12demerits
STONEHAVEN HOMEOWNERS ASSN
6615 THERMAL RD, Charlotte, NC 28211
Seasonal Swimming Pool · NC permit/State ID 2060500525
Latest result12 demerits
Last inspectedMay 6, 2026
Inspections on record13
On record sinceApr 9, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 9, 2014Lower is betterMay 6, 2026
Inspections & violations
May 6, 2026 12 demerits · 3 violations
Inspector comments: Two conspicuous boxes constructed to cover something that may have been an old diving platform mount constitute trip hazards, and are within 6 feet of the edge of the pool. These should be removed and repaired at the surface of the deck made smooth so that there is no trip hazard prior to opening the 2027 season.
No night swimming.
Expiring/expired covers requires replacement prior to permit 2026. Requires 5% flowmeter for 2026.This work has been done. New PDS form has been approved.
Permit restriction: flowmeter shower remain operable. Pool flow must remain as close to 150 gallons per minute as possible not to exceed 150 gallons per minute, suction hazard. No suitable cover on market for required turnover a 217 gallons per minute. Limitation is 160 gallons per minute for number of returns. If a clarity issue arises additional steps will be required to ensure pool is able to turnover requirements. Note: 4HPXXX on autofill.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. observed slight debris on pool floor and wall.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. observed primary entrance gate self closing, but not self latching. Repaired on site.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. observed lounge chair within 3 feet of pools edge. Pool also has two conspicuously constructed wooden boxes that are assumed to be covering something that are within 5 feet of the edge of the pool and constitute trip hazards. These should be removed and whatever they’re covering removed down to or below the deck surface and finished over to eliminate any trip hazard.
May 27, 2025 4 demerits · 1 violation
Inspector comments: Permit Restriction: Pool flow must remain as close to 150gpm as possible not to exceed 150gpm (Suction Hazard), no suitable cover on market for required turnover of 217gpm, next limitation factor is 160gpm for number of returns. If a clarity issue arises, additional steps will be required to ensure pool is able to meet turnover requirements. Flow meter must remain operational.
Note: 4HPxxx on autofill.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - Observed debris in the bottom of the pool. Needs to be cleaned.
Apr 23, 2024 0 demerits · 0 violations
Inspector comments: No violations noted at inspection.
Pool is okay to operate at owners discretion.
Pool permit and sticker were issued at inspection.
No violations were recorded for this inspection.
Apr 27, 2023 6 demerits · 2 violations
Inspector comments: EHS observed lock on throttle valve and pressure gauges were present.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed pool wall and pool floor with build up. Clean as needed.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Piping in pump room was not labeled. Label pipes.
Apr 21, 2022 22 demerits · 6 violations
Inspector comments: Permit restrictions- throttle valve must remain locked in place with pressure gauge installed flow meter not to exceed 226 gpa per the measurements.
Pool not permitted for night swimming.
PDSC verified.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
**.2537(14) Keep pool surface and pool floor free of debris. Observed debris along the pool floor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris inside of the skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Observed both ladders at 7 inches away from the pool wall.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope was too short at 40 feet . CDI Ring buoy rope replaced during inspection to meet 42 feet in length.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed 4 inches under fence in distance.
.2537(b) All gates and doors shall be self-closing, self-latching. Gate was not self-closing, self-latching initially. CDI- Gate was repaired on site to become self-latching, self closing by CPO.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap at backwash
Apr 30, 2021 6 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris in pool.
**.2537(14) Keep pool surface and pool floor free of debris.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at backwash.
**.2513(b) Filter backwash shall be discharged through an air gap.
May 1, 2020 4 demerits · 1 violation
Inspector comments: Night swimming has not been permitted.
Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.
Observed cleaning needed to the pool floors. The floors and main drains are easily visible. Have cleaned.
May 15, 2019 10 demerits · 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing or damaged skimmer basket. Observed damaged skimmer basket.
#22 · Premises: emergency telephone provided −6
.2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Observed emergency phone location not listed on pool rule sign or otherwise identified. CDI emergency phone location listed on pool rule sign.
Apr 30, 2018 26 demerits · 7 violations
Inspector comments: PDSC verified by JPERRY.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
pH was raised from 7.0 to 7.2 during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.
Observed debris on pool floor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
One weir was missing. Replaced during inspection.
#22 · Premises: emergency telephone provided −6
.2530(a) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Emergency phone was missing dialing instructions. Added during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(3) Provide continuous forced ventilation or cross ventilation in pump room. Fan is not properly functioning.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap.
No air gap provided.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2626(h) Shower(s) shall be provided. No showers are available on site.
Apr 26, 2017 4 demerits · 1 violation
Inspector comments: PDSC form submitted with Paramount equalizer line covers, but existing covers are Aquastar 6HP. Facility needs to submit revised PDSC form.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518 (e) Pool skimmer baskets shall be free of floating debris for optimum circulation. Observed debris in the skimmer baskets. CDI - PIC cleaned baskets during the inspection. -2-
Jul 6, 2016 14 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Debris observed on pool floor
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
skimmers in need of cleaning one weir popped loose and in skimmer basket.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy had no throw rope at time of inspection CDI new rope attached.
Apr 17, 2015 2 demerits · 1 violation
Inspector comments: G.C. Observed some damage to pool floor and interior surface. Repair this before next season or permit for next season may be delayed. Observed some debris on pool bottom. Keep pool clean. The portable CO monitor worn by C. Elmore activated in the Men's bathroom while tesing the hot water. It registered a reading of 88ppm. Nothing was registered on a 2nd entrance to the room. Evaluate the room an densure there is not a CO hazard.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Observed hose bibb to need backflow preventer. Ensure all hose bibbs have backflow protection.
Apr 9, 2014 2 demerits · 1 violation
Inspector comments: Print and post permit before opening the pool.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed a hole in the walls of the bathrooms that needs repair. Repair the hole.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “STONEHAVEN HOMEOWNERS ASSN” or State ID 2060500525). Inspection type (routine vs. follow-up) is not published in the county's data.