16demerits
STEELECROFT SWIM CLUB
15514 DEHAVILLAND DR., Charlotte, NC 28217
Seasonal Swimming Pool · NC permit/State ID 2060500898
Latest result16 demerits
Last inspectedMay 21, 2026
Inspections on record14
On record sinceJul 19, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jul 19, 2013Lower is betterMay 21, 2026
Inspections & violations
May 21, 2026 16 demerits · 3 violations
Inspector comments: .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
Main drains are expired.
PDSC form shows 12MFxxx
Covers observed Do not match the PDSC form.
Q-Status.
Inspection completed Alex Beasley.
No Night swimming permitted.
To schedule a reinspection there will be a $100 fee. Please call the main office 980-314-1620.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
PDSC form was submitted and main drains covers were not replaced. All equalizer covers were replaced and installed properly annoying patch to PDSC information.
Main drains are expired.
PDSC form shows 12MFxxx
Covers observed Do not match the PDSC form.
Q-Status.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Observed 2 cracked skimmers on left corner of the pool (Casing).
In need of repair.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed safety ropes at 47 ft when required to be 50 ft.
CDI - Ropes lengthened to be 50 ft.
May 21, 2025 8 demerits · 2 violations
Inspector comments: NIGHT SWIMMING NOT PERMITTED.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool furniture less than 6 feet from edge of pool deck. CDI, furniture relocated to provide required clearance.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter stuck. CDI, flow meter adjusted to become operable during inspection.
Apr 19, 2024 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. No ventilation in pump room.
Apr 18, 2023 0 demerits · 0 violations
No violations were recorded for this inspection.
Apr 28, 2022 8 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder rungs at >6" from pool wall. Maintain 3" to 6" between ladder rung and pool wall.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some deck drains with >1/2" between drains. Outside of required deck space. Corrected to <1/2” during inspection.
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Flooring in restrooms with chipping seal and does not appear slip-resistant. Flooring shall be in good repair and slip-resistant.
May 25, 2021 40 demerits · 11 violations
Inspector comments: Permit issued for no night swimming. Jeff Gaeckle and Brandon Vaughn present during the inspection.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC form not provided. New covers installed. Corrected during inspection.
(2) Equalizer lines plugged in skimmer. Removed during the inspection to match PDSC form. Verified Pentair EQK750, 7.5 hp pump with (2) Aquastar 1216xxx drain covers. (10) Aquastar 6HPHAxxx equalizer line covers.
One skimmer equalizer >1/2" from wall. Corrected during the inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
(2) skimmer weirs stuck. Corrected during the inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
3 ft. depth marker and No Diving marker at far step entry fading and not 4". Corrected during the inspection. Re-sprayed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder rungs at >6" from pool wall. Maintain 3" to 6" between ladder rung and pool wall.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy ropes >50 ft. Corrected during the inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Barrier <48" in height. Pool built 2000. Maintain 48" barrier.
Verified battery back-up present during the inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some deck drains with >1/2" between drains. Outside of required deck space. Required repair prior to 2022 operating permit.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
One pressure gauge with water. Continue to monitor to ensure operable.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Drain missing cover on floor drain. Hole in floor. Provide floor drain cover in pump room.
No fresh air intake in chemical storage room with forced draw. Recommend installing fresh air intake per mechanical code.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bib in men's restroom and pump room without backflow prevention device. Provide backflow prevention devices on all hose bibs.
Check valve in pump room listed as ASSE 1015. Required ASSE1013. Original construction. If ever changed, bring up to current code.
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Flooring in restrooms with chipping seal and does not appear slip-resistant. Flooring shall be in good repair and slip-resistant.
Apr 28, 2020 6 demerits · 1 violation
#22 · Premises: emergency telephone provided −6
.2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Observed no location for emergency phone listed on pool rule sign. CDI operator placed location of emergency phone on rule sign.
May 7, 2019 2 demerits · 1 violation
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder in 5' end of pool was loose. CDI
May 1, 2018 10 demerits · 3 violations
Inspector comments: Observed fill spout removed at ladder area. Operator re-installed spout to prevent possible trip hazard.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope at 55 feet on ring buoy. CDI, ring buoy throw rope length corrected on-site.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(3) Provide continuous forced ventilation or cross ventilation in pump room.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Observed backflow prevention device not located on hose bib in restroom and on deck
May 16, 2017 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One area did not have 6 feet clearance. CORRECTED. Table moved to provide clearance.
#27 · Equipment room: filter backwash discharged through an air gap −2
Pipes in pipe room did not have flow directions.
Jun 20, 2016 16 demerits · 4 violations
#3 · Water quality: pool water pH −6
Initial pH of 7.0 pH raised to 7.2 during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Both throw ropes were in a tangled mess - corrected by me during inspection.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
label the pipes in the pump room.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Install back-flow preventer on the hose bibb.
Jun 23, 2015 44 demerits · 11 violations
Inspector comments: Intent to Suspends issued for #9, #12 and #17.
#3 · Water quality: pool water pH −6
Pool pH at 7.0. Corrected to 7.2 during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some algea on pool steps and around equalizer line covers. Keep clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir missing from skimmer. Replace weir.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
28 to 30 ft between wall depth markers at steps on either side. Install depth markers every 25 ft or less on pool walls. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Two end caps missing from ladders. Ladder >6 " from pool wall. Maintain end caps and provide ladder between 3" and 6" from handrail to wall.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
More than half of returns missing fittings. Replace where needed. Intent to Suspend issued.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Pool greater than 3000 sq ft. One ring buoy without rope. Corrected during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Minor damage to plastic decking at 4 ft. Keep in good repair. Eliminate hazard. Intent to Suspend issued.Fill spout on deck left open. Provide plug to eliminate hazard. Intent to Suspend issued.
#22 · Premises: emergency telephone provided −6
No dialing instructions at emergency phone. Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Light and fan not operable in chemical storage room. Provide.
#27 · Equipment room: filter backwash discharged through an air gap −2
Drain in backwash pit not cut flush so standing water. Cut pipe flush to bottom of pit.
Jun 4, 2014 10 demerits · 3 violations
Inspector comments: Permit not posted as per requirement. Permit may be accessed at meckpools.charmeck.org.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Loose ladder at 5 Ft end of pool. Tighten ladder.
#22 · Premises: emergency telephone provided −6
Emergency phone not operational. Operator, Brian Yarmon and HOA president contacted by guard on duty. Both arrived and phone was repaired.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
No directional lines on pump in equipment room. Label pump lines.
Jul 19, 2013 18 demerits · 6 violations
Inspector comments: Pool lights not checked due to daylight. Observed no backflow prevention device on main water supply line in the pump room. Device could be in the wall.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed most of the weirs missing from the skimmers. Intent to suspend issued for this item.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed depth markers at the main entrances to the pool warn and barely visible. Intent to suspend issued for this item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed hand rails loose.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed no flow meter at main pool outlet pipe.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Observed pipes to main pool not identified in pump room.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Observed no backflow prevention device on the hose bibbs by the shower and in the bathrooms.
Permits at this address
Other permits for this place
Same name, separate permit (for example a pool, kitchen or lunchroom). Each is scored on its own.
- 0demeritsSteelecroft Swim ClubSeasonal Wading Pool · Jul 2013 – May 2026 · 15 inspections
Matched by street address. Each permit has its own grade and history.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “STEELECROFT SWIM CLUB” or State ID 2060500898). Inspection type (routine vs. follow-up) is not published in the county's data.