4demerits
BEREWICK MANOR HOUSE
6615 BEREWICK COMMONS PKY, Charlotte, NC 28278
Seasonal Swimming Pool · NC permit/State ID 2060501097
Latest result4 demerits
Last inspectedApr 30, 2026
Inspections on record14
On record sinceMay 8, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 8, 2014Lower is betterApr 30, 2026
Inspections & violations
Apr 30, 2026 4 demerits · 1 violation
Inspector comments: Permit Restriction: Flow meter must remain operable. Flow shall not exceed 500 pm due to drain cover flow restriction. Suction Hazard.
NIGHT SWIMMING IS NOT PERMITTED
EHS observed that PDSC form states that motor is 3 HP. During in field verification, EHS observed that the pump is a 7.5HP motor. Facility shall update and resubmit new PDSC form within 2 weeks. If facility fails to submit the new PDSC form with updated information permit action may be taken.
Main drain covers expire: 4/28/2029
Equalizer covers expire: 4/28/2029
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. EHS observed debris in the skimmer basket. CPO emptied out skimmer baskets.
-4-
Apr 16, 2025 4 demerits · 1 violation
Inspector comments: Night swimming not permitted.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris in pool and on pool floor.
May 2, 2024 2 demerits · 1 violation
Inspector comments: Per permit restrictions Flow meter must remain operable with flow not to exceed 500gpm. Observed the flow at 250gpm verified during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed pump room covered in water due to recent maintenance.
Apr 17, 2023 4 demerits · 1 violation
Inspector comments: Night swimming is prohibited at this time. Pool will be closing at 8pm. Night swimming visit will need to be conducted before night swimming could be approved. Plans to open for swim meets.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed leaves and other floating debris in the pool. CDI: pool being cleaned during inspection.
Apr 5, 2023 14 demerits · 3 violations
Inspector comments: Permit denial issued for violation 22 - 911 operator was not able to provide address for location of pool therefore would not be able to route services to pool in case of an emergency. Pool placed on Q status. Operator must call front office at 980-314-1620 and request a reinspection and $100 fee must be paid before EHS can make a visit to issue permit.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris and other debris inside the pool. CDI: being cleaned during inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 2 out of 11 weirs missing. CDI: weirs replaced during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. Observed 911 operator was not able to provide address for location of pool therefore would not be able to route services to pool in case of an emergency. Permit denial issued.
Apr 19, 2022 0 demerits · 0 violations
Inspector comments: No violations noted at this time.
No violations were recorded for this inspection.
Apr 15, 2021 2 demerits · 1 violation
Inspector comments: Covid 19 restrictions, no signature. Mike present during inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed mirror not shatterproof in restrooms.
Apr 21, 2020 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Observed mirrors in both mens and womens restrooms not shatterproof
Apr 16, 2019 0 demerits · 0 violations
Inspector comments: No violations during inspection.
No violations were recorded for this inspection.
Apr 18, 2018 6 demerits · 2 violations
Inspector comments: POOL IS NOT PERMITTED FOR NIGHT SWIMMING.
NO LIFEGUARD REQUIRED.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Horizontals in fence measured less than 45 inches but greater than 30 (38 inches). Pool and Fence constructed prior to 2010
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Flow directors on pipes were fading. CDI- Re-drawn.
May 4, 2017 10 demerits · 2 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
No 6 foot clerance in some parts of decks. CORRECTED- Chairs moved to provide 6 foot clearance.
#22 · Premises: emergency telephone provided −6
Telephone numver that 9-1-1 provided did not match telophone number posted. CORRECTED. Telophone number was corrected to reflect accurate number
Apr 27, 2016 8 demerits · 4 violations
Inspector comments: POOL PERMIT CAN BE ISSUED.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Forced air ventilation in the equipment room & the chemical room are not working. ** Correct.
Light bulbs burnt out or fixtures inoperable in equipment room. ** Resolve.
#27 · Equipment room: filter backwash discharged through an air gap −2
Backwash pipe turns down into sump. ** Provide complete air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One shower inoperable. No shower head. ** Rectify.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention on hose bib in equipment room
** Install vacuum breaker.
May 6, 2015 36 demerits · 11 violations
Inspector comments: Note: Address has been changed at pool and 911 to 6615 Berewick Commons Pky. Lettering on front of building still at 6625. Change numbering of buildnig to correct address. Pool has passed pre-permit nispection. A permit will not be issued until accurate PDSC form is submitted. Currently information provided is not correct of what is at the pool. EQ750 pump11 4HPxxx equalizers2 main drains
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No log book provided. Provide log book.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One damaged skimmer basket. Replaced during inspection.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some inlets missing fittings. Replace fitting.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fence with 38" between horizontals. Maintain at 45" or greater. •
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool furniture at deep end of pool 7 ft from pool edge. Provide 8 ft clearance.
#18 · Premises: lifeguards present or warning signs posted −4
SC Pool Rules sign posted with incorrect letter height. Corrected during inspection.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Some pool lights with water. Keep operational. No night swimming at pool. Pool hours from 10:00 to 8:00.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Light burnt out in pump room. Provide adequate lighting.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Provide air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in restrooms. Provide soap.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Hose bibs on pool deck, in pump room and in women's restroom with no backflow prevention. Provide backflow prevention device on all hose bibs.
May 8, 2014 16 demerits · 4 violations
Inspector comments: 33. No backflow device on exterior hose bib at main pool deck. Provide back flow device.
#3 · Water quality: pool water pH −6
Chemicals checked today and ph at 8.0. Operator; Zack Watkins; corrected. Chemicals checked again and pH at 7.5.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Floating debris and other debris on the steps/ pool floor at far right corner of the pool. Maintain clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Ten of eleven weir baskets full of debris. Six of eleven weirs missing. CDI- Operator corrected all.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some water on floor of pump room. Slight drip of side access line needs to be repaired.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “BEREWICK MANOR HOUSE” or State ID 2060501097). Inspection type (routine vs. follow-up) is not published in the county's data.