WEXFORD APARTMENTS

1811 WEXFORD MEADOWS LANE, Charlotte, NC 28262
Seasonal Swimming Pool · NC permit/State ID 2060500707
Latest result4 demerits
Last inspectedMay 21, 2026
Inspections on record19
On record sinceJun 27, 2013

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01938 Jun 27, 2013: 12Jun 27, 2013: 12Jun 26, 2014: 22Jun 17, 2015: 18Jun 21, 2016: 18Jun 27, 2017: 10Jun 29, 2017: 0Jun 22, 2018: 14May 10, 2019: 10May 22, 2020: 18Jun 30, 2021: 10Jun 2, 2022: 4May 19, 2023: 38Jul 6, 2023: 22Aug 17, 2023: 12May 23, 2024: 0May 16, 2025: 24Aug 12, 2025: 0May 21, 2026: 4
Jun 27, 2013Lower is betterMay 21, 2026

Inspections & violations

May 21, 2026 4 demerits · 1 violation
Inspector comments: Permit Restriction: Flow meter must remain operable. Flow required at 71 gpm to 74 gpm to meet turnover and flow restriction of the filter. Flow greater than 138 gpm is suction hazard for equalizer line cover. Suction hazard. NIGHT SWIMMING NOT PERMITTED
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed some pool chairs less than 6 feet from pool surface. Chairs were rearranged during inspection to allot 6 foot clear walking space around pool.

View this inspection on the county portal ›

Aug 12, 2025 0 demerits · 0 violations
Inspector comments: Re-inspection complete All required items confirmed: New Pump Pentair Whisperflo VST, 011533, 2.6 THP pump. New Permit Restriction: Flow meter must remain operable. Flow required at 71 gpm to 74 gpm to meet turnover and flow restriction of the filter. Flow greater than 138 gpm is suction hazard for equalizer line cover. Blue White Flow meter reading the above permit restriction. Main drain, skimmer, return line all 2” line coming out of pump room floor. 2008 Waterway 640-472x drain covers. (2) Waterway 640-822x equalizer line covers with (2) skimmers. (1) Pentair TR100 filter. (6) returns, either on the floor or the wall.

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 16, 2025 24 demerits · 5 violations
Inspector comments: The following items need to be corrected: 1. Emergency phone: Need to be able to call the number and the box/phone connects, can hear the voice calling. 2. Pump needs to be grounded. Very Important. 3. Pump needs to be inspected and passed by an electrician. 4. Call main office to schedule an in field plan review 5. A new PDSC form will need to be filled out and approved. 7. Ensure Record book is on hand at facility. 8. Ensure there is a shower sign up and visible
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. No daily records/record book on hand at facility.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed length of rope exceeding 29 ft. CDI PIC corrected during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Observed in back right corner gap under fence exceeding 2 inches.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Kings phone connects to 911 but cannot call associated number back to box. Phone number does not connect back.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(h) Provide approved pump in good repair. Observed new pump that has not been approved. Observed grounding wire not connected.

View this inspection on the county portal ›

May 23, 2024 0 demerits · 0 violations
Inspector comments: PO put bicarbonate in pool right before inspection today to adjust pH. No violations observed today

No violations were recorded for this inspection.

View this inspection on the county portal ›

Aug 17, 2023 12 demerits · 2 violations
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. CDI - Facility added sodium bicarbonate and raised pH to 7.7
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed Kings III box gave message that it was disconnected when button was pushed. Box would not call emergency number. CDI - Management called Kings III and had box reconnected.

View this inspection on the county portal ›

Jul 6, 2023 22 demerits · 4 violations
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine at 0.4 ppm. PERMIT DENIED.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed pool log missing main drain column. CDI - Facility has new record sheets that were approved and have all record keeping requirements.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible. Observed body hook was telescoping and hook was not secured to pole.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed phone number for emergency phone was incorrect. CDI - Correct emergency phone number was listed.

View this inspection on the county portal ›

May 19, 2023 38 demerits · 8 violations
Inspector comments: EHS confirmed pump, drain covers, equalizer covers as per PDSC form. Permit denied due to issues with emergency phone, no body hook, missing fittings and improper pH and chlorine levels. Once non complaint items are fixed, call main office at 980-314-1620 to pay reinspection fee and schedule next inspection.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed test kit reading 0ppm chlorine during inspection.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH of pool at 8.4 when tested.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed record keeping sheet that does not include daily checks of drain covers. Add section for checking drain covers to daily log sheet.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed missing weirs (flapping doors) in both of the skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed ladder missing rubber caps.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed large fitting missing near 3 FT depth marker (across from ladder), appears to be an overflow with a missing grate, safety hazard- large opening with potential to get hands/arm inside.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. Observed no body hook during inspection. Ensure body hook is attached to a NON collapsible pole.
#22 · Premises: emergency telephone provided −6
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. Observed Kings III phone that was unable to connect to emergency operators. Message continued to repeat, no connection. Operators attempted to call Kings III during inspection, unable to fix during inspection.

View this inspection on the county portal ›

Jun 2, 2022 4 demerits · 1 violation
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed white rubber fittings missing from railing on the left side of pool.

View this inspection on the county portal ›

Jun 30, 2021 10 demerits · 3 violations
Inspector comments: no night swimming
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
ladder missing one bumper
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
throw rope cut to 29ft and replaced during inspection
#27 · Equipment room: filter backwash discharged through an air gap −2
filter back wash needs 2'' air gap

View this inspection on the county portal ›

May 22, 2020 18 demerits · 5 violations
Inspector comments: Due to COVID19 pandemic no signature occurred. CPO Juan Perez was present during inspection. Permit Conditions inserted on permit: “Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.” Night swimming not approved until return visit occurs for approval.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 - Rails and ladders shall be maintained in good repair. - Observed ladder on 5.5ft side of pool loose in need of tightening down.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed throw rope to be 28FT. CDI- CPO- Provided rope at 29FT prior to the end of the inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Observed dialing instructions faded and non legible on the emergency phone. CDI- CPO provided permanent dialing instruction on emergency phone prior to the end of the inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(k) Provide shatterproof mirrors. - in the restrooms mirrors could not be verified to be shatterproof.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed hose bib near pool deck without backflow prevention device.

View this inspection on the county portal ›

May 10, 2019 10 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders missing rubber bumpers. Needs to be replaced. **.2521 Install ladders per manufacturer instructions.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed rope length at 27FT. Corrected during the inspection - New rope provided. **.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed pipe dripping at the handwash sink. Needs to be repaired. **.2626(m) Keep restrooms and fixtures clean and in good repair.

View this inspection on the county portal ›

Jun 22, 2018 14 demerits · 4 violations
Inspector comments: 9. One 3ft depth marker cracked -- Repair/replace
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Daily record log did not include drain checks -- Corrected
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope in poor condition -- Replaced
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Piping not labeled -- Label all piping in pump room
#27 · Equipment room: filter backwash discharged through an air gap −2
No backflow prevention on hose bib near door.

View this inspection on the county portal ›

Jun 29, 2017 0 demerits · 0 violations
Inspector comments: The pump model number was unable to be seen on the pump. The picture in the VGB book matched what was listed on the PDSC sheet. Other items on the PDSC sheet were correct. Facility has adjusted the door leading to the bathroom/laundry room to self-close and self-latch. The handle will always be locked from the inside of the laundry room so that no one can run out onto the pool deck. Residents will use the same key to unlock the door as they do to unlock the bathrooms. The door from the outside leading to the bathrooms will be unlocked now.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Jun 27, 2017 10 demerits · 2 violations
Inspector comments: The door from the laundry room leading on to the pool deck does not have a sensor on it; it stays unlocked so people can use the bathroom. The other door leading into the laundry room from the outside has a self locking handle. Residents have a key to get in to use the laundry room. People in the laundry room could still open the door to the pool deck without anyone knowing because there is no sensor. Recommend placing a sensor on the door. Pictures have been taken. I will follow up with Katie Wilson to discuss the matter. Spoke with Chris Elmore about the previous inspection. The pump model number was unable to be seen on the pump. The picture in the VGB book matched what was listed on the PDSC sheet. Other items on the PDSC sheet were correct.
#3 · Water quality: pool water pH −6
Observed the pH at 7.0; CPO tried to correct it but it went up to 8.2. Immediate suspension has been issued and the pool is closed.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
The gate would not self close or latch. Corrected during the inspection; the tension on the hinges was adjusted to make it self close and latch.

View this inspection on the county portal ›

Jun 21, 2016 18 demerits · 6 violations
Inspector comments: G.C. Observed ER phone to work properly, but to give fax # 704-510-1858. Correct the phone number with 911 so that a voice phone number is given.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed 1 cracked depth marker tile. Replace or repair the tile.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder to be missing rubber feet. Replace them.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed buoy rope to be 38ft. long. 29ft. is required. Rope was corrected. CDI
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at backflow line.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed leaking sink drain line. Repair it.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Observed no backflow preventer on hose bibb. Provide backflow preventer on all hose bibbs.

View this inspection on the county portal ›

Jun 17, 2015 18 demerits · 5 violations
#2 · Water quality: disinfectant residual provided by −6
Observed chlorine level was at 0.2ppm.**Maintain chlorine level at least 1.0ppm
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed missing end caps on ladders.**Provide end caps on all ladders to prevent injury.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed 2 missing inlet covers on the pool wall.**Damaged or missing fitting shall be replaced.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed the flow meter was not functioning.**Repair or replace flow meter.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Observed some pipes were no labeled.**Label all pipes and valves with direction of water flow.General Comment - Taylor Butler was present.***Immediate Suspension issued for #2

View this inspection on the county portal ›

Jun 26, 2014 22 demerits · 6 violations
Inspector comments: Emergency Phone line is using fax line. 911 will not be able to call the office during business hours without the correct number. Immediate Suspension issued for #15.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed missing turtle style floats under skimmer baskets. Observed one loose weir. Keep skimmers in good repair.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders missing end caps. Repair the ladders.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed inlets missing eyeball covers. Replace missing covers.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy damaged and attached rope less than 29 ft long. Replace ring buoy with approved US Coast Guard ring buoy and install a 298 ft rope on the new ring buoy.
#18 · Premises: lifeguards present or warning signs posted −4
Observed Warning No Life Guard on Duty Sign with less than 4 inch tall letters. Purchase and install the approved sign.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at back wash line. Provide air gap.

View this inspection on the county portal ›

Jun 27, 2013 12 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Provide ring buoy with throw rope measuring correct length; Observed 18ft needed 30ft, rope provided with correct length.
#22 · Premises: emergency telephone provided −6
Provide functional emergency phone; Observed kings three with no power. System fixed and operational.

View this inspection on the county portal ›

Jun 27, 2013 12 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
'Provide ring buoy with throw rope measuring correct length.
#22 · Premises: emergency telephone provided −6
Provide functional emergency phone; Observed kings three with no power. System fixed and operational.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “WEXFORD APARTMENTS” or State ID 2060500707). Inspection type (routine vs. follow-up) is not published in the county's data.