16demerits
SHANNON PARK SWIM CLUB
5126 GRAFTON DR, Charlotte, NC 28215
Seasonal Swimming Pool · NC permit/State ID 2060500494
Latest result16 demerits
Last inspectedApr 22, 2026
Inspections on record14
On record sinceJun 24, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 24, 2014Lower is betterApr 22, 2026
Inspections & violations
Apr 22, 2026 16 demerits · 5 violations
Inspector comments: PERMIT RESTRICTION: VFD INSTALLED ON PUMP REQUIRED TO BE SET AT 60HZ. ONE FLOOR RETURN WITH AQUASTAR A10RCFRXXX COVER - NO SUCTION ON COVER
NO NIGHT SWIMMING.
*NOTE: Phone number listed on emergency telephone fading out. EHS had CPO re-write in sharpie so that it was easily legible.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.
Observed debris on pool floor.
CPO cleaned out debris before end of inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
Observed a few skimmer baskets full of debris.
Keep skimmer baskets free of debris.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(a) Provide depth markers on pool walls and pool deck next to the swimming pool.
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool.
.2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background.
Observed no depth markers along one whole side of the pool. Observed few of the present spray-painted depth markers fading out, no longer easily legible. Observed some of the present spray-painted depth markers exceeding 25ft within each other. Observed some of the NO DIVING spray-painted markers fading out.
CPO had stencil kit in truck; other CPO drove to Walmart to grab spray paint; depth markers were fixed during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions.
Observed missing endcaps on 1 ladder located in diving area.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(b) Provide sufficient lighting in pump room.
Observed no lighting inside pump room.
Replace lightbulb so that there is lighting in pump room.
Apr 24, 2025 4 demerits · 1 violation
Inspector comments: Pump restriction. VFDinstall installed on pump required to be set at 60 HZ one floor return with aqua star a 10 RCFRXXX cover. No suction on cover.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed leaf debris in diving well.
May 16, 2024 0 demerits · 0 violations
Inspector comments: No violations noted during inspection. Pool is not permitted for night swimming.
Permit issued.
EHS verified VFD installed on pump set at 60HZ
No violations were recorded for this inspection.
May 15, 2024 14 demerits · 4 violations
Inspector comments: Pool is not permitted for night swimming.
EHS verified VFD installed on pump set at 60HZ
PERMIT DENIED.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed one weir missing. CDI: CPO replaced weir.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed two skimmers full of debris. CDI: CPO cleaned out skimmers.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed multiple painted depth markers faded and not clearly visible. CDI: CPO touched up depth markers to make more visible. When depth markers become not clearly visible, repaint.
.2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background. Observed no diving written out in paint beginning to fade. CDI: CPO touched up faded areas. When no diving writing begins to fade, repaint to ensure visibility.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed 3 return inlet covers on pool floor not in place or secured. Observed missing fitting on threaded hole in pool wall. CPO stated that it could be an old vacuum line. Secure all fittings before next inspection.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Post a shower sign visible upon entrance to the pool.Observed no shower sign visibly posted. CDI: CPO installed a shower sign.
May 9, 2023 14 demerits · 5 violations
Inspector comments: No night swimming permitted.
350 GPM
Pool hours will be from sunrise to sunset.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed leaves and debris on surface of pool in 5 ft area. Observed stains on pool floor in shallow and deep ends of pool.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint. Did not observed any safety rope at breakpoint of pool. They ropes were not out at breakpoint for observation.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed areas of deck near back corners and along side that had cracks greater that 1/2” on pool deck. Improvements shall be made before next pool season.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed standing water and leaves on floor of pump room.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. There was not any color bands or marking on pipes in pump room. CDI- CPO provided marking with a sharpie.
May 19, 2022 14 demerits · 4 violations
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.ph 7.1 Raised to 7.3
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.observed some debris on pool floor.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Maintain breakpoint rope and floats in good repair.
.2523(e) Maintain breakpoint rope and floats in good repair.observed not present. Installed.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water.pump room floor with leaves.
May 6, 2021 8 demerits · 2 violations
Inspector comments: *PSDC information verified on site*
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed 3 ft. Depth markers 31 ft. Apart. Depth marker added in between to reduce distant.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed damage throughout tile and concrete decking. Repair/replace as necessary.
*Improvement on coping around perimeter of pool*
.2537(2) Decks shall be kept in good repair.
May 8, 2020 4 demerits · 1 violation
Inspector comments: Verified PDSC information.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed damage throughout tile and concrete decking. Repair/replace as necessary.
May 22, 2019 18 demerits · 6 violations
Inspector comments: Onsite visit for infield plan reivew and operation permit.
Verified the following information:
Filters - 6 Pentair T100C
Pump - Pentair EQ750
Returns - 17 floor returns
Piping - Simmker 3", Return 6", Main Drain 6"
Skimmers - 10
VFD installed on pump required to be set at 60Hz.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris on pool floor.
.2537(14) Keep pool surface and pool floor free of debris.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed debris in skimmers.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Observed safety rope not in place at time of inspection.
Corrected during inspection.
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed several damaged areas on pool deck. Repaired during inspection.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Obseved bathroom hand sink leaking.
.2626(m) Keep restrooms and fixtures clean and in good repair.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Obseved bathroom hand sink leaking.
.2626(m) Keep restrooms and fixtures clean and in good repair.
May 24, 2018 4 demerits · 2 violations
Inspector comments: No night swimming. Local permit number 18-600393.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. One ladder loose and one ladder missing rubber bumpers at bottom.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap at backwash drain in pump room.
Jun 22, 2017 20 demerits · 6 violations
Inspector comments: Refinish damaged pool bottom and pool deck prior to obtaining a permit for next season.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed damage to pool floor throughout diving well area. Repair prior to opening next season.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed hand rail loose at diving well.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed pool deck uneven throughout. Repair prior to opening next season
#22 · Premises: emergency telephone provided −6
Observed no address posted near emergency phone. Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed chemical closet fan damaged.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed backwash line without air gap.
Jun 20, 2016 0 demerits · 0 violations
No violations were recorded for this inspection.
Jun 25, 2015 16 demerits · 6 violations
Inspector comments: 13. Contrasting band observed to be approximately 1-2" from edge of stairs depending on location of tiles.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 2 of 10 weirs missing.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed several loose ladder rails.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed large gap between coping and deck of pool along back side of pool.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no ventilation in equipment/pump room.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Label all pipes in pump room. Observed reutrn and back wash lines not labeled.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at backwash line.
Jun 24, 2014 32 demerits · 8 violations
Inspector comments: Intent to Suspend issued for items 5 and 9.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Daily Written Records did not include Main Drain checks. Check main drains daily and add to written records.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
3 Weirs missing.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Pool wall is missing two 11 FT depth markers and one 6 FT depth marker. "No Diving" markers need to be added at 5 FT depth end so that there is <25' between markers.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope length was only 45'. Corrected during inspection to 50'.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Fill spout not close enough to ladder. Fill spout is not permanent. Needs to be removed when pool is not open. Corrected during inspection.
#22 · Premises: emergency telephone provided −6
Emergency phone not working. Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No cross ventilation in pump and chemical room.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Pipes not labeled.