without test kit during inspection. CPO provided test kit.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope providing required >38 ft. Rope cut to correct length.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Decks in need of repair throughout. .2522(a) Provide 6 ft of clear walking space around the pool at all times. Deck chairs within 6 ft walking space around pool.

View this inspection on the county portal ›

May 15, 2019 10 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed ladder missing endcap.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Pool deck cracked in numerous locations.

View this inspection on the county portal ›

Jun 8, 2018 6 demerits · 3 violations
Inspector comments: PDSC form verified.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. There is no pump room. Pump, filter and feeder are outside behind a fence.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Backwash is through an air break, not an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(j) Provide soap and soap dispenser, no glass, at each sink. No soap available.

View this inspection on the county portal ›

Mar 31, 2016 12 demerits · 4 violations
Inspector comments: Note: Observed pump manufacturer and model number did not match what was submitted to Health Department. PDSC form must be resubmitted and approved by Katie Wilson prior to permit being issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris in pool. Keep clean.Observed paint chipping in some areas of pool wall and floor.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Repair several areas on deck that is cracked.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Re. -label pipes that are not legible. Corrected during inspection.
#27 · Equipment room: filter backwash discharged through an air gap −2
Provide at least 2 inch air gap at backwash. Corrected during inspection.

View this inspection on the county portal ›

May 27, 2015 16 demerits · 4 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed paint peeling and damage to pool wall in several areas. Repair.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 2 damaged weirs. CDI
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed 5ft depth marker not legible. CDI
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed pool deck broken and cracked in several areas. Pool deck has been repaired in some areas but more repairs are still needed.

View this inspection on the county portal ›

Jun 13, 2014 26 demerits · 6 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed areas of pool floor in poor repair.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed one skimmer missing weir. Replace
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed wall depth markers fading
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
O.bserved eyeball inlet fitting missing
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed areas of deck in poor repair and 6FT deck clearance not maintained
#22 · Premises: emergency telephone provided −6
Emergency phone not operating. (immediate suspension)

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “CARRIAGE HOUSE” or State ID 2060500077). Inspection type (routine vs. follow-up) is not published in the county's data.