10demerits
ALTA GROVE
3212 FLORAL GROVE LN, Charlotte, NC 28216
Seasonal Swimming Pool · NC permit/State ID 2060500930
Latest result10 demerits
Last inspectedApr 24, 2026
Inspections on record13
On record sinceMay 13, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 13, 2014Lower is betterApr 24, 2026
Inspections & violations
Apr 24, 2026 10 demerits · 4 violations
Inspector comments: Emergency phone works. Address posted on sign is correct location of swimming pool. 911 services said the location they had listed did not match. Operator would not tell me address that was coming up.
No night swimming permitted
Pool open dawn to dusk only.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder in 5’ area missing bumper. CPO corrected during inspection by replacing bumper
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One gate sagging. High side was 48’ but low side was below. CPO corrected during inspection. Informed CPO to monitor gate to ensure it does not droop again. Gate must remain at 48’ high with no more than 2’ gape at bottom
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Valve handles on skimmer and main drain broken. Needs to be fixed. CPO is using wrench to open and close valves.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for back wash
May 19, 2025 8 demerits · 2 violations
Inspector comments: Address on file at 911 does not match what is on sign. Sign has correct physical address. Phone is not an automatic/system dialer. Informed manager and CPO to correct address with 911/phone company
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Vacuum line cover missing at start of inspection. CPO replaced vacuum cover with approved self closing self latching cover that needs tool to be opened
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for back wash
May 15, 2024 14 demerits · 5 violations
Inspector comments: Equalizers and drain covers expire in 2025 must be replaced prior to next season.
Contact Chris Sell or Katie Rudisill for assistance and PDSC form approval.
980-314-1620
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pool floor has stains from leaf litter however no debris was in the pool. .
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One pool ladder missing bumper caps.
.2521 Install ladders per manufacturer instructions.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Pool chairs encroach on 6’ of clear walking spaces Ensure chairs are set up to allow for 6’ of clear walking space around pool
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Bags of sodium bicarbonate sitting on pump room floor. Ensure chemicals are stored properly
Some standing water around pump in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap no air gap for back wash
Jun 15, 2023 8 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope too long. Corrected during inspection
#27 · Equipment room: filter backwash discharged through an air gap −2
no air gap for back wash
Apr 5, 2022 10 demerits · 4 violations
Inspector comments: No night swimming. Pool closes at dusk per CPO.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions.
Observed end caps missing on ladder.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
Observed deck chairs < 6ft from pool edge. CDI
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Observed pool chemicals stored on the floor.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors.
Restroom mirrors are not shatterproof.
Apr 21, 2021 12 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope was 1.5' to short. Corrected during inspection.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Equalizer lines in some skimmers were covered. Keep equalizer lines open. Corrected during inspection.
May 13, 2020 10 demerits · 2 violations
Inspector comments: .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed two areas of deck one at ladder and one near 4.5ft depth that are right at .5”. These areas need to be monitored and repaired by next season. See attached photos.
Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.
Night swimming NOT permitted.
Contrasting color bands were verified today and are in compliance.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy in severe disrepair. CDI: new ring buoy provided.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow mete stuck. CDI: Flow meter fixed.
May 2, 2019 2 demerits · 1 violation
Inspector comments: 17: Observed slight cracking of the pool deck surface in various areas, cracks less than 1/4th of an inch wide.
Signed by Alejandro Aleman
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Observed no continuous ventilation source present in the chemical/pump rooms.
May 3, 2018 2 demerits · 1 violation
Inspector comments: .2521 - Tiled contrast color bands on steps and benches measured 1+1/4 inches to start of bullnose. Use of contrasting color tiles installed in the stair tread is acceptable provided the tiles are spaced no more than one inch from the edge of the tread. When season ends and water is lowered for other repairs around perimeter of pool, recommend adding paint to extend contrasting band from tile edge to at least the beginning of bullnose on step edges. Contrasting color band should measure at least 2 inches wide visible from above the stairs.
No night swimming permitted.
Local permit (yellow sticker) number 0978.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533, .2534 - Equipment (pump) room and chemical storage room require natural cross draft or continuous forced ventilation. Equipment room had one natural vent, chemical storage room had one natural vent and one fan which turned off when lights were turned off.
Apr 28, 2017 8 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Clean upper section of pool wall.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Ventilation shall be continous in chemical room and separate from lighting. Provide continous ventilation in chemical room seperate from light switch or provide a cross ventilation in chemical room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Provide soap in men bathroom.
Apr 28, 2016 10 demerits · 4 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
TILES MISSING AT SKIMMER AREAS
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
ONE ANTI-SLIP TREAD MISSING
#27 · Equipment room: filter backwash discharged through an air gap −2
NO AIR GAP INSTALLED ON BACKWASH LINE
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
NO BACKFLOW PREVENTERS ON HOSE BIBS IN RESTROOMS
May 6, 2015 18 demerits · 5 violations
Inspector comments: Pool does not have an approved PDSC form on file. Permit will not be issued until form is completed and approved by the Health Department. Forms can be found at Meckpools.charmeck.org. When permit is issued print a copy from our website to post in pool area.
#3 · Water quality: pool water pH −6
pH 7.0. Maintain between 7.2 and 7.8. Corrected to 7.4.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
All equalizer lines blocked by plastic tabs. Tabs removed by operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Pool does not have spare pump basket. Provide spare basket.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Dry chemicals stored on the ground. Store off of the ground or in buckets. Corrected by operator.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Provide soap in women's restroom and toilet paper in men's restroom.
May 13, 2014 20 demerits · 8 violations
Inspector comments: 13 - Note: Contrasting color band on steps 1 1/2" to edge. When replastered, assure 1" to edge of steps. Permit will be posted online within 3 days.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed main drain check not recorded daily. Record daily.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder end cap missing. Provide.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Lighting in pool not operating. Repair lights or no night swimming.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed fans tied to lighting. Provide continuous ventilation in chemical storage.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Observed labeling on recirc pipes faded. Relabel pipes.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap on backwash line to pit. Provide air gap. Cut drain pipe flush to floor to eliminate holding water.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed no paper towels in women's. Provide paper towels.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Observed no backflow prevention device on hose bibs - restrooms and showers.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “ALTA GROVE” or State ID 2060500930). Inspection type (routine vs. follow-up) is not published in the county's data.