18demerits
LAKESHORE VILLAGE CONDOMINIUMS
9043 J M KEYNES DR, Charlotte, NC 28262
Seasonal Swimming Pool · NC permit/State ID 2060500322
Latest result18 demerits
Last inspectedApr 16, 2026
Inspections on record13
On record sinceApr 17, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 17, 2014Lower is betterApr 16, 2026
Inspections & violations
Apr 16, 2026 18 demerits · 4 violations
Inspector comments: Permit Restriction: Flow meter must remain operable. Flow required at 80 gpm. Flow greater than 150 gpm exceeds the main drains. Suction Hazard.
New Pump Hayward TristarVS 950, SP32950VSP, 2.7 thp
FlowVis flow meter reading the above flow restriction at 80 gpm.
(1) 2” main drain line; (2) 2” skimmer lines; (1) 2” return line
(2) Aquastar 2017 1216xxx drain covers
(4) skimmers with EQ lines disabled plugged in skimmer/plugged or plastered on wall.
(4) floor returns
(1) Pentair TR100C filter.
EHS confirmed items during inspection.
Construction: 1/1/1990
Rope: 45’
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. CPO worked on suction outlet cap during inspection. EHS confirmed cap was secure and in compliance.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Rope exceeded 45’ at initial portion of inspection. CPO cut and knotted rope during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed multiple offsets greater than 1/2”. CPO filled offsets during inspection to prevent trip hazards.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Pool chemicals stored on floor in storage.
May 20, 2025 8 demerits · 2 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed fading depth markers. Needs to be printed
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed cracking and offsetting in several areas on decking. Most of the cracks have been repaired. No permit action.
Apr 17, 2024 16 demerits · 4 violations
Inspector comments: Night swimming is not permitted. Permit issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris on pool floor. CDI: CPO began cleaning floor during inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed walls inside skimmers beginning to crack. May need repair before next pool season. No permit action.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed far gate unable to self-latch. CDI: CPO repaired gate and self-latch is functioning.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed cracking and offsetting in several areas on decking. May need repair before next pool season. No permit action.
May 25, 2023 6 demerits · 2 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed fading depth markers. Needs to be printed
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Provide at least one handrail on steps. Observed hand rails in need of repair by the main entrance.
Apr 21, 2022 14 demerits · 3 violations
Inspector comments: Night swimming not permitted.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope measured at 46’. CDI - rope shortened to 45’ as required during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed original phone unable to receive calls. CDI - alternate phone provided during inspection. EHS verified phone capable of dialing 911 and of receiving call back.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(b) Provide sufficient lighting in pump room. Light out in pump room.
Jul 1, 2021 14 demerits · 3 violations
Inspector comments: Night swimming has not been approved.
Pierce Sawyer is the pool operator onsite during the inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.
Observed lake side gate entrance not properly latching. The inside door handle does not return to its proper horizontal position once turned to unlatch the gate, which then keeps the gate door from relatching. This has been corrected and the pool operator properly loosened the door handle to allow it to move freely back to its proper position.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering.
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) Provide "Adults should not swim alone." in 1" lettering.
Observed signs with incorrect height and verbiage. This was correct and the operator hung up the correct pool signs needed.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable.
Called 911 and operator was unable to hear the inspector the first time, hung up and dialed a second time and the operator was able to hear the inspector.
Observed the emergency phone not ring when called. Answered the phone and the number is correct, it just has no ring tone.
*This phone is over 20 years old and is beginning to show signs of its age. It is recommended that a new phone be installed. The phone should be 100% operable at all times.
May 8, 2020 10 demerits · 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Observed skimmers with debris. Cleaned during the inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Observed incorrect phone number on sign. Number was changed.
Michael was present during the inspection.
Apr 23, 2019 6 demerits · 2 violations
Inspector comments: PDSC form verified (pump data plate was worn off).
Observed some brick fencing with footholds (pre-2010 pool).
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Sections of the brick fence were observed to be 41"-45". (Pre-2010 pool)
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. No cross ventilation available.
Apr 12, 2018 6 demerits · 2 violations
Inspector comments: NO POINTS WERE TAKEN FOR THE FOLLOWING:
#22 - Observed emergency phone with low, muffled volume. EHS was still able to communicate with 911 to confirm address and phone number. EHS suggested having pool replace phone. .2530(a) Emergency phone shall remain operable.
#24 - Observed no extra pump stored at pool. CDI Operator provided pump from vehicle. .2518(e) Provide a spare basket for pump.
PDSC information verified. No night swimming.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
REPEAT Observed pool wall measure 47" from outside of pool wall near emergency phone area. CDI Operator dug 6" down around pool wall within a foot of the wall.
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
REPEAT Observed no forced air in in chemical storage room.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Apr 13, 2017 10 demerits · 3 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed one deck 5 ft depth marker faded, Corrected - PO re-painted depth marker.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed a few areas of brick wall pool fencing less than 48" observed at 39" at one apartment back patio near pump room and at 43" near emergency phone due to landscaping.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed that there is no forced air or cross ventilation in chemical room.
GENERAL COMMENT: Observed a few areas around pool wall below coping that are degrading, needing repair soon. PO could not access restrooms to check.
PERMIT TO BE ISSUED
Apr 27, 2016 0 demerits · 0 violations
Inspector comments: Pierce Sawyer present.Pool permit will be available for printing on meckpools.org in 3-5 business days.
No violations were recorded for this inspection.
Apr 1, 2015 4 demerits · 1 violation
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Keep skimmers clean; Observed skimmer baskets collecting debris in need of cleaning.
Apr 17, 2014 8 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Provide throw rope length at 45 ft. Observed throw rope length at 42ft. Stretched and corrected to 45ft during inspection. Maintain body hook in good repair. Observed body hook missing one screw. Screw replaced during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed that there is no forced air or cross ventilation in chemical room.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “LAKESHORE VILLAGE CONDOMINIUMS” or State ID 2060500322). Inspection type (routine vs. follow-up) is not published in the county's data.