0demerits
EDITION APARTMENTS
5923 FARM POND LANE, Charlotte, NC 28212
Seasonal Swimming Pool · NC permit/State ID 2060500536
Latest result0 demerits
Last inspectedMay 5, 2026
Inspections on record14
On record sinceMay 30, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 30, 2014Lower is betterMay 5, 2026
Inspections & violations
May 5, 2026 0 demerits · 0 violations
Inspector comments: No violations noted.
Inspection conducted with Jesenia Delgado Zapata
No night swimming.
PERMIT RESTRCTION: Flow meter must remain operable. Flow shall be set at 106 gpm to meet flow restriction of filter. Turnover not
met due to restrictions in pump room. Flow greater than 150 exceeds drain covers. Suction Hazard.
No violations were recorded for this inspection.
May 4, 2026 10 demerits · 2 violations
Inspector comments: Inspection conducted with Jesenia Delgado Zapata
No night swimming.
PERMIT RESTRCTION: Flow meter must remain operable. Flow shall be set at 106 gpm to meet flow restriction of filter. Turnover not met due to restrictions in pump room. Flow greater than 150 exceeds drain covers. Suction Hazard.
PERMIT DENIAL for low pH and missing spare filter basket.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. pH measured below 6.8. Adjust chlorine within acceptable limits.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(e) Provide a spare basket for pump. No spare basket. Obtain spare basket.
May 7, 2025 14 demerits · 4 violations
Inspector comments: Permit restriction: Flow meter must remain operable. Flow shall be set at 106 gpm to meet flow restriction of filter. Turnover not met due to restrictions in pump room.
All wall returns were present during inspection.
NIGHT SWIMMING NOT PERMITTED.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor, CPO was vacuuming during visit.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed minor debris in skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed ladder near 8ft diving marker loose. Repair.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2512(c) Over the rim fill spout shall be located under the diving board or within six inches of a ladder or handrail. Observed removable fill spout more than 50 inches from ladder. CPO removed spout and placed cover on pipe.
Apr 29, 2025 24 demerits · 6 violations
Inspector comments: Seasonal permit denied. EHS unable to provide Q sheet due to system error.
For re-inspection call Main office at 980-314-1620. Re-inspection fee required.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed ladder at 8ft diving marker loose. Repair
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible. Observed tele-scoping body hook provided. Permit denied
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed lawn chairs within 3 inches of pool water. Lawn chairs relocated.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed decking near 8ft markers with an offset of more than one inch. Permit denied.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed lifeguard signs without exact wording and less than 4inches. Permit denied.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed phone number posted on sign not match phone number registered with Charlotte 911. Permit denied.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Post a shower sign visible upon entrance to the pool. No shower sign provided
Aug 15, 2024 6 demerits · 1 violation
Inspector comments: Yessie Moncada present for inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Inaccurate phone # posted at emergency phone. 911 operator supplied number of phone on 8/14 during visit, (704-900-7568). Number was called today and phone responded.
Aug 2, 2024 26 demerits · 5 violations
Inspector comments: Permit denied today. Call Mecklenburg County Health Department to request a re-inspection at 980-314-1620. Pay $100.00 return fee before a re-inspection can be scheduled.
Cardoso Perez present during inspection.
Corrections needed: Emergency phone must be functional. 911 operator must confirm phone # and address.
Correct pH level to 7.2-7.8.
Obtain compliant ring buoy rope of 50’.
Ensure pump is operational.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Rope length on ring buoy 24.0 feet. Needs 50.0 ft for compliance.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Less than 4.0 feet clearance for walking space around some areas of pool deck.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Emergency phone not operable. Could not confirm correct address and phone # thru 911 operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter not operating.
.2518(h) Provide approved pump in good repair. Observed pump not operational.
May 9, 2023 48 demerits · 12 violations
Inspector comments: No Night Swimming.
Permit denied. Once all 4 and 6 point demerit items are in compliance, call 980-314-1620 to pay the $100 re-inspection fee, and then call or email Sr. EHS A. Hall to schedule a re-inspection appointment.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed no pool records on site.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. Observed no pool records on site.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed large leaves and debris near drains in deep end of pool.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed at least one missing weir in skimmer. Unable to see weirs at other skimmers due to presence of debris. Ensure weirs are in all skimmers.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers full of debris.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint. Observed breakpoint rope not installed at pool. Breakpoint rope is missing a hook to be properly installed.
.2523(e) Maintain breakpoint rope and floats in good repair. Observed one float on breakpoint rope damaged.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Provide at least one handrail on steps. Observed no handrail on steps.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length on buoy at 20’. Provide rope of 50’.
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy damaged and no longer USCG compliant.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed door to the gym from the pool deck does not self-close, self-latch. Door does self-close. Install audible alarm or make self-closing, self-latching.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed lounge chairs creating less than 6’ of deck clearance around approximately half of the pool edge.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed wording is 2.5” in height.
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. Observed incomplete signage.
.2530(c) Provide "Adults should not swim alone." in 1" lettering. Observed incomplete signage.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed no signage for phone number and address of pool.
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. Observed kings III phone not dialing 911. When button is pushed, nothing happens.
.2530(f) Emergency phone shall remain operable. Observed pool phone unable to be called back to.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Post a shower sign visible upon entrance to the pool. Observed no shower sign.
Jun 12, 2019 14 demerits · 4 violations
Inspector comments: CPO present during inspection.
PDSC form verified and reviewed for compliance.
All bottom floor sliding doors and doors are permenantly locked with the exception of the door leading the bathroom hallway. This door leads to the outer gate/fence which meets compliance and can be used if needed as it meets requirements.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
Observed missing weir at deep end skimmer. CPO replaced with new weir.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions.
Provide missing protective caps at deep end ladder.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed ring buoy rope at 39 feet with paperwork requiring 50 feet of rope. CDI. CPO was able to provide new rope at end of inspection at 50 feet.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(6) Provide sufficient lighting in chemical storage room.
No lighting noted in the chemical storage room.
Jun 15, 2018 0 demerits · 0 violations
No violations were recorded for this inspection.
Jun 19, 2017 4 demerits · 1 violation
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed hose on deck near pool edge. Moved
Jul 15, 2016 4 demerits · 2 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
no bumpers on ladder. CDI
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump/chemical room.
Jul 1, 2015 0 demerits · 0 violations
Inspector comments: Observed EQ lines covered. Observed weirs replaced. Observed new approved ring buoy. Observed water to be clean and clear. Fill spout is more than 4 feet from the nearest ladder. It must be made removable with no more than 1/2" fitting sticking up above the deck. The fitting on the deck must also be capped in a way that does not make the fitting stick up more than 1/2" when capped, including the cap. Pool moved to W status.
No violations were recorded for this inspection.
Jun 18, 2015 32 demerits · 8 violations
#1 · Water quality: water clear enough to clearly see bottom of pool and pool drain −6
Observed water too cloudy to observe the main drains or see the bottom of the pool. Pool closed to swimming. IS Issued.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed skimmer missing an EQ line cover. This is a suction/entrapment hazard. Pool closed to swimming. I.S. Issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 skimmer out of 4 missing the weir. Replace it.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed 1 ladder missing the rubber feet. Replace them.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed damaged ring buoy. Replace it with proper approved ring buoy.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed fill spout to be a trip hazard. It is located more than 4 feet from the nearest ladder. It must be made removable and not be a trip hazard.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed leak at filter. Repair it.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Provide shower sign visable at pool deck area.
May 30, 2014 12 demerits · 3 violations
#3 · Water quality: pool water pH −6
Pool pH shall be maintained between 7.2 and 7.8. Observed the pool pH to be at 8.4. CDI- pool pH was lowered to 7.7.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Rope length of safety buoy shall be 1.5 times the width of the pool. Observed the rope length to be at 55ft. CDI-rope length was cut to 50ft.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Over-the-rim spouts shall be located within 6 incles of the ladder or handrail. Observed the over-the-rim spout to be 2ft from the ladder.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “EDITION APARTMENTS” or State ID 2060500536). Inspection type (routine vs. follow-up) is not published in the county's data.