10demerits
CAMDEN FOXCROFT-PHASE II
4428 SIMSBURY ROAD, Charlotte, NC 28226
Seasonal Swimming Pool · NC permit/State ID 2060500506
Latest result10 demerits
Last inspectedMay 14, 2026
Inspections on record14
On record sinceMay 19, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 19, 2014Lower is betterMay 14, 2026
Inspections & violations
May 14, 2026 10 demerits · 2 violations
Inspector comments: NO NIGHT SWIMMING
PERMIT RESTRICTION: Pump shall be set at 2350 RPM or flow meter shall remain operable with flow range at 65 GPM to 98 GPM to meet turnover and flow restriction of filter.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope exceeding 39ft. CPO cut rope to 39ft during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed lounge chairs within 6 ft of waters edge. Lounge chairs were pushed back to provide 6ft of deck clearance.
May 4, 2026 18 demerits · 5 violations
Inspector comments: Re-inspection fee required. Call Main office at 980-314-1620 once all 4 AND 6 point demerits are corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Install skimmer per manufacturer specifications and eliminate equalizer line plugs or plug per State requirements. Observed both skimmers with with both lines inside the skimmer not plugged. Pool does not have equalizers. Permit denied.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate near the mailboxes not self closing self latching. Permit denied
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed lounge chairs within 6ft of waters edge. CPO moved chairs to provide 6ft of deck clearance.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter not functioning. Pool has a flow requirement for turnover. Permit denied.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(l) Provide toilet paper and dispensers in restrooms. Observed both restrooms without toilet paper.
May 16, 2025 2 demerits · 1 violation
Inspector comments: Permit Restrictions-pump shall be set at 2350 RPM or flow meter must be within the range of 65-98 GPM. Today 90 GPM
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(c) Over the rim fill spouts shall not protrude greater than two inches beyond the edge of the pool. Observed fill spout extends greater than 2” into pool.
.2512(c) Over the rim fill spouts shall be located under the diving board or within six inches of a ladder or handrail. Observed fill spout >6 inches from ladder
Apr 30, 2024 4 demerits · 1 violation
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Openings in the barrier shall not allow passage of a four inch diameter sphere and shall provide no external handholds or footholds. A small storage container for pool chemicals, two flower pots and an old fan cover attached to wall outside chemical room were observed directly outside pool fence creating footholds. Pool Operator moved storage container and flower pots away from fence and removed fan cover on outside wall leaving only a 1/2 inch ledge on wall.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Audible alarm attached to door leading from gym to pool deck was inoperable. Pool operator adjusted batteries in audible alarm. Audible alarm was operating properly.
Jul 25, 2023 8 demerits · 2 violations
Inspector comments: Pool met all permit restrictions.
No night swimming permit
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Pool was missing a suction cap. The pool operator put a new cap on the port..2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool chairs were less than 6 feet from the pool edge. Pool operator loved the chair to greater than 6 feet..2522(a) Provide 6 ft of clear walking space around the pool at all times.
Jun 17, 2022 8 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed fallen leaves present on pool floor. CDI - PIC began vacuuming during inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmer baskets with leaves present. CDI - PIC emptied baskets.
May 7, 2021 2 demerits · 1 violation
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. observed no air gap at backwash line in pump room.
Jun 11, 2020 2 demerits · 1 violation
Inspector comments: POOL HAS PASSED INSPECTION.
PERMIT ISSUED. STICKER ISSUED.
POOL IS NOT APPROVED FOR NIGHT SWIMMING. IF NIGHT SWIMMING IS DESIRED, A NIGHT SWIMMING EVALUATION MUST BE PERFORMED. CONTACT C. ELMORE AT 704-507-6814 FOR THIS EVALUATION IF NIGHT SWIMMING IS DESIRED.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, 141 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
May 24, 2019 8 demerits · 2 violations
Inspector comments: "CHILDREN SHALL NOT USE THE POOL WITHOUT ADULT SUPERVISION" was missing on pool signs. PIC made a temporary sign with proper letter height requirements and placed it adjacent to pool rules by the end of the inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed buildup on all skimmers checked throughout.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed deck structure near 5ft side of pool with protruding cement that could be considered a trip hazard. Ensure that this area is filled in and/or grouted for compliance.
May 21, 2018 8 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed pool floor in need of cleaning.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed pool skimmers in need of cleaning.
May 26, 2017 0 demerits · 0 violations
Inspector comments: Emergency phone is still low to hear but it is audible. Both kings3 and 911 could hear us loud and clear, and the address/phone number matched records.
Fence has been raised to meet the rule.
No violations were recorded for this inspection.
May 12, 2016 0 demerits · 0 violations
No violations were recorded for this inspection.
May 14, 2015 16 demerits · 3 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope grossly short on 5-13. Corrected with new rope on 5-14.
#18 · Premises: lifeguards present or warning signs posted −4
Observed signage lettering too smnall<3 in on 5-13. Corrected to 4 in on 5-14.
#22 · Premises: emergency telephone provided −6
Observed emergency phone not working properly on 5-13. Working properly on 5-14.
May 19, 2014 8 demerits · 2 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Maintain deck clearance at least 6ft. Observed 4ft 11 in in some areas. Relocate deck furniture.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Observed pool light 1/4in protruding. Secure tight seal to wall or fill in around light- light is currently screwed into wall
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “CAMDEN FOXCROFT-PHASE II” or State ID 2060500506). Inspection type (routine vs. follow-up) is not published in the county's data.