PARK WALK

9467 S VICKSBURG PARK COURT, Charlotte, NC 28210
Seasonal Swimming Pool · NC permit/State ID 2060500415
Latest result6 demerits
Last inspectedApr 9, 2026
Inspections on record13
On record sinceApr 21, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01122 Apr 21, 2014: 12Apr 15, 2015: 12Apr 13, 2016: 18Apr 18, 2017: 22Apr 24, 2018: 6Apr 10, 2019: 6Apr 15, 2020: 0Jun 8, 2021: 14Apr 12, 2022: 4Apr 13, 2023: 0May 16, 2024: 12May 15, 2025: 4Apr 9, 2026: 6
Apr 21, 2014Lower is betterApr 9, 2026

Inspections & violations

Apr 9, 2026 6 demerits · 2 violations
Inspector comments: EHS observed open hole by back corner of decking by bathrooms. EHS observed capped wires protruding from hole. Operator stated it is possibly due to old lighting that was removed and placed a barrier over hole for temporary fix. Hole is located near the mulching at the very edge of the decking surface away from the pool. Operator stated cover will be permanently installed prior to pool opening. Flow meter must remain operable. Flow shall not exceed 104GPM due to equalizer line flow restriction. Suction hazard. EHS verified equalizer covers have been replaced and match PDSC form. Equalizer line covers expire 4/2/2031. Main drain covers expire 3/9/2028.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. EHS observed numerous cracks on pool decking. No crack observed deeper than 1/2”, no trip hazards observed. EHS advised to fill in cracks as needed.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. EHS observed debris throughout bathroom floor, interior of toilet fixtures soiled with debris and residue. CPO stated bathrooms will be cleaned prior to opening.

View this inspection on the county portal ›

May 15, 2025 4 demerits · 1 violation
Inspector comments: No night swimming.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. .2530(c) Provide "Adults should not swim alone." in 1" lettering. Observed signage posted with incorrect wording and lettering too small. CDI- New sign was posted.

View this inspection on the county portal ›

May 16, 2024 12 demerits · 3 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed no USCG approved ring buoy or rope at start of inspection. Properly sized rope and heavily damaged ring buoy were found within pump room. CDI - CPO provided new USCG approved ring buoy and attached rope such that it was the proper 30’ in length.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed cracks forming throughout deck. No trip hazards or gaps of greater than 1/2” were observed; resurface or fill in cracks as needed.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(j) Provide soap and soap dispenser, no glass, at each sink. .2526(l) Provide toilet paper and dispensers in restrooms. Observed no soap in either male or female restroom. Observed no toilet paper in either restroom.

View this inspection on the county portal ›

Apr 13, 2023 0 demerits · 0 violations
Inspector comments: In field verification with Pierce Sawyer, PO explained they do not intend on adding stairs to the pool, therefore they do not need in field plan review.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 12, 2022 4 demerits · 1 violation
#18 · Premises: lifeguards present or warning signs posted −4
No Lifeguard sign posted. Sign was posted on fence.

View this inspection on the county portal ›

Jun 8, 2021 14 demerits · 4 violations
Inspector comments: Night swimming not permitted.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed throw rope length at 31 ft. 10 in. CDI, new throw rope adjusted to required length.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. .2530(c) Provide "Adults should not swim alone." in 1" lettering. Observed pool rules sign with "Children should not use the swimming pool without adult supervision" and "Adults should not swim alone" measuring 1/2 in. lettering. CDI, new standard pool rules sign provided.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed no cross ventilation provided in equipment / chemical room.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap provided.

View this inspection on the county portal ›

Apr 15, 2020 0 demerits · 0 violations
Inspector comments: NIGHT SWMIMMING NOT PERMITTED. Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.” Until further guidance from local, state and federal health authority, when Pool opens, assure furniture is set up in a way to practice social distancining of 6 feet or greater.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 10, 2019 6 demerits · 3 violations
Inspector comments: PDSC form verified. Pump did not have model # available but did match picture in pool book.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Pump/chemical room does not have cross-ventilation.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Observed no back flow preventer on hose bibb at restrooms.

View this inspection on the county portal ›

Apr 24, 2018 6 demerits · 2 violations
Inspector comments: VGB and PDSC information verified.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris on floor of pool. Vacuum pool to clean debris.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed air gap for back flow discharge.

View this inspection on the county portal ›

Apr 18, 2017 22 demerits · 8 violations
Inspector comments: CPO reports deck lighting is insufficient for night swimming. CPO changed 2 pool signs correcting hours of operation from 10:00am to DUSK while EHS on-site. POOL PERMIT CAN BE ISSUED. Post pool permit in visible location on pool deck.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some etching & chipped areas on pool floor. ** Maintain in good repair.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Safety rope hooks are not recessed in pool wall. ** See .2515(f). (Note: safety rope not present nor is one required.)
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
-- Chain link fence damaged in 3 areas near corner adjacent to tennis court entrance. ** 2 areas repaired while EHS on-site. Temporary means of correction made at 3rd area/ pool deck run off site; however, CPO reports he will take additional action.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
-- Deck cracks/( pieces of concrete missing) in 4 areas creating > 1/2" offsets. ** Corrected during inspection (CDI). -- Pieces of concrete missing & chunk of concrete missing from under side of coping at pool corner closest to equipment/ chemical room. ** CDI. -- Corner portion of pool deck closest to tennis court entrance has settled creating long deck crack & offset. ** Repair, resurface (or replace if necessary) deck in this area as soon as possible; otherwise, 2018 pool permit will be denied.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed high and low vents in equipment room/ chemical room double door; however, no natural cross draft ventilation or forced air ventilation present. ** See .2533(e) & .2534(3).
#27 · Equipment room: filter backwash discharged through an air gap −2
Filter backwash pipe inserted down into larger pipe in floor. ** Backwash water should discharge through a complete air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
-- Urinal leaking. ** Repair. -- Toilets dirty. ** Clean. -- Leak in ceiling in men's restroom. ** Resolve. -- Shower drain grate missing. ** Install grate.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bib in men's restroom does not have any back flow prevention. ** Install vacuum breaker.

View this inspection on the county portal ›

Apr 13, 2016 18 demerits · 4 violations
Inspector comments: Update excel sheet to reflect correct pump type and number. Operator will also need to submit new PDSC to reflect new equalizer install date prior to permit being issued. GC: #7 Missing/ broken copeing in corner of pool wall.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Equalizer had expired. 2 replaced during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope was fraying. Buoy replaced during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Regrout cracks in concrete and replace missing/broken expansion joints.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Repair ventilation in chem/storage room. Clean up excess debris in storage.

View this inspection on the county portal ›

Apr 15, 2015 12 demerits · 5 violations
Inspector comments: #11 Bolt protruding from one step on ladder. ** CDI. #30 Hose bibs in men's restroom do not have back flow prevention. ** Install vacuum breakers. Note:MCHD has 9435 S. Vicksburg Park Court. 911 & sign have 9445 S. Vicksburg Park Court. Old pool. 9445 is the street number for the closest condominium unit. 9435 is near the end of the same building; however, this unit is farther from the pool. Address needs to establishment for the pool via Meck. Co. Addressing. Issue to be referred to Katie Wilson (Sr. Environmental Health Specialist). POOL PERMIT CAN BE ISSUED.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Safety rope anchors are not recessed. ** Anchors could be removed because safety rope not used or required.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Abundant deck cracks, some with concrete chipped out. ** Repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Forced air vent in chemical/ equipment room inoperable & no cross ventilation. ** Repair/ replace.
#27 · Equipment room: filter backwash discharged through an air gap −2
Filter backwash pipe inserted down into larger pipe. ** Backwash water should discharge through a complete air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in restrooms. ** Provide. No toilet paper in mens. ** CDI Mirrors in restrooms are not shatterproof. ** Mirrors should be made of shatterproof material

View this inspection on the county portal ›

Apr 21, 2014 12 demerits · 3 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed depth markings and no diving signs faded. CDI-repainted.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Observed safety rope anchors not recessed.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy dry rotted. CDI-replaced.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “PARK WALK” or State ID 2060500415). Inspection type (routine vs. follow-up) is not published in the county's data.