JOHNSTON CREEK CROSSING

10310 CEDAR TRAIL LN, Charlotte, NC 28210
Seasonal Swimming Pool · NC permit/State ID 2060500084
Latest result6 demerits
Last inspectedMay 21, 2026
Inspections on record13
On record sinceJun 19, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01632 Jun 19, 2014: 12May 29, 2015: 8Jul 20, 2016: 32May 12, 2017: 4Jun 13, 2018: 12May 9, 2019: 10May 15, 2020: 12May 25, 2021: 8Jul 26, 2022: 16May 11, 2023: 12May 23, 2024: 8May 16, 2025: 18May 21, 2026: 6
Jun 19, 2014Lower is betterMay 21, 2026

Inspections & violations

May 21, 2026 6 demerits · 2 violations
Inspector comments: NIGHT SWIMMING NOT PERMITTED. PERMIT RESTRICTION: FLOW METER MUST REMAIN OPERABLE AT 100 GPM + OR - 5% DUE TO PIPE AND FILTER SIZE RESTRUCTIONS. FLOW GREATR THAN 119 GPM IS SUCTION HAZARD.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool furniture within 6 feet of edge of pool deck.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap at backwash.

View this inspection on the county portal ›

May 16, 2025 18 demerits · 4 violations
Inspector comments: Karen Axton present for inspection Permit restriction: Flow meter must remain operable. Flow shall be set at 100 pm +/- 5% for suction hazard. No night swimming is permitted.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed two of five weirs missing. CPO replaced weirs during inspection - Corrected. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Observed leaves and flower debris in skimmers. CDI- CPO cleaned skimmers.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Vertical barrier members have been pried outward in two areas to exceed 4”. Likely due to attempts to access. CDI- Maintenance bent members to 4” opening.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Charlotte 911 had differing phone # from what was posted. Number posted that was same as for 911. Number called and Kings III box lit up.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter not operating. Restriction to 100 gpm +/- 5%. Maintenance worked with meter and became operational. Photo taken of 100 gpm flow.

View this inspection on the county portal ›

May 23, 2024 8 demerits · 2 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed top step missing at ladder near 5 foot depth marker. Missing step was found and installed onto ladder during time of inspection. Observed threading missing at 3 foot depth marker on top and bottom step.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope length at 34 feet. Corrected during time of inspection to required 38 feet.

View this inspection on the county portal ›

May 11, 2023 12 demerits · 4 violations
Inspector comments: Night swimming not permitted.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed one of five weirs missing. CPO replaced weir during inspection - Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Ladders shall have slip-resistant tread. .2521 Install ladders per manufacturer instructions. - Observed ladders on 3 and 5 ft side without tread on top step.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Lettering for this signage is <4”. CPO posted correct signage during inspection. - Corrected
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. - Observed no forced or cross ventilation in chemical storage room.

View this inspection on the county portal ›

Jul 26, 2022 16 demerits · 5 violations
Inspector comments: Images for in field pool verification of changes attached. Night swimming is not approved. Permit Restriction: flow meter must remain operable at 100 gpm +/- 5 % due to pipe and filter size restriction.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Observed leaves and flower debris in skimmers. CDI- CPO cleaned skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Ladders shall have slip-resistant tread. .2521 Install ladders per manufacturer instructions. - Observed ladders on 3 and 5 ft side without tread on top step. Observed ladder on 5Ft side in need of tightening down.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed buoy throw rope to be 44ft long. CDI- CPO provide rope at 38Ft.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. - Observed no forced or cross ventilation in chemical storage room.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed hose bibs near pool without proper back flow prevention devices.

View this inspection on the county portal ›

May 25, 2021 8 demerits · 2 violations
Inspector comments: This pool has a Kings III style phone that rings to the office when posted number is dialed. EHS advised that this pool phone is acceptable because pool operator stated the pool is only open when the office is open. Office has been on a 7 day a week business hour schedule. EHS advised that this pool phone meets the requirements for the pool phone if office phone can be answered by a person during normal business hours for the pool. No night swimming permitted.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed one missing weir at beginning of inspection. CDI - Operator replaced weir during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Observed gate with 3” space between grading and bottom of fence. Pool operator stated this is the original fencing. If fencing is replaced or the gate replaced, this gap shall be reduced to the required 2”. Operator stated a metal installation closing this gap will be completed this season.

View this inspection on the county portal ›

May 15, 2020 12 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed all skimmers basket with leaves and other debris. .2518(k) Replace missing weirs. Observed 3 inoperable weirs that were stuck in the upright position.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Ladders shall have slip-resistant tread. Observed 1 ladder on the right side, 5 ft area with two missing treads. .2521 Install ladders per manufacturer instructions. Observed 1 ladder on the left side, 5ft area that was very loose and could be a potential hazard.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed a ring buoy that was completely white, no indications of USCG writing and blue tabs around the ring. Not an approved life saving device. Pool permit denied. $100 fee will be charged to facility for re-inspection.

View this inspection on the county portal ›

May 9, 2019 10 demerits · 2 violations
Inspector comments: PDSC information verified in-field.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed no covering on vacuum port while line was turned off. CDI- cover installed on vacuum port.
#22 · Premises: emergency telephone provided −6
.2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Observed no signage indicating where emergency phone is located. CDI- sign added to notify bathers where phone is located.

View this inspection on the county portal ›

Jun 13, 2018 12 demerits · 3 violations
Inspector comments: .2524(b) Lighting shall be sufficient to illuminate all parts of the pool, the water, the depth markers, signs, entrances, restrooms, safety equipment and the required deck area and walkways. Pool operation hours listed as 10a-10p. Return visit tonight to check for adequate lighting. .2530(a) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Initial signage advised of phone being on the pool deck, Kings III system actually provided around the corner near the restroom entrances. Signage posted as the gate at to location of Kings III system.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Three of five weirs missing. CDI- CPO replaced missing weirs.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Two of main entry/exit ladders loose and coming up out of the pool deck. CDI- CPO repaired.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. .253. Throw rope almost 3 feet longer than required length. CDI- CPO corrected.

View this inspection on the county portal ›

May 12, 2017 4 demerits · 1 violation
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed skimmers in need of cleaning.

View this inspection on the county portal ›

Jul 20, 2016 32 demerits · 7 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no written records recorded for July 16th and 17th for main drains and ph, and hlorine levels.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed inorret pump information on PDSC form. Actual pump is a Pentair Challenger CHII-NI-3FE 3HP. New PDSC form shall be submitted and approved by MCHD.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed floating debris, pine needles, leaves, and bag in skimmer baskets.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope on ring buoy at 50 feet. CDI, operator cut rope to required length during inspection.
#18 · Premises: lifeguards present or warning signs posted −4
Observed "ADULTS SHOULD NOT SWIM ALONG" sign not 1" minimum height. Observed "CHILDREN SHOULD NOT USE THE SWIMMING POOL WITHOUT ADULT SUPERVISION" not a minimum of 1 inch height.
#22 · Premises: emergency telephone provided −6
Observed emergeny pool phone not operational..
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no backwash line at air gap.

View this inspection on the county portal ›

May 29, 2015 8 demerits · 3 violations
Inspector comments: 8. Observed two missing weirs from skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed one ladder that was loose and another ladder missing one of the slip resistent bands.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck with cracks and dents that can cause trip hazards.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Observed no shower sign posted. CDI sign posted.

View this inspection on the county portal ›

Jun 19, 2014 12 demerits · 4 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Empty skimmer baskets as needed. Observed all skimmer baskets with a lot of debris. Observed one skimmer basket cracked and broken. Provide weirs for all skimmers. Observed 2 of 5 weirs missing.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Provide plug for vacuum line when not in use.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Provide labels for all pipes in pumproom. Observed main drain line, return line and backwash lines not labeled.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in bathrooms should be shatter proof.

View this inspection on the county portal ›