10demerits
WEDGEWOOD SWIM CLUB
8400 LONDONSHIRE DRIVE, Charlotte, NC 28216
Seasonal Swimming Pool · NC permit/State ID 2060500576
Latest result10 demerits
Last inspectedMay 7, 2026
Inspections on record15
On record sinceMay 1, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 1, 2014Lower is betterMay 7, 2026
Inspections & violations
May 7, 2026 10 demerits · 2 violations
Inspector comments: FLOW CANNOT EXCEEP MORE THAN 500GPM
DUE TO SUCTION HAZARD
NOT APPROVED FOR NIGHT SWIMMING COULD NOT GET LIGHTS TO TURN ON DUE TO TIMER. WILL MAKE NIGHT VISIT TO ENSURE LIGHTS WORK BEFORE ALLOWING NIGHT SWIMMING
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope 5’ too long. Corrected during inspection
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Corrected during inspection.
.2518(g) Keep flow meter operational.
May 15, 2025 0 demerits · 0 violations
Inspector comments: This inspection sheet is entered because I forgot to correct status on inspection sheet prior to sending
Flow must be below 500gpm. Verified flow at 375
Night swimming approved.
All previous violations corrected. No violations noted during this inspection
No violations were recorded for this inspection.
May 9, 2025 0 demerits · 0 violations
Inspector comments: Flow must be below 500gpm. Verified flow at 375
Night swimming approved.
All previous violations corrected. No violations noted during this inspection
No violations were recorded for this inspection.
Apr 14, 2025 16 demerits · 3 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
PDSC did not match drain covers that were present in the pool.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy rope too long. Rope was 60’ instead of 50’. CPO corrected during inspection
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation.
Liquid chlorine feeder must be linked to NSF approved feeder
Apr 18, 2024 8 demerits · 2 violations
Inspector comments: 3) .2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0. CDI- pH increased
NOTE: FACILITY DOES NOT CURRENTLY WANT TO DO NIGHT SWIMMING, HOWEVER, THAT MAY CHANGE. EHS WILL MAKE A NIGHT SWIMMING VISIT IF FACILITY WANTS TO NIGHT SWIM.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed weir missing. Get replaced.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed cracks in deck.
Apr 21, 2023 6 demerits · 1 violation
Inspector comments: Night swimming has been approved based off approval from 6/7/2021. EHS verified during inspection that lights were still operable. Pool will have to be reverified for night swimming for the 2024 pool season.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0 at start of inspection. Corrected during inspection to 7.2
May 11, 2022 2 demerits · 1 violation
Inspector comments: Permit issued
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed dry wall in womens shower in need of repair. Does not prevent guests from showering.
May 21, 2021 0 demerits · 0 violations
Inspector comments: 2 eyelets needed to be adjusted.
*Sidenote-EHS verified a few things in the field:
Pentair EQ750 with 7.5 HP motor
6" main drain line with 2-(they were approved for 1,) but they have 2- 4" skimmer lines and 2-4" return lines
Neptune Benson Aegis 30*30 drain covers
(7) Aquastar 6HPxxx, (2) Aquastar 4HPxxx equalizer line covers
(4) Pentair TR140c filters
16 returns
No violations were recorded for this inspection.
Apr 17, 2020 0 demerits · 0 violations
Inspector comments: Due to Covid 19 restrictions--no signature required.
No violations were recorded for this inspection.
May 16, 2019 4 demerits · 1 violation
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter frozen. CDI- operational after adjustment.
May 1, 2018 14 demerits · 3 violations
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH at 6.9. CDI pH increased to 7.4
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.
Observed debris in pool floor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
Observed skimmer soiled with debris.
May 2, 2017 2 demerits · 1 violation
Inspector comments: Inspection completed and placed on A status.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed end caps missing on handrail.
May 12, 2016 8 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Repair pool floor near base of step. General cleaning of pool floor and wall.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Repair handles and shower head on showers. Repair ceiling in men bathroom. Replace missing attic panel in women bathroom.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Replace missing back flow prevention device on hose bib.
Return outlet cover secured at time of inspection. Repaint fading contrasting bands on steps by next pool season.
May 1, 2015 8 demerits · 3 violations
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed a pool floor inlet off today- repaired and secured during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed water on the pump room floor today- keep dry.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed a leaking toilet today- fresh water leaking a little.
May 1, 2014 18 demerits · 7 violations
Inspector comments: #21 Pool wall light (noted on 4/23/14 visit) is secure; however, pool wall frame for light has become bent over years.
*Pool permit can be issued.
*Permit can be issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed some soil on ladders (inset) steps & some on pool wall & floor. **clean.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Missing 1 escutcheon @ top & the other not secure at bottom 1 rail @ steps. **correct.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed 2 deck cracks & pieces of concrete missing/broken @ edge of "new" concrete area. **repair deck @ edge of new concrete.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak @ top of one filter & therefore, floor wet. **repair filter.
Forced air vent in equipment room inoperable. **repair.
Forced air vent in chemical room operates on switch. **leave fan on @ all times.
#27 · Equipment room: filter backwash discharged through an air gap −2
Backwash line down in sump. **should have air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Replace broken shower handles (2 in womens).
Handicap "hose" nozzles missing in both restrooms.
Handicap bench in men's shower broken.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Install vacuum breakers on all hose bibs (1 by storage room, 1 in equip., 1 in chem.)
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “WEDGEWOOD SWIM CLUB” or State ID 2060500576). Inspection type (routine vs. follow-up) is not published in the county's data.