CRESWICK CONDOMINIUMS
2516 STRADBROOK DRIVE, Charlotte, NC 28210
Seasonal Swimming Pool · NC permit/State ID 2060500152
Latest result8 demerits
Last inspectedApr 22, 2026
Inspections on record13
On record sinceApr 21, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 21, 2014Lower is betterApr 22, 2026
Inspections & violations
Apr 22, 2026 8 demerits · 3 violations
Inspector comments: No night swimming
Expired reagent #2. Replace
Verified at pool:
Permit Restriction: Flow meter must remain operable. Flow required at 85 gpm to 100 gpm to meet turnover and flow restriction of the filter.
Flow greater than 125 gpm exceeds the main drains. Suction Hazard. 5% flow meter needed.
New Pump Hayward TristarVS 950 SP32950VSP, 2.7 THP
Blue white flow meter reading the above range on flow.
Main drain, skimmer and return line all 2” pipe
2008 Hayward WG1048E drain covers.
(3) skimmers with (3) Aquastar 2017 6HPHAxxx eq line covers.
Triton TR100 filter
6 returns located on either the floor or the wall.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Provide at least one handrail on steps. Observed handrail loose. CDI-tightened
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed 2 missing wall return fittings. CDI-replaced
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Observed mirrors shatterproof
.2526(l) Provide toilet paper and dispensers in restrooms. Observed no toilet paper
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed bathrooms need cleaning
Apr 9, 2025 6 demerits · 2 violations
Inspector comments: No night swimming.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) Provide "Adults should not swim alone." in 1" lettering.
Observed no signage with exact wording. CDI - operator put up appropriate signage.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed urinal constantly running. Observed toilets in need of cleaning. Needs repair/cleaning.
Apr 12, 2024 8 demerits · 3 violations
Inspector comments: Observed faded, incorrect emergency phone number under proper, legible number. CPO covered phone number with permanent marker to prevent any potential confusion.
Observed wooden bridge post at rear of perimeter fencing serving as a potential foothold.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool furnature measuring approximately 5 feet from pool edge of pool on deck. CDI, furniture relocated to provide necessary clearance.
.2537(2) Decks shall be kept in good repair. Observed small cracks appearing on pool deck but not large enough for a trip hazard currently
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Observed sealed dry chemicals stored beneath sealed liquid chemical containers.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed men and women’s bathroom in need of cleaning. Observed left men’s room sink with no running water.
Apr 19, 2023 6 demerits · 2 violations
Inspector comments: Inspection completed with Pierce Sawyer
Pool operates from dusk til dawn
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed small cracks appearing on pool deck but not large enough for a trip hazard currently
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed men and women’s bathroom in need of cleaning.
Apr 8, 2022 6 demerits · 1 violation
#2 · Water quality: disinfectant residual provided by −6
pH was originally 8.4, CDI to 7.8.
Apr 9, 2021 20 demerits · 5 violations
Inspector comments: No night swimming permitted.
General Comment: Impeller was verified in 2016. Per operator no changes.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed accumulation of debris in skimmer. Observed damaged lid. CDI, debris removed and lid replaced.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy / rope not in good repair. CDI, new ring buoy with new rope provided on-site.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-2010 construction). Observed 9" opening from grade to bottom horizontal on fence. Observed foot hold at back end of fencing. (pre-2010 construction)
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool furnature measuring 3 feet from pool edge of pool on deck. CDI, furniture relocated to provide required clearance.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed sodium bicarb and calcium chloride on ground in back storage room.
Apr 15, 2020 22 demerits · 6 violations
Inspector comments: NO NIGHT SWIMMING.
Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect
unless such Orders are rescinded or superseded by another applicable Order.”
Until further guidance from local, state and federal health authority, when Pool opens, assure furniture is set up in a way to practice
social distancining of 6 feet or greater.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
SKIMMER BASKETS WERE DIRTY, CLEANED DURING INSPECTION.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
FOOTHOLD LESS THAN 45 INCHES ON OUTSIDE OF FENCE TOWARDS BACK END OF POOL. NO PERMIT ACTION. POOL CONSTRUCTED PRE 2010.
#18 · Premises: lifeguards present or warning signs posted −4
NO SIGNAGED THAT STATES 'ADULTS SHOULD NOT SWIM ALONE'. PROVIDED DURING INSPECTION.
#22 · Premises: emergency telephone provided −6
EMERGENCY PHONE WAS NOT WORKING AT START OF INSPECTION. CORRECTED, ROUTER RE-STARTED. PHONE WORKED AND CALLED 9-1-1.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
NO VENTILATION SYSTEM IN PUMP ROOM. FACILITY WILL PROVIDE.
#27 · Equipment room: filter backwash discharged through an air gap −2
NO AIR GAP FOR BACKFLOW PIPES. PROVIDE.
Apr 10, 2019 6 demerits · 3 violations
Inspector comments: PDSC form verified. Pump no longer shows model# but picture matches in pool book.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed water on pump room floor.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Ventilation fans were not functional today.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
.2626(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose. No hose bibbs at restrooms.
Apr 11, 2018 10 demerits · 4 violations
Inspector comments: PDSC and VGB information verified.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chair stationed closer than six feet to the pool edge. Corrected during inspection by moving chair to correct position.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Ventilation fan in chemical room not operational.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for back wash discharge.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib observed in either restroom.
Apr 18, 2017 10 demerits · 4 violations
Inspector comments: Hose bib located at far end of pool deck does not have any back flow prevention; however, hose bib is inoperable. CPO was advised accordingly.
POOL PERMIT CAN BE ISSUED. Post permit in visible location on pool deck.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chipped near skimmer at right side pool creating >1/2" offset. ** Corrected during inspections.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
-- No natural cross draft ventilation or operable forced air ventilation in equipment/ chemical room. ** Provide.
-- Leak at junction circulation pump & pipe leading to filter.
** Keep equipment/ chemical room dry. Resolve.
#27 · Equipment room: filter backwash discharged through an air gap −2
Circulation system backwash pipe inserted down into larger pipe in floor. ** Backwash water should discharge through a complete air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Shower inoperable. CPO reports that shower has been shut off due to plumbing leak. ** Resolve.
Apr 13, 2016 10 demerits · 3 violations
Inspector comments: PDSC form needs to be updated prior to issuance of permit. Form had wrong pump info.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope was fraying. Buoy was replaced during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fix/repair ventilation in chem/storage room.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Need vaccum breaker on hose bibb (spigot)
Apr 1, 2015 12 demerits · 5 violations
Inspector comments: #17 Crack in pool deck on either side of one skimmer. ** Patch.
Water to pool house has been cut on.
Pool permit can be issued.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Over flow pipe does not have a fitting/ grate on pool wall. ** Install.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Forced air vents in equipment/ chemical room are inoperable. ** Repair.
#27 · Equipment room: filter backwash discharged through an air gap −2
Backwash pipe inserted down into larger pipe in floor.
** Backwash water should discaharge through a complete air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in restrooms are not shatterproof. ** Mirrors should be made of shatterproof materials.
Shower is missing drain cover & the drain is clogged.
** Unclog drain & install drain cover.
Leak in water line to shower. ** Repair.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bib (with hose) outside wall of pool house does not have any back flow prevention. ** Install vacuum breaker.
Apr 21, 2014 6 demerits · 3 violations
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed ventilation not functioning in pump/chemical room. Needs adequate ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed mirrors not shatterproof. Mirrors should be shatterproof.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Observed no backflow preventers at hose bibs.