‹ Back to search

18demerits

BAYBRIDGE CONDOMINIUMS

18023 KINGS POINT DRIVE, Cornelius, NC 28031
Seasonal Swimming Pool · NC permit/State ID 2060500653
Latest result18 demerits
Last inspectedApr 15, 2026
Inspections on record13
On record sinceApr 22, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0918 Apr 22, 2014: 6Apr 17, 2015: 10Apr 28, 2016: 8Apr 24, 2017: 12Apr 27, 2018: 0Apr 17, 2019: 16May 14, 2020: 10Apr 19, 2021: 14Apr 13, 2022: 12Apr 26, 2023: 6Apr 25, 2024: 4Apr 22, 2025: 4Apr 15, 2026: 18
Apr 22, 2014Lower is betterApr 15, 2026

Inspections & violations

Apr 15, 2026 18 demerits · 4 violations
Inspector comments: No Night Swimming. Permit Restriction: Flow Meter shall remain operable. Flow may be no greater than 119 gpm due to drain cover restriction. Suction Hazard.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Pollen present on surface and floor of pool. Cleaning in progress during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Table and umbrella stand observed to be closer than 6’ to the pool edge. Moved during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Phone jack was loose, rendering phone inoperable at start of inspection. Repaired and observed phone to be in proper working order by end of inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter was stuck at beginning of inspection. Repaired by operator.

View this inspection on the county portal ›

Apr 22, 2025 4 demerits · 1 violation
Inspector comments: No night swimming. Permit restriction - Flow meter must remain operable. Flow required no greater than 119gpm due to drain cover flow restriction.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision” and "Adults should not swim alone" in 1" lettering. Observed 3/4” lettering for signage stating “children should not use the pool without adult supervision” and “adults should not swim alone”. CDI: CPO provided new signage with 1” lettering.

View this inspection on the county portal ›

Apr 25, 2024 4 demerits · 1 violation
Inspector comments: NOTE: - The flow meter was not operable at the time of inspection. The red bobbin stocked at the bottom. CPO fixed the issue at the time of inspection. The flow read at 41 GPM. PERMIT RESTRICTION: Flow meter must remain operable. Flow required no greater than 119 GPM due to drain Cover Flow restriction. - CPO: Kara Gilchrist present during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.- Observed one of the gate to residential is not self- latching. Fixed the issue with WD-40 during the inspection.

View this inspection on the county portal ›

Apr 26, 2023 6 demerits · 2 violations
Inspector comments: No night swimming
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed missing end caps on ladders.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool deck furniture < 6’ from edge of pool. CDI

View this inspection on the county portal ›

Apr 13, 2022 12 demerits · 3 violations
Inspector comments: EHS confirmed PDSC information during inspection. Operator Kara Gilchrist on site during inspection. Permit issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed a missing weir, closest to pool entrance. Kara Gilchrist provided weir and replaced during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed missing end cap on ladder in deep end.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy with ropes that were frayed and damage. CDI- Kara Gilchrist provided new ring buoy on site during inspection.

View this inspection on the county portal ›

Apr 19, 2021 14 demerits · 4 violations
Inspector comments: Kara Gilchrist present during the inspection. Verified pumps and main drain covers. Equalizers are plugged per state regulations. Permit issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2517(a)1 Diving equipment shall be installed per manufacturer's instructions. Observed missing ladder end cap. Replace.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.Observed ring buoy more than the required length, measured at 51ft. CDI - CPO adjusted the length to 50ft during the inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed deck chairs and lounging chairs less than 6 ft from the pool. CDI - CPO relocated the chairs and lounge chairs.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. Observed missing backflow preventer on outside hose bib.

View this inspection on the county portal ›

May 14, 2020 10 demerits · 4 violations
Inspector comments: due to covid-19 restrictions report will not be signed by cpo night swimming at this pool is prohibited. skimmer equalizer lines are plugged in skimmers.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. observed floating debris in skimmers. CDI
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. observed missing end caps on ladder in deep end.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(6) Provide sufficient lighting in chemical storage room. add light bulb in pump room
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. provide air gap at drain

View this inspection on the county portal ›

Apr 17, 2019 16 demerits · 6 violations
Inspector comments: 16. 3 units that open to pool deck area are required to have audible alarms or not open >4" on sliding glass doors. Residents should be notified of this. 28-29. There are no pool restrooms 28. There are no restroom facilities at this pool
#3 · Water quality: pool water pH −6
pH corrected to 7.8 during inspection
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Missing bumper, ladders should be > 6" from the pool wall
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Replace light bulb, natural cross or continuous forced ventilation required
#27 · Equipment room: filter backwash discharged through an air gap −2
2" air gap required
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Fill spot > 2" from pool edge
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Hose bib for pool at pump room, which is > 100' from pool

View this inspection on the county portal ›

Apr 27, 2018 0 demerits · 0 violations
Inspector comments: 16) .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed fence horizontals are wider than 4". If fence is changed, it must be in compliance with post 2010 regulations.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 24, 2017 12 demerits · 4 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed depth and "NO DIVING" markers faded and needing repainting before next pool season. REPEAT.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed >4" openings in vertical members of pool fence.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump room floor wet.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap provided at backwash pit.

View this inspection on the county portal ›

Apr 28, 2016 8 demerits · 2 violations
Inspector comments: Permit pending due to corrected PDSC form Pump - hayward SP2615x20 Drains - SDX retro Covers - Aquastar A10RCFR
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Touch up the 'No Diving" and Depths with more paint
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed cracking of the paint on the pool deck

View this inspection on the county portal ›

Apr 17, 2015 10 demerits · 3 violations
Inspector comments: NOTE: Permit will be posted online within 3 days at meckpools.charmeck.org.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed > 4 inch gaps through fence.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed chairs < 6ft around deck. Moved back during inspection.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap @ backwash. CDI - Pipe lifted so air gap was visible.

View this inspection on the county portal ›

Apr 22, 2014 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fence has cross members <45" apart. Gates and fences are < 48" at private patio entrances to condos.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No cross ventilation in pump room, walls are damaged and the light is out.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “BAYBRIDGE CONDOMINIUMS” or State ID 2060500653). Inspection type (routine vs. follow-up) is not published in the county's data.