SOUTH PARK SWIM & TENNIS CLUB

2200 HUNTINGTOWNE FARMS LN, Charlotte, NC 28210
Seasonal Swimming Pool · NC permit/State ID 2060500290
Latest result10 demerits
Last inspectedApr 16, 2026
Inspections on record13
On record sinceMay 6, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0918 May 6, 2014: 2May 11, 2015: 14Apr 27, 2016: 6May 15, 2017: 12Apr 9, 2018: 10Apr 15, 2019: 14Apr 8, 2020: 8Apr 20, 2021: 14May 5, 2022: 8Apr 21, 2023: 4May 13, 2024: 18May 9, 2025: 8Apr 16, 2026: 10
May 6, 2014Lower is betterApr 16, 2026

Inspections & violations

Apr 16, 2026 10 demerits · details not yet loaded

Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.

May 9, 2025 8 demerits · 2 violations
Inspector comments: Inspection with CPO, Wayne Lowery. No night swimming approved. Call Jeremy Stawinsky at 704-519-7338 to schedule visit at dawn or dusk for night swimming approval. Main drain and slide pull through same set of drains. Slide suction is tied into filtration suction line.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy longer than 50 ft. CDI-CPO shortened rope to 50 ft.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed standing water just past front door inside equipment room due to rain from the previous night. Equipment room is sloped to drain with a channel that is slowly draining.

View this inspection on the county portal ›

May 13, 2024 18 demerits · 4 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers baskets full of debris. Skimmer baskets were dumped during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope exceeding 50ft. CPO cut rope to 50FT during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed main entrance gate not self latching. CPO adjusted gate during inspection. Gate is now self latching.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
.2537(9) Underwater light niches shall be maintained or covered so not to present a hazard. Observed underwater light coming out of its housing. CPO tightened light during inspection.

View this inspection on the county portal ›

Apr 21, 2023 4 demerits · 1 violation
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - minor debris in pool

View this inspection on the county portal ›

May 5, 2022 8 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor and floating debris.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris in skimmer baskets.

View this inspection on the county portal ›

Apr 20, 2021 14 demerits · 4 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Observed 10" difference between ladder rung and pool wall. PO repaired ladder to read 6" distance.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed swimming pool rope length at 56ft. PO cut rope to read 50 ft.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
.2524(c) Lighting fixtures shall not present a hazard to the public. Observed wide gap between wall and pool light by slide area. Light not tightly fitting inside of socket, creating a potential electrical hazard. PO properly fit light into socket, removing all gaps and potential electrical hazards.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(c) Over the rim fill spouts shall be located under the diving board or within six inches of a ladder or handrail. Observed over the rim fill spout located within 10 inches of ladder. Fill spout was able to be moved within 6 inches from ladder during inspection.

View this inspection on the county portal ›

Apr 8, 2020 8 demerits · 2 violations
Inspector comments: PDSC information verified in-field. No signature due to COVID-19.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed 2 gates not self closing. CDI- gates were repaired. .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed one area underneath pool fencing with 6 inch gap. Pool built prior to 2010.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed holes in pool deck (used for swim blocks) not covered. CDI- covers installed.

View this inspection on the county portal ›

Apr 15, 2019 14 demerits · 4 violations
Inspector comments: Night swimming is permitted. Verified on site that all pool lights inside pool were operable and observed sufficient lighting on pool deck.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed PH at 7.0. CDI: corrected to 7.2 during inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed lots of debris in skimmer baskets. CDI: cleaned during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed one endcap missing on ladder at 3ft depth next to fill spout.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(k) Provide shatterproof mirrors. No shatterproof mirrors provided in restrooms.

View this inspection on the county portal ›

Apr 9, 2018 10 demerits · 4 violations
Inspector comments: Per pool operator, Jeff Gaeckle, pool will operate with lifeguards at all times. Note - Pool not approved for Night Swimming. Contact inspector to schedule a night visit to verify lighting. Per operator, additional lighting is being added to pool deck. Electrical permits required before approval.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed >6" from pool wall to ladder rung in shallow end. Maintain 3" to 6". Observed some starting platforms >30" from pool water surface at depth 4 ft. Pools with water depth of 4 ft, starting platforms shall be no more than 30" from waters edge. Observed no labeling on diving board. Diving board must be installed per manufacturer instructions and with proper labeling under Rule .2517. Some tread on starting platforms beginning to wear. Provide slip-resistant tread.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Offset around one anchor for starting platform at shallow end. No trip hazard present. Deck drain offset by snack bar. Repair for 2019 operating season. Some deck drain damage at entry into women's locker room (<1/2") and at entry into attendent area. Repair for 2019 season. Observed hole in deck at skimmer at deep end. Corrected during inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in restrooms not shatterproof. Provide shatterproof glass.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bib on pool deck without backflow prevention. Provide backflow prevention device.

View this inspection on the county portal ›

May 15, 2017 12 demerits · 2 violations
Inspector comments: This is not a pool permit. Pool permit will be available at Mecklenburg County health department website at meckpools.charmeck.org. Current PDSC forms not approved and updated forms must be submitted and approved by MCHD prior to permit being released.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
• Observed PDSC form list 10 skimmers but pool had 11 skimmers. Observed incorrect drain covers listed on PDSC form. Actual drain covers are Aquastar 1216xxx. Operator stated in process of updating PDSC form. Updated PDSC form for drain cover information and pump must be submitted and approved by MCHD. Slide pump identified on site as Pentair Whisperflo WFE 3; 3/4 HP
#22 · Premises: emergency telephone provided −6
Observed emergency pool phone not working upon arrival. Operator identified wire with some damage. Phone repaired while on-site and now working.

View this inspection on the county portal ›

Apr 27, 2016 6 demerits · 1 violation
Inspector comments: Observed dirty skimmer baskets. Clean all skimmer baskets.Observed one ladder with bottom bortion not securely attached to pool wall.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
VGV forms facility submitted stated main drain was a Aquastar WAV RXX. Inspection verified the main drain cover was actually an AquaStar P12xxx. Facility must updated VGB sheets as well as include equalizer covers.

View this inspection on the county portal ›

May 11, 2015 14 demerits · 4 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed debris in skimmer baskets. C.D.I. items were cleaned.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed 1 throw rope on buoy to be longer than the required 50 feet. C.D.I. Rope shorteded to 50 feet.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed floor of pump room wet due to leak from wall. Keep flow dry and fix any leaks.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Observed no backflow preventers on hose bibbs.

View this inspection on the county portal ›

May 6, 2014 2 demerits · 1 violation
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrails loose near kids pool. Handrails tighten during my visit.

View this inspection on the county portal ›