SPINNAKER POINT

924 JETTON ST, Davidson, NC 28036
Seasonal Swimming Pool · NC permit/State ID 2060500750
Latest result10 demerits
Last inspectedApr 22, 2026
Inspections on record14
On record sinceApr 17, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0612 Apr 17, 2014: 10Apr 24, 2015: 0Apr 28, 2016: 10Apr 13, 2017: 4Apr 19, 2018: 2Apr 15, 2019: 12Apr 23, 2020: 8Apr 16, 2021: 8Apr 22, 2022: 12Apr 27, 2023: 8Apr 22, 2024: 0Apr 10, 2025: 10Apr 30, 2025: 0Apr 22, 2026: 10
Apr 17, 2014Lower is betterApr 22, 2026

Inspections & violations

Apr 22, 2026 10 demerits · 3 violations
Inspector comments: NO NIGHT SWIMMING. Permit Restriction - Flow meter must remain operable. Flow required at 119 gpm or less due to flow restriction of drain covers. Suction Hazard.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed deck chairs < 6’ from pool edge. CDI
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed sign less than 4” lettering. CDI- replaced by CPO
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed discharge pipe in the drain.

View this inspection on the county portal ›

Apr 30, 2025 0 demerits · 0 violations
Inspector comments: General Comment: No violations noted Automated chlorinator not in use. Permit restrictions written on permit.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 10, 2025 10 demerits · 2 violations
Inspector comments: NOTE: Automatic feeder not in use. Flow meter operable and at 119GPM. Permit denied. Please call front office for fee payment and re-inspection, 980-314-1620.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed no updated paperwork for removal of equalizers. Facility is supposed to have 4 equalizers. All covers are missing, paperwork does nor reflect change.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed depth markers 30 FT apart. CDI- Marker placed between the 30Ft markers.

View this inspection on the county portal ›

Apr 22, 2024 0 demerits · 0 violations
Inspector comments: NOTE: - Permit Restriction: Flow meter must remain operable. Flow required at 119 GPM or less due to flow restriction of drain covers. - No violation observed at the time of inspection. - PIC: Mr. Brian Pridmore present during inspection permit.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 27, 2023 8 demerits · 2 violations
#22 · Premises: emergency telephone provided −6
emergency phone not working CPO replaced phone during inspection
#27 · Equipment room: filter backwash discharged through an air gap −2
no air gap for back wash

View this inspection on the county portal ›

Apr 22, 2022 12 demerits · 4 violations
Inspector comments: EHS confirmed that screw has been replaced in drain cover. EHS confirmed PDSC information. Operator Kara Gilchrist on site during inspection. $100 dollar reinspection fee paid. Permit issued.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine levels at 0.4 when tested. CDI- Pressure was too high on filter, chlorine was not dispensing properly. CPO backwashed and chlorine levels rose to 4.0ppm.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed no cap on end of ladder.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap for discharge at backwash.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. Observed no backflow preventer at hose bib at pool deck.

View this inspection on the county portal ›

Apr 16, 2021 8 demerits · 2 violations
Inspector comments: Kara Gilchrist on site today. No night swimming.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. observed rope length >42'. CDI
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. need backflow device at pool deck hose bib.

View this inspection on the county portal ›

Apr 23, 2020 8 demerits · 2 violations
Inspector comments: Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order. All 4 and 6 point demerit items in compliance by end of inspection. Night swimming is NOT permitted.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope at 40ft. CDI: New rope provided at 42ft. REPEAT VIOLATION
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. Observed no back flow preventer on hose bib on deck. REPEAT VIOLATION

View this inspection on the county portal ›

Apr 15, 2019 12 demerits · 3 violations
Inspector comments: CPO Kara Gilchrist was present during the inspection. Night Swimming is not permitted.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed buoy rope to be 41 ft. Rope length shall be 42 ft. CDI- CPO provided a new rope at 42 ft.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(e) Provide a spare basket for pump. - Observed no spare pump basket available during the inspection. CDI- CPO provided a spare pump basket.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
(.2512) - Provide back flow prevention. - Observed no back flow prevention device on the hose bib located on the pool deck.

View this inspection on the county portal ›

Apr 19, 2018 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
observed water on the floor in the pump room.

View this inspection on the county portal ›

Apr 13, 2017 4 demerits · 1 violation
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed "NO DIVING" spray painted letters on deck faded and will need re-painting by next season.

View this inspection on the county portal ›

Apr 28, 2016 10 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed one weir stuck. Repair.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed "NO DIVING" markers faded. Re-paint.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed missing endcap on ladder.

View this inspection on the county portal ›

Apr 24, 2015 0 demerits · 0 violations
Inspector comments: Observed mesh installed on fence. Observed tile replaced. Observed skimmer equalizer line uncovered. Permit inspection pass45rl4ed. Permit not valid until available online

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 17, 2014 10 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope length too long - corrected during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
observed cracking on pool deck

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “SPINNAKER POINT” or State ID 2060500750). Inspection type (routine vs. follow-up) is not published in the county's data.