18demerits
WALNUT CREEK - PHASE I
6745 MALLARD PARK DR, Charlotte, NC 28262
Seasonal Swimming Pool · NC permit/State ID 2060500983
Latest result18 demerits
Last inspectedMay 18, 2026
Inspections on record13
On record sinceJul 3, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jul 3, 2014Lower is betterMay 18, 2026
Inspections & violations
May 18, 2026 18 demerits · 4 violations
Inspector comments: Restriction: Flow meter must remain operable. Flow shall be set at 78 gpm to 106 gpm to meet turnover and flow restriction of filter. Flow greater than 138 gpm exceeeds main drains. Suction Hazard.
Construction: 7/1/2002
Rope: 32’
NIGHT SWIMMING NOT APPROVED.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
GPM above required 80GPM setting. CPO corrected to 80GPM setting per approved PDSC.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions.
Ladders without end caps.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy rope extending past approved length. CPO cut and knotted rope to proper length.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
Fence with clearance greater than 4” in areas around fence and near gate. CPO to move rocks to close gap under area.
May 16, 2025 10 demerits · 2 violations
Inspector comments: Permit restrictions
- no night swimming
Flow meter must remain operable. Flow shall be set at 78gpm to 106 to meet turn over and flow restriction of filter.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck deterioration
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed 911 has a different address from the one on site. CDI. PIC wrote the same address 911 has. Facility is advised to ensure the calls to 911 are routed to the right address.
911 has 6700 mallard park dr and facility had 6745 mallard park dr
May 30, 2024 6 demerits · 1 violation
Inspector comments: Permit restrictions verified on site.
: Flow meter must remain operable. Flow shall be set at 78 gpm to 106 gpm to meet turnover and flow restriction of filter. Blue white flow meter installed.
2. New pump – Pentair Intelliflo3, 011077 3 hp
3. Main drain and skimmer – 3” pipe; 2.5” return line
4. (2) Aquastar VGBA-2017 A10RCFRxxx drain covers
5. 3 skimmers with EQ lines plugged
6. (1) Pentair TR140 filter – double check the model listed on the filter placard. This is a permit restriction.
7. 7 returns, either on wall or floor
No night swimming permit.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
operator corrected the rope length
May 23, 2023 8 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed greater than 4” under some parts of the fence.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck deterioration
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
Apr 27, 2022 18 demerits · 5 violations
Inspector comments: Mike Henson present during inspection.
Confirmed emergency phone with 911 operator and phone rang when posted # called.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Debris in pool.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. 2 out of 3 weirs missing. CPO replaced one weir.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. End caps missing on ladders.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Buoy rope exceeds required 32’. Rope adjusted to 32’ while on site.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. standing water on floor of pump room.
Apr 15, 2021 16 demerits · 4 violations
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed ph below 7.0 ppm. soda ash added and pH raised to 7.5 ppm.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed leaf debris on floor and surface.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck deterioration and raised joint expansion strip over 15 ft from pool edge.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed no cross ventilation.
.2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft. Observed standing water in chemical room.
Apr 21, 2020 4 demerits · 1 violation
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - Observed debris in pool
Jul 2, 2019 10 demerits · 2 violations
Inspector comments: David Johnson present during inspection.
Night swimming not permitted at this time.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope measured 34 feet rather than required 32 feet. Rope shortened by CPO to 32 feet during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Pool built in 2002. Two areas of fence had more than 4" beneath bottom post. CPO added decorative cement landscaping blocks to existing decorative block walls outside fences to ensure distance was less than 4 in all areas.
Apr 10, 2018 12 demerits · 3 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
No ring buoy present upon arrival for inspection. Corrected during the inspection. Ring buoy was provided. 15A NCAC 18A .2530
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
7 inch spacing under fence near the 5 feet end of pool. Corrected during the inspection. Stones added to decrease spacing under fence. 15A NCAC 18A .2528
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Baseboards missing in men's restroom. Wall damage in women's restroom. Needs to be repaired. 15A NCAC 18A .2528
Jul 6, 2017 16 demerits · 5 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC form lists Pentair Challenger CHII-NI-2F 2 HP, observed pump plackard on pump listed as Pentair Challenger CHII-NI-1/2F 1/2 HP. Need to complete a plan review application if pump has been changed or otherwise provide proof of installed pump. Sent application to PO by email. Have this completed in 3 days or pool permit will be suspended.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fencing with foot holds 27" from ground with 6" gaps at fence from pool house. Maintain no more than 4" gaps in pool fence. Observed one area at bottom of pool fence with bottom clearance of 6". Maintain no more than 4" gap from bottom of fence.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room ceiling exhaust vent does not appear to be operating, and there is only one source of natural ventilation. Have exhaust fan repaired/ replaced or provide natural cross ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water observed above 110 in restrooms, needs to be 110 max. Mirrors not shatter proof in restrooms. Baseboard trim falling off wall needs refastening in men's restroom.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device observed on a few hose bibs connected to pool house.
Jun 22, 2016 4 demerits · 1 violation
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed pool deck chipping, flaking surface near entrance. Surface in need of repair. ITS Issued. Pool surface in need of repair in 30 days.
Apr 16, 2015 6 demerits · 1 violation
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2537, 2530 Provide throw buoy with correct rope length; Observed throw rope measuring 50 ft, required length 32 ft, CDI rope cut to 32 ft.
Jul 3, 2014 8 demerits · 3 violations
Inspector comments: 15. Flip direction of bolts to prevent injury
22. Additional signage, visible from pool deck, for emergency phone location. Fire extinguisher sign?
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Pool lights not working - replace bulbs
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Forced ventilation fan not working
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Toilet in women's restroom not working, mirror is loose from wall, mirrors to be of shatterproof construction
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “WALNUT CREEK - PHASE I” or State ID 2060500983). Inspection type (routine vs. follow-up) is not published in the county's data.