COLONY CROSSING SWIM CLUB

3500 COLONY CROSSING DR, Charlotte, NC 28211
Seasonal Swimming Pool · NC permit/State ID 2060500129
Latest result10 demerits
Last inspectedMay 7, 2026
Inspections on record15
On record sinceMay 9, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0918 May 9, 2014: 16May 18, 2015: 18Apr 20, 2016: 6May 17, 2017: 0May 17, 2017: 4May 25, 2018: 4May 31, 2019: 12Apr 16, 2020: 6May 13, 2021: 0Apr 26, 2022: 8May 11, 2023: 14May 16, 2023: 8May 23, 2024: 8May 15, 2025: 10May 7, 2026: 10
May 9, 2014Lower is betterMay 7, 2026

Inspections & violations

May 7, 2026 10 demerits · 3 violations
Inspector comments: Note: have the broken phone connection jack replaced. Wires are exposed to the weather. Check phone daily that it is operable. No night swimming Flow meter must remain operable and flow not to exceed 119 GPM.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed spray painted depth marker didn’t include the 1/2 portion. CDI-faded or missing depth markers filled in with sharpie. Repaint if starts to fade.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed one sign overly sun faded. Needs replacing or removing. (There is one legible sign)
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Observed all pump equipment below the deck.

View this inspection on the county portal ›

May 15, 2025 10 demerits · 2 violations
Inspector comments: Automatic feeder with timer switch removed. Pool is now using CCH feeder with tablets. Permit Restriction: Flow Meter must remain operable. Flow not to exceed 119 GPM due to flow restriction of drain cover.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope at 52 feet. Rope cut to 50 feet.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter not operating. CPO fixed flow meter during inspection. Flow meter read 60 gpm.

View this inspection on the county portal ›

May 23, 2024 8 demerits · 2 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed 4ft and 3 1/2ft painted depth markers starting to fade. CPO repainted depth markers.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed lounge chairs less than 6ft away from pool surface. Chairs were pushed back to allow for more deck clearance.

View this inspection on the county portal ›

May 16, 2023 8 demerits · 3 violations
Inspector comments: Night swimming not approved. Flow meter must remain operable. Flow not to exceed 119 gpm due to flow restriction of the drain covers.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537 Keep pool surface and pool floor free of debris. Pool floor shall be maintained in good repair. - Pool floor is heavily stained pool plaster shall be monitored for any damages. May require maintenance or re-plaster prior to next year pool permit. Pool floor is smooth during inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. - Mirrors in club house bathroom without documentation of being shatterproof.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed hose bib near pool deck for filling of pool per CPO without a back flow prevention device.

View this inspection on the county portal ›

May 11, 2023 14 demerits · 3 violations
Inspector comments: Night swimming not approved. Permit denied due to flow meter not installed per manufacturer instructions.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - Observed debris on pool surface and floor. CDI- CPO started to clean debris.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed rope at 40 ft. CDI- CPO provided rope at 50ft.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Install flow meter on return line per manufacturer instructions. - Observed flow meter improperly installed. Permit denial item.

View this inspection on the county portal ›

Apr 26, 2022 8 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
slight debris present on pool walls, cleaned during inspection
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
debris in skimmer baskets, emptied during inspection, verified suction of the skimmers during inspection.

View this inspection on the county portal ›

May 13, 2021 0 demerits · 0 violations
Inspector comments: No corrections necessary

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 16, 2020 6 demerits · 2 violations
Inspector comments: NIGHT SWIMMING NOT PERMITTED. Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.” Until further guidance from local, state and federal health authority, when Pool opens, assure furniture is set up in a way to practice social distancining of 6 feet or greater.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter wasn't working. CDI- Fixed.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash

View this inspection on the county portal ›

May 31, 2019 12 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope length was incorrect but was corrected during inspection
#22 · Premises: emergency telephone provided −6
Phone was not working when checked. Att. was working on the phone as the inspection was being conducted. By end of inspection phone as working.

View this inspection on the county portal ›

May 25, 2018 4 demerits · 1 violation
Inspector comments: Slight static was observed on emergency phone, 911 dispatch was able to hear but noted interference. Address and number were both verified. Lattice fencing on the back section of the observed slightly loose, has been repaired with barbed wire in the loose sections to prevent entry. Emailed to Allie Neal at end of inspection. Verified receipt.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed no diving markers faded at time of inspection. Repainted by operator during inspection.

View this inspection on the county portal ›

May 17, 2017 4 demerits · 1 violation
Inspector comments: Gate has been repaired and is self closing and self latching. Back wooden gate is to stay locked and not be used.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence(lattice around deck) is removable and can be used,once the lattice is easily moved, to crawl under the deck to access the pool area. Due to the age of the pool, this is a deduction and not permit aciton. Highly recommend to secure this fencing on the exterior so it is not accesable.

View this inspection on the county portal ›

May 17, 2017 0 demerits · 0 violations
Inspector comments: Inspection entered into CDP as re-inspection from a Q status. Entered incorrectly. Inspection under re-inspection dated 5/17/17.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 20, 2016 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate not self closing. Correctes onsite.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
no shower present

View this inspection on the county portal ›

May 18, 2015 18 demerits · 4 violations
#3 · Water quality: pool water pH −6
Observed pH at 6.0. pH raised to 7.4
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris in pool from party.Corrected onsite.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed uncapped vac inlet with slight draw. CDI- capped
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gate opens in both directions. Corrected by modifying gate so it wont open in to pool.

View this inspection on the county portal ›

May 9, 2014 16 demerits · 5 violations
Inspector comments: 17..Pool deck drain may be a trip hazard as it's elevated. Repair so flush with pool deck.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Rail at steps is loose. Tighten.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate on wooden deck is remaining locked. Lower gate had to be adjusted so it would properly close.
#22 · Premises: emergency telephone provided −6
Phone number on emergency telephone has worn off. Relabeled.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No cross ventilation or vent in chemical room.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
•No shower on site.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “COLONY CROSSING SWIM CLUB” or State ID 2060500129). Inspection type (routine vs. follow-up) is not published in the county's data.