NORTHSTONE COUNTRY CLUB-BACK
15801 NORTHSTONE DR., Huntersville, NC 28078
Seasonal Swimming Pool · NC permit/State ID 2060500832
Latest result4 demerits
Last inspectedMay 6, 2026
Inspections on record15
On record sinceMay 12, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 12, 2014Lower is betterMay 6, 2026
Inspections & violations
May 6, 2026 4 demerits · 1 violation
Inspector comments: PERMIT RESTRICTION: Flow meter must remain operable. VFD installed. Flow shall be maintained at 238 gpm - 360 gpm meet turnover and flow restrictionf the drain cover. Suction hazard.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed minor cracks in deck.
May 5, 2026 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Horizontals shall not be located less than 45" in height. Observed horizontals 28” from bottom. Fence is pre-2010. PERMIT DENIED
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Observed mirrors not shatterproof.
Apr 25, 2025 0 demerits · 0 violations
Inspector comments: Permit issued.
Night swimming is not permitted.
Permit restriction: Flow meter must remain operable. Flow shall not exceed 360 GPM due to drain Cover Flow restriction.
Flow meter reading: 220 GPM
PDSC states that this pool has 8 skimmers. EHS observed 10 skimmers on pool. Update PDSC to reflect this.
No violations were recorded for this inspection.
May 6, 2024 0 demerits · 0 violations
Inspector comments: Pool is open for the 2024 season. No night swimming. Lifeguard on duty when pool is open.
Flow meter was working properly less than 360 gpm.
No violations were recorded for this inspection.
May 6, 2024 0 demerits · 0 violations
Inspector comments: Pool is open for the 2024 season. No night swimming. Lifeguard on duty when pool is open.
Flow meter was working properly less than 360 gpm.
No violations were recorded for this inspection.
May 17, 2023 8 demerits · 2 violations
Inspector comments: David Johnson present during the inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 8 ft of clear walking space around the pool at all times (>1600 sq. ft). Observed 4 ft to 5 ft walking space between the furnitures and the edge of the deck. Furnitures rearranged to give at least 8 ft walking space during the inspection.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Warning - No Lifeguard on Duty" in 4" lettering. Observed faded No Lifegurad on Duty sign. Letter is not legible. The new sign posted to replace the old one during the inspection.
May 11, 2022 10 demerits · 3 violations
Inspector comments: No night swimming permitted.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder missing bumper end caps.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One inlet eye missing.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operating properly. Corrected during inspection.
May 17, 2021 8 demerits · 3 violations
Inspector comments: Night swimming NOT permitted.
Inspection completed with Jacob Wilks.
Report to 'Jacob Wilks'
No sign due to COVID-19.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris in skimmer baskets. CDI: CPO emptied baskets.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed end cap missing on bottom of ladder. CDI: CPO provided end cap.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed wet floor throughout various areas of pump room.
May 20, 2020 20 demerits · 6 violations
Inspector comments: Inspection conducted with Jacob Wilks. Due to COVID-19 precautions, inspection was not signed by the operator.
Note: Gate by tiki bar opens into the pool due to topography. Recommend having the gate open away from the pool.
One of the body hook poles is cracked. Recommend replacing with a new 12ft non-collapsible pole.
Permit issued.
No night swimming.
“Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in
effect unless such Orders are rescinded or superseded by another applicable Order.”
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One of the ladders not installed. .2521(a) Steps or ladders shall be provided every 75 ft along the shallow area perimeter. .2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate for Tiki Bar not self-closing or self-latching. .2528(a) Gates other than pedestrian access gates shall have a self-latching device. Latch corrected by operator, gate will remain locked when not in use.
#22 · Premises: emergency telephone provided −6
Incorrect phone number posted for emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Corrected by operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Pool recently replastered, eyeball fittings installed on vacuum lines. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. Corrected by operator.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Filters leaking. .2533(d) Pump room floor shall be kept dry and free of standing water.
Chemical storage room used for general storage. Store only pool chemicals in the chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Backwash line extends into backwash pit. .2513(b) Filter backwash shall be discharged through an air gap.
May 8, 2019 12 demerits · 4 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. One ladder missing safety end caps.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. PO could not locate key to non-used pool gate next to tiki bar, could not verify if self closing/ self latching. Gate securely closed with band clamps.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. Hose bib outside guard room needs backflow prevention device.
GENERAL COMMENT: Observed a few depth markers and No Diving markers on deck begining to fade, need repainting by next season. Permit issued.
Apr 19, 2018 16 demerits · 4 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537 Pool floors kept clean; Observed debris on pool floor in need of cleaning.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518, .2537 Keep skimmer system clean; Observed skimmer baskets having debris collected in need of cleaning.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530, .2537 Provide ring buoy with correct throw rope length; Observed rope too long (60Ft). rope cut to correct length 50Ft.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533, .2534, .2537 Keep equipment room dry; Observed wet pump room.
Keep equipment room in good repair; Observed wall damaged in pump room.
May 11, 2017 4 demerits · 1 violation
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed dibris in the skimmers. Advised to keep skimmers clean.
May 12, 2016 8 demerits · 2 violations
Inspector comments: Pool passed pre-inspection - pending update of VGB spreadsheet to reflect pump as Pentair EQK750
Report received by Amanda Shore
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
NO DIVING markers > 25' apart - 4 markers added during pool inspection
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck drain pieces are loose and need to be secured to prevent tripping
Jun 1, 2015 14 demerits · 5 violations
Inspector comments: Observed one equalizer line protruding a little under 2" from pool wall.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed one loose ladder and 2 loose handrails. Repair.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed 2 ring buoy throw ropes greater than 50FT. CDI-rope shortened to correct length.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump floor wet. Keep dry. Observed light/ventilation tied together. Provide continuous forced ventilation.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap provided at backwash pit. Provide air gap.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Observed no back flow prevention on hose bib. Provide.
May 12, 2014 12 demerits · 4 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris in the pool. Clean the pool.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed metal tent frames within 8 ft of pool. Maintain 8 ft of clearance around the pool.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed the pump room wet and the chemical room light not functioning properly. Keep the pump room dry and repair chemical room light.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at back wash pit. Provide air gap.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “NORTHSTONE COUNTRY CLUB-BACK” or State ID 2060500832). Inspection type (routine vs. follow-up) is not published in the county's data.