4demerits
TWIN OAKS
19901 OAK LEAF CIR, Cornelius, NC 28031
Seasonal Swimming Pool · NC permit/State ID 2060500785
Latest result4 demerits
Last inspectedJul 9, 2026
Inspections on record13
On record sinceJun 2, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 2, 2014Lower is betterJul 9, 2026
Inspections & violations
Jul 9, 2026 4 demerits · 1 violation
Inspector comments: Night swimming not permitted
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed missing weir near 3' depth marker.
May 14, 2025 4 demerits · 1 violation
Inspector comments: Night swimming not permitted
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed bench and table less than 6ft from pool edge.
May 20, 2024 0 demerits · 0 violations
No violations were recorded for this inspection.
May 23, 2023 0 demerits · 0 violations
Inspector comments: EHS discussed that drain covers and equalizer covers are set to expire 5-1-2024. Check information on PDSC form, will require new form to be submitted and approved by MCHD.
NO night swimming at this location, per CPO.
No non compliant items, permit issued.
No violations were recorded for this inspection.
Aug 5, 2022 0 demerits · 0 violations
Inspector comments: Observed no non compliant conditions
Permit issued
No violations were recorded for this inspection.
May 13, 2021 0 demerits · 0 violations
Inspector comments: No out-of compliance issues noted today on this return visit. Iron gate has been made part of the permanent unbroken barrier.
No violations were recorded for this inspection.
May 18, 2020 4 demerits · 1 violation
Inspector comments: pool does have no diving markers around pool
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Fill in cracks around pool
Jun 20, 2019 10 demerits · 4 violations
Inspector comments: Restrooms are to remain available when the pool is open.
Metal gate with latching mechanism removed. Gate is part of the barrier. Front entery is at mailbox location.
Continue to monitor decking to ensure no gaps or offsets > 1/2".
CYA at 100ppm. This is the maximum allowed. Recommend draining and adding fresh water to maintain CYA below 100ppm.
Permit issued with the following condition:
No night swimming
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Provide spare pump basket for pump. Corrected by operator.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump room or chemical storage room.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bibb or floor drains in restrooms. .2626(c) Floor drains shall be provided in restrooms.
.2626(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose.
May 23, 2018 10 demerits · 3 violations
#13 · Pool maintenance: contrasting band on steps and benches −4
Pool built with bench more than 18" wide.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed secondary gate secured permanently to brick wall. As part of fence now observed more than 2" from distance under fence to first horizontal member. Pool built prior to 2010.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump room or chemical storage room. Provide either cross or continuous forced air ventilation.
Jun 15, 2017 4 demerits · 2 violations
Inspector comments: Barbara Cormier was present during the inspection. All suspension items corrected and PDSC form was verified. Inspection emailed to splishsplashpool@yahoo.com
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump room or chemical storage room. Provide either cross or continuous forced air ventilation in pump room and
chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Provide air gap for backwash.
Jul 19, 2016 42 demerits · 11 violations
Inspector comments: Provide chemical placard on building where chemicals are stored.
Intent to suspend issued.
9)
12)
24)
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC form does not match what is installed. Actually have Aquastar 8HP equalizer line covers. - Corrected form submitted and approved.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
More than 25 feet between depth markers. Depth markers shall be no more than 25 feet apart as measured along the perimeter of the pool. Depth markers shall be either a 6x6 inch tile or written in at least 4 inch lettering. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose. Maintain secure and in good condition.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed only one functional inlet. Provide functional inlets. - Intent to suspend item.
Provide directional inlet fittings for inlets. Only one, non-functioning inlet with directional fitting. - Intent to suspend item.
#13 · Pool maintenance: contrasting band on steps and benches −4
Pool built with bench more than 18" wide. Benches should not be more than 18" wide.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope 22 feet long. Corrected to 24 feet long.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate not self-latching. Provide self-closing and self-latching gate. Corrected by operator.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chairs too close to pool. Maintain at least 6 feet clear walkway around pool. Corrected by operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flex line used on pool piping. Use rigid Schedule 40 piping. - Intent to suspend item.
Flow meter stuck. Repair or replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemcals stored in pump room. Store chemicals in chemical storage room. Corrected by operator.
No ventilation in pump room or chemical storage room. Provide either cross or continuous forced air ventilation in pump room and chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Provide air gap for backwash.
Jun 24, 2015 10 demerits · 4 violations
Inspector comments: Intent to suspend issued for #18.
#18 · Premises: lifeguards present or warning signs posted −4
Signage incomplete
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Continuous forced or natural cross ventilation required
#27 · Equipment room: filter backwash discharged through an air gap −2
2" air gap required on back wash line
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Floor drain need in bathrooms
Jun 2, 2014 4 demerits · 1 violation
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed stuck flow meter on return line. CDI