10demerits
NORTH POINT CONDOMINIUMS
400 NORTHWEST DRIVE, Davidson, NC 28036
Seasonal Swimming Pool · NC permit/State ID 2060500386
Latest result10 demerits
Last inspectedMay 6, 2026
Inspections on record14
On record sinceApr 29, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 29, 2014Lower is betterMay 6, 2026
Inspections & violations
May 6, 2026 10 demerits · 3 violations
Inspector comments: NO NIGHT SWIMMING.
ENSURE POOL FURNITURE STAYS AT LEAST 6’ FROM POOL EDGE WHEN PLACED.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
Observed floating debris in skimmers. CDI
.2518(k) Replace missing or damaged skimmer basket.
Observed 2 skimmer baskets in poor repair. CDI- replaced with new by CPO.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
Observed opening in fence > 1/2” allowing access to latch mechanism. CDI- reposition of existing expanded metal grate sheet to close gap by CPO.
Fencing alongside tennis court does not meet current standards, fence was constructed in 1983.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair.
Restrooms need cleaning.
Apr 28, 2025 0 demerits · 0 violations
Inspector comments: No night swimming.
No permit restrictions.
No violations were recorded for this inspection.
Apr 23, 2025 10 demerits · 2 violations
Inspector comments: Permit denied.
No night swimming.
Violations to be corrected before permit issued:
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
Observed 6” under fence near entrance to women’s restrooms.
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone.
Observed third party call center and 911 unable to verify address- no address on file.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
Observed 6” under fence near entrance to women’s restrooms.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone.
Observed third party call center and 911 unable to verify address- no address on file.
Apr 26, 2024 18 demerits · 4 violations
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
breakpoint rope from 5' depth to 8' depth was not present, installed during during inspection
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
fencing alongside tennis court does not meet current standards, fence was constructed in 1983.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
pool had 2 buoys present, but only 1 with a correct rope length attached. Buoy without rope was removed. Pool only requires 1 set of lifesaving equipment.
#22 · Premises: emergency telephone provided −6
phone number was not written down at time of inspection, written during inspection and verified with local dispatch.
Apr 26, 2023 12 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
no breakpoint rope not provided
Provide breakpoint rope between 8' and 5' area
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
ring buoy in poor condition. Replaced during inspection
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
fence does not meet current state rules.
pool constructed in 1983
Apr 12, 2022 22 demerits · 6 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
small amount of leaves in pool. Corrected during inspection
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Missing break point rope. Correct during inspection
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail at steps not attached properly. corrected during inspection
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope exceeded 50' corrected during inspection
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs encroach on 6' of clear deck space. Corrected during inspection
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fence measured 38". Fence is grandfathered in due to age of pool
Apr 14, 2021 18 demerits · 5 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris in skimmers. CDI - Operator cleaned skimmers.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint. Observed no safety rope at the breakpoint.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Observed ladder greater than 6 inches from the wall. CDI - Operator repaired ladder so it was closer to wall.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed pool fence that extends around tennis court at only 38 inches in height. Pool fence is grandfathered in as pool was built in 1983.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed pool phone number was not clear and had worn away a number. CDI - Operator fixed phone number so it is easily readable.
Apr 21, 2020 8 demerits · 2 violations
Inspector comments: .2522(a) Provide 6 ft of clear walking space around the pool at all times.
Observed pool chairs less than 6 ft around the deck. Chairs were moved.
No signature required due to COVID-19.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint.
Observed no safety rope at breakpoint.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed rope for ring buoy longer than 50 ft. New rope was provided and was 50 ft.
Apr 30, 2019 36 demerits · 11 violations
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Men's toilet drains slow-need soap, mirrors to be of shatterproof construction
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Record daily/weekly readings, corrected during inspection
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders missing bumpers
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fence-built prior to 2010, is < 48", mesh size is 3"
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Maintain clear walkway around pool edge
#18 · Premises: lifeguards present or warning signs posted −4
Sign posted during inspection
#22 · Premises: emergency telephone provided −6
Address & phone # corrected during inspection
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Pressure gage replaced during inspection
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Natural cross or continuous forced ventilation required, keep bagged chemicals off the floor
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Pipes remarked during inspection
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Signs posted during inspection
Apr 9, 2018 10 demerits · 4 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed staining on the pool floor
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed missing escutcheon plates on the one ladder
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed wet floor in pump room
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Observed no back-flow preventers on hose bibb
Apr 24, 2017 20 demerits · 6 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed floating debris in pool.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed floating debris in skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed encaps missing on two ladders.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed opening from fence to ground >4"
Observed section of pool fence <48" at tennis courts.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed furniture <6' from pool edge.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump room floor wet. No fan or cross ventilation.
Apr 19, 2016 10 demerits · 3 violations
Inspector comments: Permit pending per corrected PDSC form
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
observed debris on pool floor
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
keep furniture >6' from pool edge
#26 · Equipment room: valves and pipes identified by color codes or labels −2
label pipes in pump room (flow direction).
Apr 27, 2015 24 demerits · 6 violations
#2 · Water quality: disinfectant residual provided by −6
observed chlorine reading of 0.5 CDI retested at 4.0
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
observed floating debris in surface skimmers. CDI
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
observed 2 loose ladders. CDI
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope 52.5' . CDI cut to 50'
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
observed openings under fence > 4"observed section of pool fence < 48" at tennis courts
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
observed water on the floor in pump room. no fan or cross ventilation.
Apr 29, 2014 22 demerits · 6 violations
#3 · Water quality: pool water pH −6
pH reading too low - corrected to 7.2 during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
observed debris on pool floor
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
observed debris in skimmers
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
tighten up the handrail and add protective bumpers to the ladders
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Keep furniture at least 6' from pool edge-also replace the caulking around the coping
#27 · Equipment room: filter backwash discharged through an air gap −2
shorten the filter backwash pipe to maintain an air gap
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “NORTH POINT CONDOMINIUMS” or State ID 2060500386). Inspection type (routine vs. follow-up) is not published in the county's data.