4demerits
LANDINGS APARTMENTS
16938 LANDINGS DRIVE, Huntersville, NC 28078
Seasonal Swimming Pool · NC permit/State ID 2060500736
Latest result4 demerits
Last inspectedJun 3, 2026
Inspections on record14
On record sinceMay 27, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 27, 2014Lower is betterJun 3, 2026
Inspections & violations
Jun 3, 2026 4 demerits · 1 violation
Inspector comments: Night Swimming Not Permitted
Pool will update Emergency Phone system to Kings III during the pool season. Operator has been advised that:
Emergency phone shall remain operable.
Pool telephone shall be capable of directly dialing 911 or another emergency notification system.
Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
1.Permit Restriction: Flow meter must remain operable. Flow required at 138 gpm to meet turnover and flow restriction of the suction lines.
2.New Pump Pentair Intelliflo3 VSF 011076, 3 hp pump
3.Aquastar FM30 flow meter reading 138 gpm +/- 5%.
4.3” main drain, skimmer, and return line.
5.(2) Aquastar 1216xxx 2017 drain covers
6.(4) skimmers with 2008 Waterway 640-8240x equalizer line covers
7.(2) Pentair TR 100C
8.(8) returns, either on the floor or the wall.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Observed test kit with an expiration of 5/26. Pool operator ordered new test kit during inspection.
Jun 5, 2025 6 demerits · 2 violations
Inspector comments: NOTE:
- NIGHT SWIMMING IS NOT PERMITTED.
- Maintenance: Ronnie Blackwelder present during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
REPEAT
.2521(b) Ladders shall have slip-resistant tread.- Observed two missing slip resistant tread on one of the ladder, same side the entrance way. The part was ordered and are on the way and will be replaced by Caribbean pool. Ensure to replace slip resistant treads.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
REPEAT
.2537(b) All gates and doors shall be self-closing, self-latching.- Observed back side gate with chain around it, unlocked the chain and tested. The gate is not self latching. CDI- the gate is now screwed dead piece of metal to keep it permanently lock. Maintenance stated the gate was used for groundskeeper, now on they will be using the front only gate instead.
May 23, 2025 20 demerits · 5 violations
Inspector comments: NOTE:
- This pool # 500736, permit denied today due to following items on the inspection sheet.
- All items needs to be repaired/replaced, and ensure it is in good working condition.
- Contact EHS: 704-617-9777 or email for return inspection to obtain the operational permit.
- The pool shall remain closed until permit is issued.
- Please call the office (980-314-1620) to make a payment of a return visit fee is $100. Fee must be paid through the office prior to inspection request.
- NIGHT SWIMMING IS NOT PERMITTED
- Drain covers will be expired on 3/16/2026
- Maintenance and Maintenance supervisor: Richard and Ronnie, property manager: Amber present during operational permit inspection.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm.- Observed 0.2 ppm of chlorine in the pool water. Chlorinator needs to be working properly and automatically feed the chlorine into the pool.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Ladders shall have slip-resistant tread.- Observed two missing slip resistant tread on one of the ladder, same side the entrance way. Ensure to replace slip resistant treads.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.- Observed back side gate with chain around it, unlocked the chain and tested. The gate is not self latching. CDI- adjusted the hatch of the gate, and it is now self latching at the time of inspection. Ensure to keep all gates working and remain self-closed/latched.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.- Observed window in the office that lead to a pool deck, it can be opened wide greater than 4’’. Need audible alarm or limit the opening access less than 4”.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times.- Observed lounge chairs and table from edge of the pool measured at 3ft -5ft. CDI- furniture rearranged at the time of inspection and provided 6ft clearance.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational.- Observed a red bubble of the flow meter stuck at the bottom reading zero. Repair or Replace a flow meter.
.2519(k) Provide operational pressure gauge on filter.- Observed one of a pressure gauge on the left sand filter is not working, read at zero. Repair or Replace a pressure gauge.
Jun 20, 2024 4 demerits · 1 violation
Inspector comments: Night swimming not permitted.
Permit issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers with build up of debris.
May 3, 2023 6 demerits · 1 violation
Inspector comments: CPO Terry Paskadi present during inspection.
Night swimming not permitted.
EHS confirmed pump, drain covers and equalizer covers during inspection.
Permit issued.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 8.2 when first tested. CDI- CPO adjusted acid feeder, pH at 7.8 at end of inspection.
May 17, 2022 0 demerits · 0 violations
Inspector comments: Terry Paskadi present during the inspection.
NO violations noted during the inspection.
Night swimming is NOT permitted.
No violations were recorded for this inspection.
May 20, 2021 0 demerits · 0 violations
Inspector comments: No violations noted on this re-inspection. 911 operator called back on Kings iii phone by using posted number at phone.
No violations were recorded for this inspection.
Jun 1, 2020 4 demerits · 1 violation
Inspector comments: Pool will not be opening for night swimming. Pool operating hours are from 10a -8p. No night swimming visit is required. Observed pool had equalizers Custom Molded Products Model # 25207 that was not in 2020 Pool Operating Season Book. Equalizer and model number was looked up and verified online but just needs to be added to the Pool Book.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed windows in leasing center opening > 4". Pool operator placed screws in window to prohibit windows from opening > 4".
May 14, 2019 2 demerits · 1 violation
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed loose recess ladders. Corrected during inspection.
May 22, 2018 0 demerits · 0 violations
No violations were recorded for this inspection.
Jun 5, 2017 10 demerits · 3 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed several pavers protruding up more than 1/2"
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed the flow meter not operating
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed a small leak at the pump
Apr 7, 2016 10 demerits · 3 violations
Inspector comments: Pool passed pre-inspection pending VGB form approval - Katie making an OSV 4/7/16.
Report received by Walter Pearce
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Keep baskets free of debris, replace cracked skimmer cover
#18 · Premises: lifeguards present or warning signs posted −4
Lettering size and verbage incorrect, sign replaced during inspection
#27 · Equipment room: filter backwash discharged through an air gap −2
2" air gap required on backwash line
May 15, 2015 0 demerits · 0 violations
Inspector comments: Received a call from Kim Garret asking me to go by the pool and check to see if the phone is working. It is now operating.
No violations were recorded for this inspection.
May 27, 2014 20 demerits · 5 violations
Inspector comments: 17..Provide 6' of clearance around pool. Observed deck chairs <6' from pool- operator moved them to correct.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed one missing weir today- replaced during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gate not self closing today- must be self closing, self latching- repaired by operator today.
#22 · Premises: emergency telephone provided −6
Observed no phone number posted @ emergency phone today- added to sign today to correct.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed the flow meter not working today- repaired during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed 117F water in restrooms today- Hot water should not exceed 110F.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “LANDINGS APARTMENTS” or State ID 2060500736). Inspection type (routine vs. follow-up) is not published in the county's data.