8demerits
RISE SUNRIDGE
2109 ARROWCREEK DR, Charlotte, NC 28273
Seasonal Swimming Pool · NC permit/State ID 2060501119
Latest result8 demerits
Last inspectedMay 29, 2026
Inspections on record13
On record sinceJun 26, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 26, 2013Lower is betterMay 29, 2026
Inspections & violations
May 29, 2026 8 demerits · 2 violations
Inspector comments: Re-inspection conducted with CPO, Junior Sampson. All 6 and 4 demerit violations from previous inspection have been corrected. Permit issued.
Field verification conducted, interlock tested and operable.
Not approved for night swimming.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH at 7.0.
Corrected- CPO adds acid and pH increases to 7.2
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
.2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose.
Observed no hose bib within 50 ft of restrooms.
May 22, 2026 24 demerits · 5 violations
Inspector comments: Inspection conducted with CPO, Junior Sampson. Permit denied due to pH at 6.6.
Compliant signage warning “children should not use swimming pool without adult supervision” and “adults should not swim alone” (1 inch lettering minimum) must be provided within 30 days.
Field verification conducted, interlock tested and operable.
Not approved for night swimming.
Please contact the main office at (980) 314-1620 to pay $100 fee prior to scheduling re-inspection.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm.
Observed chlorine at <0.5ppm
Corrected- Chlorine increased to 1ppm during inspection with autochlorination system.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH at 6.6
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
Observed no signage with proper wording for this item. Provide within 30 days.
.2530(c) Provide "Adults should not swim alone." in 1" lettering.
Observed no signage with proper wording for this item. Provide within 30 days.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Observed incorrect phone number at emergency phone signage- number listed calls leasing office, which may not be open at all times there are swimmers. Phone number of call box itself must be provided.
Corrected- EHS confirms correct phone number for Kings 3 box and CPO creates sign at emergency phone.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
.2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose.
Observed no hose bib within 50 ft of restrooms.
Jun 9, 2025 16 demerits · 4 violations
Inspector comments: Main drains more than 36” apart. SVRS is not required. Small leak at SVRS. Fix or remove.
Permit Restriction: Flow meter must remain operable. Flow shall not exceed 119 gpm due to drain cover flow restriction. Suction
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed missing inlet.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate not self-closing/self-latching. -CDI- CPO repaired.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed incorrect address posted on pool signage. -CDI- CPO printed correct address.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed water on pump room floor due to leak at SVRS.
Jul 19, 2024 12 demerits · 3 violations
Inspector comments: Night swimming not permitted.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(a) Provide depth markers on pool walls and pool deck at both ends of the pool. Observed depth mark not provided at shallow end of pool and not legible. CDI, depth marker stenciled and provided during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope measuring 46 ft. CDI, throw rope adjusted to proper length of 33 feet.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Post a shower sign visible upon entrance to the pool. Observed no shower sign posted.
May 12, 2023 20 demerits · 5 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539 - Observed one equalizer line in skimmer below basket plugged. CPO indicated that this was done during repairs. Other equalizers are unblocked and operable. CPO removed plug during inspection. - Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
1 of 3 weirs missing. CPO replaced during inspection - Corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy throw rope observed at 46ft. CPO cut down rope to 33ft - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Observed no forced or cross ventilation in pump room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Observed mirrors not shatterproof.
Jul 28, 2022 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Observed mirrors not shatterproof.
May 31, 2019 6 demerits · 1 violation
Inspector comments: NIGHT SWIMMING NOT PERMITTED.
#3 · Water quality: pool water pH −6
PH RECORDED AT 7.1. CORRECTED- SODA ASH ADDED, INCREASED TO 7.3.
Jun 11, 2018 12 demerits · 3 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no section on the record books to check the main drains daily. Informed the pool operator to add a section in the record books to check the main drain. CDI- Page made and printed.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed the rope greater than 33 feet. CDI- Cut to 33 feet.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Observed the pipes in the pump room not labeled. Label.
Permit Issued 18-600619
Jun 13, 2017 12 demerits · 4 violations
Inspector comments: Permit not posted at pool today. Operator Tracy Surgeon advised that he will check with property manager to access. Check meckpools.charmeck.org for permit.
General comment:
#5- Operator advised that they have been open for 2 days and have been checking the chemicals. Operator provided forms for this season's use. Will follow up with to ensure ongoing records due to short history of documentation.
#8- One of three weirs missing. Replace weir.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door leading from club house hallway for access to restrooms and other activity rooms not self closing and self latching. Bolt lock is in place to lock door per maintenance personnel after pool closes for the day. Operator locked bolt as temporary measure until repair of door is completed to ensure that door meets rule. Intent to suspend issued today for repair of door.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operational. Repair flow meter.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Directional lines not present on filter system piping. Replace directional lines.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower is not operational. Repair shower.
Jul 11, 2016 34 demerits · 9 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no main drain check on the daily records.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
-Observed 1 weir stuck.
-Observed 1 weir missing. CDI- Replaced.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed cover to an inlet (eyelet) missing. Provide.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed the buoy rope at 31 feet. CDI- 33 feet now.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
-Observed the self closer device on the clubhouse/restroom door in disrepair. (Most times the door closes, a few times it did not). Repair.
#18 · Premises: lifeguards present or warning signs posted −4
Observed the sign directing people to shower before entering the pool peeling and hard to read. CDI- Printed out a bold sign and put it on the gate. *PROVIDE/PURCHASE A SIGN ASAP!
A sign was purchased as the inspector was leaving.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed the flow meter stuck. CDI-Repaired
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed the pump room floor wet. Repair leak.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed the shower inoperable. Repair.
Jul 10, 2015 44 demerits · 10 violations
Inspector comments: #29 Shower inoperable. ** Correct.
GC #30 Water added to pool directly into circulation system & no apparent backflow prevention device seen.
** See .2512(b).
Note: temporary staff person taking care of pool.
** This must be done by the CPO on a daily basis. See .2537(c).
IMMEDIATE SUSPENSION issued for #2, #3 & #15.
#2 · Water quality: disinfectant residual provided by −6
Cl @ 0ppm. ** Maintain at least 1ppm.
Chlorine tablets in skimmer baskets & chlorinator empty. ** Automatic chlorinator must be used & properly operating. Never put Cl tables in baskets.
(Immediate Suspension/ IS)
#3 · Water quality: pool water pH −6
pH @ 7.0. ** Maintain 7.2 to 7.8. (IS)
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Pool records show chlorine levels @ .02 (?), .03 (?), .04 (?) & .5. ** Maintain Cl level at a minimum of 1ppm.
No main drain checks, no total alkalinity or cyanuric acid readings. ** Check main drains (& equalizer line covers) & record daily. Check & record total alkalinity & cyanuric acid levels at least 1 time per week.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Scum on pool wall tiles. ** Clean.
Some leaf debris on pool floor. ** Remove.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
No apparent pull from 1 skimmer. ** Resolve.
1 weir stuck. ** Resolve.
1 skimmer basket in disrepair. ** Replace.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope part of ring buoy dry rotted. No throw rope present. ** New ring buoy & throw rope obatined while on-site. Rope needs to be secured to the ring buoy & shortened to proper length. (IS)
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Self-closure device on door leading from club house/ restroom area is in disrepair; door also damaged - door cannot self-close & self-latch. ** Rectify.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool furniture as close as 3' from pool edge.
** Maintain 6'.
Coping chipped, deck cracks & concrete chipped where tile was. ** Correct.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Leak @ pool pump. ** Resolve.
Flow meter float stuck. ** Keep operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No natural cross draft or forced air ventilation in equipment/ chemical room. ** Provide.
Jun 10, 2014 20 demerits · 5 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed on Daily Pool Check paperwork that the main drain covers are not being checked everyday. / INTENT TO SUSPEND ISSUED IN ORDER TO ENSURE FACILITY COMPLETES DAILY CHECKS OF MAIN DRAIN COVERS AND DOCUMENTS ACCORDINGLY
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Main drain cover not attached when I checked it with body hook. / COVER WAS ATTACHED DURING INSPECTION
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed 3 pool deck chairs placed too close (within 6ft) of pool edge. / CHAIRS RELOCATED TO CREATE AT LEAST 6FT OF CLEARANCE AROUND POOL EDGE
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed bobber not working in flowmeter. / ENSURE BOBBER WORKS IN FLOWMETER
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed wet floor in equipment area. / REPAIR LEAK THATS CAUSING THE WET FLOOR
Jun 26, 2013 16 demerits · 5 violations
Inspector comments: Pool lights not checked due to daylight. - Pipes from the pool labeled with flow incorreclty. Fix arrow direction.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
2 out of 3 wiers are missing. The third on is stuck and not operational. Observedbaskets full of debirs. Intent to suspend issued for this item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Allow for 6 feet of clear wlak way around the deck. Some areasof the deck are nto suitable for chairs. This is a Repeat Violation.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter not working. This is a repeat violation.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Backflow preventer required on hose bibb. This is a repeat violation.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Pipes from the pool labeled with flow incorreclty. Fix arrow direction.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “RISE SUNRIDGE” or State ID 2060501119). Inspection type (routine vs. follow-up) is not published in the county's data.