18demerits

RANDOLPH PARK APARTMENTS-OFFICE

4536 RANDOLPH RD, Charlotte, NC 28211
Seasonal Swimming Pool · NC permit/State ID 2060500459
Latest result18 demerits
Last inspectedMay 27, 2026
Inspections on record18
On record sinceAug 20, 2013

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

02346 Aug 20, 2013: 46Jul 18, 2014: 4May 21, 2015: 10May 13, 2016: 14Jun 8, 2017: 0Jun 15, 2017: 4Jun 12, 2018: 8May 15, 2019: 10Jun 8, 2020: 6Apr 27, 2021: 8May 17, 2022: 10May 31, 2024: 22Jun 13, 2024: 12Jun 14, 2024: 4Jun 6, 2025: 12Jun 10, 2025: 10May 13, 2026: 36May 27, 2026: 18
Aug 20, 2013Lower is betterMay 27, 2026

Inspections & violations

May 27, 2026 18 demerits · 5 violations
Inspector comments: Permit issued. NO NIGHT SWIMMING.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed minor debris in skimmer basket. CPO dumped basket
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed missing rubber cap on ladder
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed 2 electrical conduits outside of fencing. Fence was less than 48 inches from electrical conduit. CPO covered conduits to eliminate the foot holds during inspection
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed signage stating “call 911”. Facility has a kings three box. Sign was corrected to say “push button” to call 911.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Observed worn off labels on piping.

View this inspection on the county portal ›

May 13, 2026 36 demerits · 8 violations
Inspector comments: Re-inspection fee is required. Call Main office at 980-314-1620 once ALL 4 AND 6 point demerits are corrected.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. CPO attempted to raise the pH. EHS observed pH at 6.8 at end of inspection. Permit denied
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. Observed return cover on vacuum line in pool. Permit denied
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed missing rubber end cap on ladder
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed damaged ring buoy with a rope at 43ft long. CPO provided new undamaged ring buoy and rope was adjusted to 45ft.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed damaged decking beside skimmer lid at 1.5 inches. Permit denied
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. .2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. .2530(c) Provide "Adults should not swim alone." in 1" lettering. Observed signage on pool deck not including any of the statements listed above. CPO found old pool signs including these items.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. Observed emergency phone unable to connect to 911. Facility has a kings 3 box. EHS was only able to speak to kings 3 operators and operators were unable to connect the phone call to 911. Permit denied
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Observed piping in pump room without labeling.

View this inspection on the county portal ›

Jun 10, 2025 10 demerits · 3 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed one gate hanging up. CDI- Self closure tightened
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed work needs to be done on deck to fit smoothly around skimmer cover.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Provide restrooms at all pools except for hotels, motels, condominiums and apartments where pool use is restricted to guests and residents. Observed water to office shut off for pipe repair. Repairmen on site.

View this inspection on the county portal ›

Jun 6, 2025 12 demerits · 2 violations
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. No chlorine residual in pool - measured 0.0.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Pool pH measured 6.8.

View this inspection on the county portal ›

Jun 14, 2024 4 demerits · 1 violation
Inspector comments: Not approved for night swimming.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pools chair less than 6ft from pool surface. Chairs were moved to allow for 6ft clearance.

View this inspection on the county portal ›

Jun 13, 2024 12 demerits · 2 violations
Inspector comments: No night swimming.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope greater than 45’. CDI: Rope cut to length.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed emergency phone not in operation.

View this inspection on the county portal ›

May 31, 2024 22 demerits · 4 violations
Inspector comments: Permit denied. No night swimming.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed PDSC form shows equalizers. Pool has been replastered and equalizers have been removed. Resubmit updated form for approval.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy ropes are deteriorated and flaking. Observed rope at 43.5’. Required length is 46’.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter not functioning.

View this inspection on the county portal ›

May 17, 2022 10 demerits · 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed one missing weir. 75% of skimmers had weirs present. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris present in skimmers. CDI - Skimmers emptied during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed emergency phone not in operation. Phone line employee working on phone line during inspection. Emergency phone fixed and able to connect to 911 by end of inspection.

View this inspection on the county portal ›

Apr 27, 2021 8 demerits · 2 violations
Inspector comments: General Comment: The directional arrows on the pumps are beginning to fade. Have redrawn. Night swimming has not been approved. Chad Burchfield was the Pool Operator onsite during the inspection. No signature today due to COVID 19 Issuance of permit by this Department does not negate meeting requirements of Executive Order 195 or subsequent Order in effect unless such Orders are rescinded or superseded by another applicable Order.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed missing weir. This was corrected and the operator installed a new weir.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed bobber stuck to the bottom of the flow meter. This was corrected and the flow meter was fixed.

View this inspection on the county portal ›

Jun 8, 2020 6 demerits · 2 violations
Inspector comments: PERMIT ISSUED. STICKER ISSUED. POOL IS NOT APPROVED FOR NIGHT SWIMMING. IF NIGHT SWIMMING IS DESIRED, A NIGHT SWIMMING EVALUATION MUST BE PERFORMED. CONTACT C. ELMORE AT 704-507-6814 FOR THIS EVALUATION IF NIGHT SWIMMING IS DESIRED. “issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, 141 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.” NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING PDSC form verified.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 skimmer out of 3 to be missing the weir. No permit action taken as the majority of weirs still in place. Replace the missing weir.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap for backwash line.

View this inspection on the county portal ›

May 15, 2019 10 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed buildup along pool water. - 4 points.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed buildup in all skimmers checked. - 4 points.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. No color codes or arrow were in place on pump room piping to detail the flow of the filtration system. - 2 points.

View this inspection on the county portal ›

Jun 12, 2018 8 demerits · 2 violations
Inspector comments: Observed missing backflow preventer on hose bib at the pump house. MCHD Permit #18-600519
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed one missing weir out fo three. CDI - Operator installed weir during inspection. -4-
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528 (a)(2) Footholds shall not be available on the outside of fencing. Observed chemical storage box at the left rear of the fencing leading to the pump house. -4-

View this inspection on the county portal ›

Jun 15, 2017 4 demerits · 1 violation
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed the flow meter stuck today.

View this inspection on the county portal ›

Jun 8, 2017 0 demerits · 0 violations
Inspector comments: Inspection completed by L. Bromberg. See visit sheet from earlier today. CDP would not allow to go from B status to E status. Total demerits for inspection was 22.

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 13, 2016 14 demerits · 4 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Two weirs missing. Replace. One weir replaced during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs are too close to pool on one side. Maintain 6 ' of clearance form pool edge. Corrected during inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operating properly. Fix or replace. Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No cross ventilation in pump room.

View this inspection on the county portal ›

May 21, 2015 10 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pool floor needs to be cleaned.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in restroom not shatterproof.

View this inspection on the county portal ›

Jul 18, 2014 4 demerits · 1 violation
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed vacuum port uncovered and drawing water. Corrected onsite. Plugged and valve turned off. Observed one equalizer cover not mounted properly. To be Replaced

View this inspection on the county portal ›

Aug 20, 2013 46 demerits · 12 violations
Inspector comments: Permit not posted. Must be visible on pool deck. Meckpools.charmeck.orgImmediate Suspension issued for #3 and #22. Once corrected, contact Kaite at 704-309-5494 to re-open pool.
#3 · Water quality: pool water pH −6
Observed pool pH at <6.8. Maintain at 7.2 to 7.8. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no log book. Record as required. Acid reading >100 ppm. Max limit is 100 ppm.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed tile missing from pool walls and some damage to wall/coping. Keep in good repair.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed weirs missing from skimmers. Replace weirs.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed wall depth marker not match deck (5 1/2 ft). Replace wall depth marker.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed slip resistant tread missing from ladder. Provide.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed multiple inlets missing fittings. Replace fittings.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed rope not attached to ring buoy and attached to fence. Keep attached to ring buoy. Observed ring buoy damaged. Replace with USCG approved buoy. Immediate Suspension issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed pool furniture 3 ft to pool. Maintain 6 ft clearance.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Keep operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no cross/forced ventilation in pump room. Provide adequate ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed no toilet paper/paper towels in restrooms and water >113 F. Provide tp and paper towels and maintain water at 110 F or below.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “RANDOLPH PARK APARTMENTS-OFFICE” or State ID 2060500459). Inspection type (routine vs. follow-up) is not published in the county's data.