‹ Back to search

4demerits

OAKMORE ON SELWYN

2719 SELWYN AVENUE, Charlotte, NC 28209
Seasonal Swimming Pool · NC permit/State ID 2060500393
Latest result4 demerits
Last inspectedJul 8, 2026
Inspections on record10
On record sinceJul 26, 2013

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01326 Jul 26, 2013: 26Jun 18, 2014: 16Jun 17, 2015: 18Jun 5, 2020: 18May 20, 2021: 0May 2, 2022: 14May 5, 2023: 8May 13, 2024: 6May 13, 2025: 8Jul 8, 2026: 4
Jul 26, 2013Lower is betterJul 8, 2026

Inspections & violations

Jul 8, 2026 4 demerits · 1 violation
Inspector comments: Permit Restriction checked and adhered to: For meter must remain operable. Flow shall not exceed 104 gpm due to drain cover and equializer flow restriction. Electrical conduit outside of required deck space to be blocked to prevent trip hazard.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.Debris on pool floor

View this inspection on the county portal ›

May 13, 2025 8 demerits · 2 violations
Inspector comments: Flow meter must remain operable. Flow shall not exceed 104 gpm due to drain cover and equalizer flow restriction. Suction Hazard. 2) Electrical conduit line outside of required deck space must remain blocked at all times to eliminate trip hazard. NIGHT SWIMMING NOT PERMITTED.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Rope was 10 feet too long of required length. Cut to 41 inches. CDI
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(j) Provide soap and soap dispenser, no glass, at each sink. No soap in bathroom

View this inspection on the county portal ›

May 13, 2024 6 demerits · 1 violation
Inspector comments: Night swimming is prohibited.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope exceeding 41ft. CPO cut rope to 41ft during inspection.

View this inspection on the county portal ›

May 5, 2023 8 demerits · 3 violations
Inspector comments: Night swimming is not approved. Electrical conduit line outside required deck space must remain blocked to eliminate trip hazard at all times.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - Observed minor leaf and stick debris on pool floor and surface. CDI- PIC cleaned debris during the inspection. EHS able to see pool floor and main drains verified.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. - Mirrors in restroom are without documentation of being shatterproof.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed hose bib near pool deck without a back flow prevention device.

View this inspection on the county portal ›

May 2, 2022 14 demerits · 3 violations
Inspector comments: Permit restricted such that the electrical box located within 6' of the pool deck must be blocked off at all times, congruent with previous restrictions noted by K. Rudisill.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
gates leading to pool from apartments adjacent to pool were not self closing at time of inspection. Repaired during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Electrical box is present within 6' of the pool deck, as mentioned by K. Rudisill in previous inspection. Box is currently blocked off by safety cones.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed safety ropes 4' longer than required length. Adjusted to proper length during inspection.

View this inspection on the county portal ›

May 20, 2021 0 demerits · 0 violations
Inspector comments: No violations found during inspection.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Jun 5, 2020 18 demerits · 5 violations
Inspector comments: Temporary emergency pool phone signage on deck. Provide permanent signage for phone showing location of emergency phone. Location added to the pool rules sign also. Onsite visit to pool for construction and permit inspection. Construction final passed. Equipment installed matched plan approval. Backwash tank with air gap installed above equipment. Tank hard drains to floor drain. Mike Molle present during inspection. No signature due to COVID-19 restrictions. Equalizer line covers approved only with Aquacal measurements. Permit Restriction 1) Electrical conduit line outside required deck space must remain blocked to eliminate trip hazard at all times Permit issued for no night swimming. Issuance of a permit by this department does not negate closure required by Executive Order No. 141 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some skimmers with debris in baskets. Keep clean.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Brick wall provides foothold at street entrance gate. Decorative cut-outs in condominium patio walls. Decorative cut-outs shall not exceed 1.75". Window limiters on windows could not be verified. Windows on to pool deck shall not open greater than 4". All items listed were not part of renovation and are original construction.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Electrical conduit provides trip hazard. Original constrution. Eliminate trip hazards. Permit Restriction - trash can or barrier must remain present next to conduit at all times pool is operational. Trash can in place at time of inspection. 5 1/2 ft. from pool to brick barrier. Original construction. Maintain 6 ft. of clearance around pool at all times. Deck drains growing weeds in some locations. Did not observe standing water. May require repair in future inspections. Ensure deck is sloped to drain and drains properly.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Small leak on pipe in pump room. Leak does not appear to affect pool circulation. Pool chemistry ok and no pooling of water on pump room floor. Repair leak.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Light in restroom not operational. Repair light. Chemical storage room could not be accessed at time of inspection. Viewed on previous inspection. Provide storage to maintain chemicals up off pump room floor.

View this inspection on the county portal ›

Jun 17, 2015 18 demerits · 5 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Clean pool floor.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
REPAINT FADING DEPTH AND NO DIVING MARKING ON POOL DECK. INTENT TO SUSPEND ISSUED DUE TO THIS VIOLATION.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Keep a six feet clearance around pool deck. Observed chairs too close to pool.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Repair leak on pump.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Repair light in pump room.

View this inspection on the county portal ›

Jun 18, 2014 16 demerits · 4 violations
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed inlet fitting missing on vacuum cover. Replaced during inspection
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy rope at 51FT. Cut to 41FT
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Maintain at least 6FT deck clearance. Observed <6FT
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed wret floor in pump room. Maintain dry.

View this inspection on the county portal ›

Jul 26, 2013 26 demerits · 7 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed damage (etching and chipping) on pool floor. Keep in good repair.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed equalizer line plugged. Corrected during inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed depth markers faded on pool walls in some areas. Still legible. Replace by next season or if fading continues to not legible.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy damaged. Replaced during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed openings in fence >1.75" in multiple locations at gates.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no cross or forced ventilation in pump room. Provide cross/forced ventilation.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at backwash line. Provide air gap.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “OAKMORE ON SELWYN” or State ID 2060500393). Inspection type (routine vs. follow-up) is not published in the county's data.