8demerits
OASIS AT REGAL OAKS, THE
6701 ENGLISH HILLS DRIVE, Charlotte, NC 28212
Seasonal Swimming Pool · NC permit/State ID 2060500194
Latest result8 demerits
Last inspectedMay 14, 2026
Inspections on record13
On record sinceMay 7, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 7, 2014Lower is betterMay 14, 2026
Inspections & violations
May 14, 2026 8 demerits · 2 violations
Inspector comments: Inspection conducted with Juan Compres.
No night swimming.
PERMIT RESTRICTION: Flow meter must remain operable. Flow required at 104 gpm due to return pipe flow restriction. Turnover cannot be met due to restrictions in the pump room. Flow greater than 172 gpm is suction hazard.
Pool testing chemicals are expired. Operator stated that he will purchase a new test kit prior to opening.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Adults should not swim alone." in 1" lettering. CDI - Operator posted required signage.
#19 · Premises: signs prohibit glass containers or pets in pool area −4
.2530(d) Provide a sign prohibiting pets and glass containers in the pool area. CDI - operator posted required pets signage.
May 30, 2025 6 demerits · 1 violation
Inspector comments: Permit Restriction: Flow meter must remain operable. Flow required at 104 gpm due to return pipe flow restriction. Turnover cannot be met due to restrictions in the pump room.
NIGHT SWIMMING NOT PERMITTED.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length at 50 feet. Rope was cut to required length of 30 feet during time of time of inspection by CPO.
May 9, 2024 4 demerits · 1 violation
Inspector comments: Juan Compres present for inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 2 missing weirs. Replaced while on site.
May 23, 2023 4 demerits · 1 violation
Inspector comments: Observed all other non compliant conditions corrected.
Doors must be self closing within 30 days.
Permit issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed doors alarmed but not self closing.
.2528(a) Ground level doors shall be self-closing, self-latching andchild protected by audible alarm.
May 4, 2023 18 demerits · 4 violations
Inspector comments: Permit denied today due to bonding wire not attached to motor on pump in equipment room. Inspection from MC code enforcement required. Please provide electrical permit number. Senior Chris Sells: (704)-576-8678 Email Christopher.Sells@mecklenburgcountync.gov if you have any questions or concerns.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed one missing wier in skimmer basket. CDI: Wier replaced.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope on buoy to be greater than the 30ft requirement for this pool. CDI: rope cut to 30 ft.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed windows opening greater than 4 inches without audible alarm.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. Observed return fitting on vacuum line. CDI: CPO installed a threaded vacuum cap cover.
.2518(h) Provide approved pump in good repair. Observed bonding wire not connected to pool pump.
May 27, 2022 12 demerits · 3 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
decorative owls had been placed directly adjacent to the pool deck, within 6' to prevent ducks from landing in the pool. Owls were moved to be further than 6' from the deck
#22 · Premises: emergency telephone provided −6
Emergency phone initially gave EHS a busy tone after EHS verified callback number. Phone was verified through multiple subsequent attempts to be functioning properly and dialing 911 upon pick up.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in the bathroom are not shatterproof glass.
May 24, 2021 6 demerits · 2 violations
Inspector comments: EHS conducting onsite visit for pool inspection. Observed loose fence opening and loose pool step ladders with no end caps. Both violations repaired and corrected during inspection. No other violations observed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed loose step ladders with missing end caps. CDI, ladders repaired and fixed in place with fitted end caps.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed loose fence opening behind picnic table area. Observed fenced probably kicked in at joint for forced entry. CDI, fence repaired, opening closed and fixed permanently.
May 23, 2019 14 demerits · 4 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed fence peeled back in one section at top of hill
greater than 4". CDI - Maintenance repaired fence during inspection. -4-
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed 5'9" clearance near deck chairs on the pool deck.
CDI - Operator moved chairs back to greater than 8'.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed holes on deck that appear to be for a ladder at 2.5". CDI - Operator placed plugs in the holes during inspection. -4-
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Adults should not swim alone." in 1" lettering. Observed no sign stating exact wording for adult swimming as listed
in pool rules. CDI - Operator posted sign with exact wording during inspection. -4-
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed filter backwash piping below the floor plane of the sump.
CDI - Operator shortened pipe during inspection. -2-
May 18, 2018 0 demerits · 0 violations
Inspector comments: No violations found. No night swimming; Pool will close at or before dusk each night. Local permit number 18-600394.
No violations were recorded for this inspection.
May 30, 2017 14 demerits · 3 violations
Inspector comments: Facility has a covered, non operational Spa. Spa is covered with tensioned springs and a taut tarp. Facility should look into repairing and opening the spa, or permanently closing the spa by filling in with concrete or other means.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed depth markings on the pool deck painted over and no longer visible. Operator was able to template and paint the depth markings during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope at time of inspection was measured at 58 feet. Rope length required as calculated by PEHS staff is 18 feet. Rope cut down to 18 Feet
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed several pool chairs 3-4 feet from the pool edge. Maintain at least 6 feet of distance from the pool edge.
Jun 15, 2016 12 demerits · 3 violations
#2 · Water quality: disinfectant residual provided by −6
Cl @ .8 CDI to 2.0
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
ladder on club house side loose.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck.
May 27, 2015 16 demerits · 3 violations
#2 · Water quality: disinfectant residual provided by −6
No chlorine observed at time of inspection. CDI chlorine adjusted to 2 ppm by end of inspection.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
vacuum port did not have plug at time of inspection. CDI plug installed.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmers need to be cleaned.
May 7, 2014 0 demerits · 0 violations
No violations were recorded for this inspection.