14demerits

PROSPERITY RIDGE

6225 PROSPERITY COMMONS DR, Charlotte, NC 28269
Seasonal Swimming Pool · NC permit/State ID 2060501045
Latest result14 demerits
Last inspectedApr 13, 2026
Inspections on record14
On record sinceApr 4, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0918 Apr 4, 2014: 8Apr 15, 2015: 12Apr 21, 2016: 6May 18, 2017: 10Apr 10, 2018: 6Apr 8, 2019: 6Apr 27, 2020: 0Apr 22, 2021: 6Apr 27, 2022: 6Jun 22, 2023: 18May 23, 2024: 10Apr 14, 2025: 4May 21, 2025: 0Apr 13, 2026: 14
Apr 4, 2014Lower is betterApr 13, 2026

Inspections & violations

Apr 13, 2026 14 demerits · 3 violations
Inspector comments: No Night Swimming Gate to gazebo has been disabled by use of 2 sets of locks. Gate not in use for several years per PIC.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers with debris present. Clean as needed.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed USCG approved ring buoy in bad repair. CDI - Ring buoy replaced by PIC.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate to gazebo locked with 2 sets of locks. Gate originally went to Gazebo that has since burned down. PIC stated gate remains locked and is not in use. Gate disabled by use of several locks.

View this inspection on the county portal ›

May 21, 2025 0 demerits · 0 violations
Inspector comments: Not approved for night swimming No violations observed today

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 14, 2025 4 demerits · 1 violation
Inspector comments: Permit denied today
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed that ground level windows slide open more than 4 inches on to the pool deck. CDI PO put nails in window so they do not slide open at all. 2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Observed the Access gate at gazebo does not self close or self-latch. The gate is off the hinges.

View this inspection on the county portal ›

May 23, 2024 10 demerits · 3 violations
Inspector comments: NO NIGHT SWIMMING. Field verified: New Pump Hayward HCP30503, 5 hp pump Main drain, skimmer and return line coming out of floor all 4” pipe (2) VGB 2008 Aquastar WAV12WRxxx drain covers EQ lines plugged in skimmer (2) Pentair TR100C filters 10 wall or floor returns 5 skimmers Electrical Permit #E4619704
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. CDI-Access gate at gazebo does not self latch. CPO has disabled gate (TD). CPO/PERMIT HOLDER must ensure this meets building and fire code requirements.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed deck chairs < 6’ from pool edge. CDI
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Restroom mirrors are not shatterproof.

View this inspection on the county portal ›

Jun 22, 2023 18 demerits · 4 violations
Inspector comments: Inspection conducted with Patrick, “Cool Hand” and Ben. Pool has been re-plastered and equalizer lines have been disabled. PDSC showing updated suction compliance provided during inspection. Copy attached to this inspection report. Permit will be issued and available for printing from the website health.mecknc.gov/envhealth/pools. Sticker provided during inspeciton. Night swimming not approved. Pool signage updated to reflect pool closes at dusk. EHS unable to determine if mirrors in restrooms are shatterproof. Ensure no glass in restrooms or on pool deck.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Pool has been re-plastered and equalizer covers have been removed and lines have been disabled. EHS verified equalizers have been plastered over on pool wall and plugged inside of the skimmers. PDSC documentation has not been provided showing updated pool drain suction compliance. Operator completed and submitted updated PDSC form during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy with no rope attached. Operator attached 50’ rope as required.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Gate near clubhouse not self latching. Gate near gazebo does not always self close and latch. Both corrected by operator during inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. Fixtures in both restrooms with no water at this time. Plumber on site repairing due to complete work today. Ensure hot water temperature remains at 110f or less once water is restored.

View this inspection on the county portal ›

Apr 27, 2022 6 demerits · 1 violation
Inspector comments: Mike Henson present for inspection. Confirmed teal dot on covers. Night swimming not permitted.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Adjusted buoy rope to 50’ as required.

View this inspection on the county portal ›

Apr 22, 2021 6 demerits · 2 violations
Inspector comments: Night swimming NOT permitted. Report to 'David Johnson' No signature due to COVID-19.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed cover plate at bottom of handrails in shallow end of pool loose/raised. EHs recommended securing to ground to prevent trip/cut hazard.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter stuck. CDI: CPO corrected.

View this inspection on the county portal ›

Apr 27, 2020 0 demerits · 0 violations
Inspector comments: No violations during this inspection

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 8, 2019 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Horizontals shall not be located less than 45" in height. Observed area of fence near disabled gate with handrails less than 45" from fence that can be used as foot holds. - Pre- 2010 permit - Non permit item.o
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(m) Observed no water available to restrooms. Water needs to be restored. GENERAL COMMENT: Two gates were fixed to be permanantly closed. Violation corrected. Permit issued.

View this inspection on the county portal ›

Apr 10, 2018 6 demerits · 2 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
No diving sign posted near ladder around the 4 ft portion of pool was damaged. Corrected during the inspection. Replaced by international symbol. .2523
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water stained ceiling in both male and female restrooms. Needs to be repaired/repainted. .2526

View this inspection on the county portal ›

May 18, 2017 10 demerits · 2 violations
Inspector comments: Permit has not been issued. The information on the PDSC sheet was incorrect. The following is what they have installed: -The 2 pumps that are installed are Starite MPEAG6L (2 HP) and a Pentair Whisperflo WFE 208 (2 HP) -4 aquastar 4hp’s and 1 waterway 640-801 or 640-803 - 2 aquastar WAV9WR installed for main drains An in field-plan review needs to be sent to Katie Wilson. Permit will not be issued until the form is approved.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed the rope at 55ft. Corrected during inspection to 50ft.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed chairs 4ft away from the pool edge. Corrected during inspection to 6ft.

View this inspection on the county portal ›

Apr 21, 2016 6 demerits · 1 violation
Inspector comments: Model number on pump and PDSC did not match. New PDSC sheet was filled and will be brought to the office.Observed "no diving" letters on the deck fading. Pool has tile markers as well.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope on buoy was 63ft. Corrected onsite to 50ft.

View this inspection on the county portal ›

Apr 15, 2015 12 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed baskets collecting debris. Corrected during inspection - baskets emptied.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed chairs closer than 6ft to pool deck. Corrected during inspection - chairs moved to other side of pool with 6ft clearance.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Corrected on site - flow meter changed out.

View this inspection on the county portal ›

Apr 4, 2014 8 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed debris in the skimmer baskets.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Maintain chemicals in a dry enclosure. Observed the ceiling leaking inside the door where chemicals are stored. Chemicals were moved temporarily.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Clean the tiolets and replace the blown out light in the restroom.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “PROSPERITY RIDGE” or State ID 2060501045). Inspection type (routine vs. follow-up) is not published in the county's data.