8demerits

LEXINGTON SWIMMING POOL

11030 TAVERNAY PARKWAY, Charlotte, NC 28262
Seasonal Swimming Pool · NC permit/State ID 2060500766
Latest result8 demerits
Last inspectedApr 9, 2026
Inspections on record15
On record sinceJun 17, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01632 Jun 17, 2014: 12Jun 15, 2015: 2Jul 19, 2016: 32Jul 5, 2017: 4Apr 18, 2018: 6May 24, 2019: 2Jun 1, 2020: 6Jun 3, 2020: 0Apr 9, 2021: 4May 3, 2022: 2Apr 12, 2023: 2May 1, 2024: 12May 10, 2024: 8May 22, 2025: 12Apr 9, 2026: 8
Jun 17, 2014Lower is betterApr 9, 2026

Inspections & violations

Apr 9, 2026 8 demerits · 2 violations
Inspector comments: Flow meter must remain operable. Flow not to exceed 340 GPM. No night Swimming
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed slight debris present on pool surface. Clean as needed
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed slight debris in skimmers. Clean as needed.

View this inspection on the county portal ›

May 22, 2025 12 demerits · 2 violations
Inspector comments: Not approved for night swimming Flow meter does not exceed 340 gpm.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed 1 of the 2 ring buoy ropes longer than required 50ft. CDI PO adjusted rope to 50 ft.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed emergency phone not ringing when calling back in. CDI PO switched out phone. Also observed sign with address and phone number at least 10 ft away from the actual emergency phone. PO made a sign and put it on the wall above the phone.

View this inspection on the county portal ›

May 10, 2024 8 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed pool floor in need of cleaning
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed deck with several cracks/ chipping pieces

View this inspection on the county portal ›

May 1, 2024 12 demerits · 3 violations
Inspector comments: operator on site: Griffin Ballard
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed depth marker for 31/2 FT side of the pool spaced over 25FT apart. .2523(d) The distance between no diving markers shall be no more than 25 feet perimeter or as the crow flies. Observed no diving marker over 25FT at the 3 1/2 part of the pool.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed clubhouse doors not self closing and latching or self closing with audible alarm.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed cracks on deck.

View this inspection on the county portal ›

Apr 12, 2023 2 demerits · 1 violation
Inspector comments: Observed 267 gpm on flow meter. No night swimming requested.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed high ventilation for cross ventilation without a low ventilation area. Provide a lower level ventilation. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Observed dry chemical spill in chemical storage area. CDI - Operator cleaned.

View this inspection on the county portal ›

May 3, 2022 2 demerits · 1 violation
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed ladder railing loose. CDI: CPO secured railing.

View this inspection on the county portal ›

Apr 9, 2021 4 demerits · 1 violation
Inspector comments: PDSC verified.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(e) Provide a spare basket for pump. No basket available. Obtained.

View this inspection on the county portal ›

Jun 3, 2020 0 demerits · 0 violations
Inspector comments: No violations during the inspection. Previous issues with phone resolved.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Jun 1, 2020 6 demerits · 1 violation
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. - Observed address not identifiable when calling 911.

View this inspection on the county portal ›

May 24, 2019 2 demerits · 1 violation
Inspector comments: Non-adequate lighting for night swimming.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump room floor with moisture under piping. Ensure pump room floor stays dry. .2533(d) Pump room floor shall be kept dry and free of standing water. Observed forced air fan not working. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room DJ Scott present for inspection.

View this inspection on the county portal ›

Apr 18, 2018 6 demerits · 2 violations
Inspector comments: NO POINTS WERE TAKEN FOR THE FOLLOWING: PDSC information verified. No night swimming.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed Operator to not have access to clubhouse to confirm if doors to pool were self-closing/self-latching or if they were protected by an audible alarm. CDI: Operator gained access by end of inspection and it was found that the doors were not self-closing/self-latching and they did not have an alarm. Windows had inhibitors that came out from window frame that do limit window openings to less than 4 inches. Operator obtained two alarms for the two separate access doors by end of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump room floor with moisture under piping. Ensure pump room floor stays dry. .2533(d) Pump room floor shall be kept dry and free of standing water. Observed forced air fan not working. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.

View this inspection on the county portal ›

Jul 5, 2017 4 demerits · 1 violation
Inspector comments: G.C. Observed 3 pumps in pump room connected to 3 2HP motors. 1 motor housing label reads CFII-NR5FE, which is a 5HP. Steven Eddings was contacted and stated that the impeller is a 2HP impeller as reflected on the PDSC form. This will be referred to Katie Wilson of MCHD for follow-up.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gate not self-closing/self-latching. Correct gate, using proper methods, such that it is fully self-closing/self-latching. Observed cross piece on one gate to be on the outside of the gate and to be less than 45" apart. Pool built in 1997.

View this inspection on the county portal ›

Jul 19, 2016 32 demerits · 8 violations
Inspector comments: Intent to suspend issued. 5) 17)
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No recent total alkalinity or cyanuric acid checks. Check daily Cl, pH, main drains and at least weekly CYA and TA. - Intent to suspend item.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC form does not match what is in place. Pool actually has 12 equalizer line covers.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir stuck. Provide functional weirs. Some skimmer baskets weighted down with rocks. Use only NSF approved skimmer baskets.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder loose. Maintain secure and in good condition.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chairs too close to pool edge. Maintain at least 8 feet clear walkway around pool. - Intent to suspend item. Observed one of the anchors sticking up. Maintain deck free of trip hazards.
#22 · Premises: emergency telephone provided −6
Emergency phone unhooked at time of inspection. Provide functional emergency phone. Corrected. Emergency phone around the corner out of sight. Provide signage alerting bathers to the location of the emergency phone.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in pump room or chemical storage room. Provide either cross or forced air ventilation for both rooms. Leak at pump. Fix leak.

View this inspection on the county portal ›

Jun 15, 2015 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed the restroom mirrors were not shatterproof. **Restroom mirror shall be oif shatterproof material.General Comment - Thekla Meli was present during the inspection.#9 - Observed the "no diving" marker near the mair stairs is beginning to fade. **Re-stencil all the faded "no diving" markers.

View this inspection on the county portal ›

Jun 17, 2014 12 demerits · 3 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Maintain NO DIVING markers visible. Observed NO DIVING MARKERS faded but still visible. Markers will need to be re-painted by next season.
#22 · Premises: emergency telephone provided −6
Maintain a working emergency phone. The 911 operator was unable to hear anything from the phone. The phone was replaced with a properly working phone.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Properly store chemicals. Observed a bag of calcium chloride stored on the floor of the chemical room.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “LEXINGTON SWIMMING POOL” or State ID 2060500766). Inspection type (routine vs. follow-up) is not published in the county's data.