4demerits
QUEENS STATION
310 QUEENS ROAD, Charlotte, NC 28204
Seasonal Swimming Pool · NC permit/State ID 2060500447
Latest result4 demerits
Last inspectedApr 7, 2026
Inspections on record13
On record sinceMar 27, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Mar 27, 2014Lower is betterApr 7, 2026
Inspections & violations
Apr 7, 2026 4 demerits · 1 violation
Inspector comments: Pool open for 2026 season.
No night swimming
Flow meter was within range.
Address verified
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
Operator moved chairs greater than 6 feet off the pool
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
May 13, 2025 14 demerits · 3 violations
Inspector comments: Permit restrictions: Flow meter must remain operable. Flow shall be kept at 74gpm due to flow restriction of the filter and the drain Cover Flow restriction.
No night swimming.
Inspection conducted with CPO Jorge.
General Comment/Note: Signage on pool phone changed to 310. Address was recently changed and operator is working on updating with phone provider to reflect correct address of 310 Queens Rd. 911 still had 308 Queens Rd. Strong recommendation that the address match prior to opening to the public.
Verified and confirmed the following items per Katie’s email:
New Pump Hayward TristarVS950, SP32950VSP, 2.7 THP
FlowVis flow meter reading the above permit restriction.
Main drain, skimmer and return line all 2” pipe
(2) Aquastar 2017 A10RCFRxxx drain covers
(1) Pentair TR100 filter
(3) skimmers with EQ lines plugged per State requirement.
(6) returns on floor.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed PH at 8.0. CDI: Corrected to 7.2 during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed leaf and other debris on the pool floor. CDI: cleaning during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed < 6ft clearance around pool deck due to lawn chairs. CDI: chairs moved to provide 6ft clearance.
Apr 19, 2024 8 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy greater than 42’. -CDI- CPO corrected rope length to 42’.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(b) Provide sufficient lighting in pump room. Observed no light in pump room.
Apr 3, 2023 4 demerits · 1 violation
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed slight leaf debris on the pool floor. - 4 -
Apr 13, 2022 0 demerits · 0 violations
No violations were recorded for this inspection.
Apr 8, 2021 20 demerits · 6 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Test kit missing essential reagents.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool surface and floors.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers with heavy debris.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed 3 gates with measurements greater than 4” underneath to horizontal. *No permit action taken due to pre-2010 construction*
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(b) Provide sufficient lighting in pump room. Observed light in pump room no providing lighting.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap to backwash.
Apr 7, 2020 22 demerits · 6 violations
Inspector comments: Note: No restrooms at pool and operator stated there have never been restrooms, due to age, pool built '83. All units have restrooms and showers in condos. Ensure there is access to restrooms and showers.
Salt generator installed, must keep chlorinator as primary disinfection.
No Night Swimming.
Changed to "A" Open for Business, valid permit, with condition of staying closed to public by Executive Order-120, or other Orders, outlined in permit.
Operator unable to sign due to COVID-19 protocol and safety precautions to not share equipment.
#1 · Water quality: water clear enough to clearly see bottom of pool and pool drain −6
Skimmer equalizer and main drains with some leaves/debris at time of inspection.
.2535(2) Main drains must be clearly visible from the pool deck. Operator cleaned and corrected.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No records for pool at time of visit. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain
cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and
total alkalinity weekly. Provided operator with record keeping forms and operator filled out. Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate onto pool deck propped open by maintenance at time of visit.
.2537(b) All gates and doors shall be self-closing, self-latching. Operator removed stopper and closed gate. Corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool furniture moved by maintenance and within 6' of pool at time of inspection.
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Operator moved items and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pool built in 1983. No chemical storage on site. No 3' clearance around piping and equipment. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting
Rule.2534. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap.
Apr 3, 2019 8 demerits · 2 violations
Inspector comments: A paint company was spraying new paint around the pool during the inspection
#3 · Water quality: pool water pH −6
PH was 7.0 but was raised to 7.2 during the inspection
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash
Apr 17, 2018 8 demerits · 3 violations
Inspector comments: PDSC and VGB information verified.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed floating debris on surface of pool.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no ventilation in chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap for back wash discharge.
Apr 3, 2017 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed only one vent in the pump room so that cross ventilation is not occuring.
Mar 24, 2016 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no cross ventilation or fan in pump room.
Mar 24, 2015 18 demerits · 4 violations
#3 · Water quality: pool water pH −6
pH 7.1. Maintain between 7.2 and 7.8. Corrected to 7.2.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope on ring buoy 30 ft. Needs to be 42 feet. Corrected by operator.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater light not securely attached. Corrected by operator.
#27 · Equipment room: filter backwash discharged through an air gap −2
Provide air gap for backwash.
Mar 27, 2014 4 demerits · 2 violations
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed only one wall vent. Provide forced ventilation or crossed ventilation in the chemical/pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed the backwash line recessed in the floor. Provide an air gap above the floor. Adam Kennell present.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “QUEENS STATION” or State ID 2060500447). Inspection type (routine vs. follow-up) is not published in the county's data.