PROSPERITY PLACE

12725 LIVENGOOD LN, Charlotte, NC 28269
Seasonal Swimming Pool · NC permit/State ID 2060501124
Latest result14 demerits
Last inspectedJul 17, 2026
Inspections on record16
On record sinceApr 4, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01632 Apr 4, 2014: 8May 8, 2014: 10Apr 22, 2015: 10Apr 21, 2016: 6May 2, 2017: 12Apr 13, 2018: 8Apr 25, 2019: 6May 19, 2020: 16May 11, 2021: 8Apr 29, 2022: 4Apr 26, 2023: 4May 2, 2024: 10Jul 18, 2025: 26Aug 28, 2025: 0Aug 28, 2025: 32Jul 17, 2026: 14
Apr 4, 2014Lower is betterJul 17, 2026

Inspections & violations

Jul 17, 2026 14 demerits · 3 violations
Inspector comments: The following IFPR items have been verified during today's inspection: 1. Pump = Pentair Intelliflo3 VSF 011075 2. Blue-White flow meter must remain operable at 104-141 GPM to meet turnover and restriction of the filter 3. 4" Main Drain piping 4. 4" Skimmer piping 5. 3" Return piping 6. (2) Aquastar 1216xxx main drains 7. (4) Aquastar 6HPHAxxx equalizer line covers 8. (4) skimmers 9. (10) returns Inspection was conducted with CPO Daniel. NO NIGHT SWIMMING.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris buildup on pool walls. CPO stated they are scheduled to clean pool walls this week.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed two out of the four weirs missing. Replace missing weirs.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed signage posted with "pool phone number" and "physical address of pool" missing required information. CPO corrected during inspection and EHS was able to verify phone number and address on file with local 911.

View this inspection on the county portal ›

Aug 28, 2025 32 demerits · 10 violations
Inspector comments: Inspection conducted with CPO Daniel Robertson. Operator refused to sign for inspection. Observed most items from previous inspection corrected. Facility passed electrical inspection and in-field plan review for new pump. New PDSC form approved. Observed deck and coping damaged. Maintain coping in good condition, maintain deck with no gaps or offsets > 1/2 inch. Outer rope on ring buoy and throw rope starting to fray, before next pool season recommend replacing with new US Coast Guard approved ring buoy with attached 36 foot throw rope at least 1/4 inches in diameter. New permit condition. Flow meter must remain operable and read between 90 GPM and 141 GPM which is the limitation of the filter. Pre-permit inspection did not pass. 7) 24) Will need to call our office (980) 314-1620 to pay $100 re-inspection fee prior to rescheduling a pre-permit inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No records or log book provided. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Left copy of state log sheet for operator.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Buildup of organic matter on pool wall, floors, and pool fixtures. .2537(14) Keep pool surface and pool floor free of debris. - Pre-permit item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one of four weirs. .2518(k) Provide functional weirs.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose. .2521 Install handrails per manufacturer instructions. Both ladders loose. .2521 Install ladders per manufacturer instructions.
#22 · Premises: emergency telephone provided −6
Observed no signage with address or telephone number at emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Spare pump basket not provided for new pump .2518(e) Provide a spare basket for pump. - Pre-permit item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Bag of dry chemicals on the floor in the chemical storage room. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. - Corrected.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
New piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower not functioning. .2526(h) Shower(s) shall be provided.

View this inspection on the county portal ›

Aug 28, 2025 0 demerits · 0 violations
Inspector comments: All permit items now in compliance. Permit is issued. Status changed to “A” open for business.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Jul 18, 2025 26 demerits · 7 violations
Inspector comments: Observed pump different from PDSC form. Complete infield plan review form and submit to Christopher.Sells@mecknc.gov. Provide electrical permit number for pump change. Observed chlorine pucks in skimmers, removed during inspection. Observed the following: Pump - Pentair IntelliFlo 3 011075 Piping - 4" Main Drain, 4" Skimmer, 3" Return Returns - 10 Skimmers - 4 Filter - Pentair TR140C
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed several depth markers missing, Replace .2523(a) Provide depth markers on pool walls and pool deck next to the swimming pool.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gap in gate 1" between gate and fence within 18" of the unlatch mechanism. .2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
#22 · Premises: emergency telephone provided −6
Observed no sign with dialing instructions, address or telephone number at emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Automatic feeder does not have display functioning for controls. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed pump different from previously submitted PDSC form. WFE 12 on file IntelliFlo 3 present. .2518(h) Provide approved pump in good repair. Observed flow meter not functioning. .2518(g) Keep flow meter operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Store in chemical closet. Observed mechanical ventilation not functioning in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Urinal in mens room not functioning. .2526(a) Provide restrooms at all pools except for hotels, motels, condominiums and apartments where pool use is restricted to guests and residents.

View this inspection on the county portal ›

May 2, 2024 10 demerits · 2 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
one depth marker missing around the stairs to enter the pool, the adjacent markers were 27' apart. Operator painted the 3.5' depth marker in greater than 4" lettering. The "No diving markers" were sufficient to meet the 25'.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
buoy had a 50' rope attached at beginning of inspection, cut down to required footage during.

View this inspection on the county portal ›

Apr 26, 2023 4 demerits · 1 violation
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris on pool floor.

View this inspection on the county portal ›

Apr 29, 2022 4 demerits · 2 violations
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
natural cross or continuous forced ventilation required; fan not working; noted very strong chlorine smell
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
mirrors to be of shatterproof construction; sink in women's room loose from wall; soap required in both bathrooms

View this inspection on the county portal ›

May 11, 2021 8 demerits · 2 violations
Inspector comments: Mark Houff present during permitting and inspection. No night swimming permitted. ADDRESS ON PERMIT IS 12725 LIVENGOOD LANE. ADDRESS ON POOL HOUSE AND SIGNAGE IS 12475 LIVENGOOD LANE. 911 OPERATOR CONFIRMED ADDRESS 911 HAS IS 12475 LIVENGOOD LANE PER SR EHS KATIE RUDISELL, POOL CPO MUST CONTACT PHONE COMPANY AND HAVE ADDRESS CHANGED TO 12725 LIVENGOOD LANE, AS IT DISPLAYS IN POLARIS BECAUSE 911 USES POLARIS. 911 WILL AUTOMATICALLY THEN RECEIVE THE ADDRESS UPDATE FROM THE PHONE COMPANY. POOL SIGNAGE WILL THEN NEED TO BE CHANGED TO MATCH. CPO MUST HAVE THIS FINISHED WITHIN 30 DAYS TO AVOID PERMIT ACTION.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed leaf debris on floor of pool
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed leaf debris in skimmer baskets

View this inspection on the county portal ›

May 19, 2020 16 demerits · 4 violations
Inspector comments: 8. cracked skimmer basket replaced during inspection
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope corrected to 36'
#22 · Premises: emergency telephone provided −6
phone number corrected and posted during inspection
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
natural cross or continuous forced ventilation required
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
soap and toilet paper to be supplied

View this inspection on the county portal ›

Apr 25, 2019 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed neither the main gate or the locked secondary gate not self latching at time of inspection. Gates were repaired/adjusted by B. Vaughn, observed to be properly self latching by end of inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Observed sodium bicarbonate stored directly on the floor adjacent to the pool pump/backwash area. Item was moved to proper storage by brandon vaughn

View this inspection on the county portal ›

Apr 13, 2018 8 demerits · 2 violations
Inspector comments: NO POINTS WERE TAKEN FOR THE FOLLOWING: #16 - Observed back gate with chain and lock. Latch is 54 inches. Operator removed lock to test gate. Gate was self closing but was not latching. CDI Operator fixed gate to be self latching. Operator stated they would put their own lock on gate and that it will remain locked throughout season. .2537(b) All gates and doors shall be self-closing, self-latching. PDSC information verified. No night swimming.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
REPEAT Observed rope length to be 34 feet. CDI Operator lengthened rope to 36 feet. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump room floor with water. Operator stated they have contacted plumber to fix leak coming from backflow. .2533(d) Pump room floor shall be kept dry and free of standing water. .2533(d) Pump room floor shall be kept dry and free of standing water.

View this inspection on the county portal ›

May 2, 2017 12 demerits · 3 violations
Inspector comments: PDSC sheet was correct.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed a missing depth marker. The closest 2 markers were 27ft. Corrected during inspection - a depth marker was added.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed a loose rail
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed the rope length at 34ft. Corrected during inspection to 36ft.

View this inspection on the county portal ›

Apr 21, 2016 6 demerits · 1 violation
Inspector comments: Typo on PDSC sheet. PDSC says the equilizers are Waterway 842-821x, but they have Waterway 640-803x installed. CPO willupdate sheet and submit to Katie.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope on the buoy to be 50ft. Corrected onsite to 36ft.

View this inspection on the county portal ›

Apr 22, 2015 10 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed collar loose at hand rail at 3 1/2 ft of pool. **Keep hand rail collars secure.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope knotted under 36ft. Corrected on site - rope was unknotted and rope distance met 36ft requirement.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed water not present at handsink in women's restroom. Corrected on site water was turned on under sink. Water provided.

View this inspection on the county portal ›

May 8, 2014 10 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Maintain gates self closing and self latching. Main gate was not self closing or latching during periods of high wind. Gate was repaired using a tension cord while onsite. A work order has been placed to have the gate spring tightened.
#22 · Premises: emergency telephone provided −6
Provide a working emergency phone. At arrival the phone was not operable. Phone was replaced and is working properly.

View this inspection on the county portal ›

Apr 4, 2014 8 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed debris in the skimmer baskets.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Maintain chemicals in a dry enclosure. Observed the ceiling leaking outside the door where chemicals are stored and splashing into the storage area. Chemicals will be moved temporarily.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Clean the toilets and replace the blown out light in the restroom.

View this inspection on the county portal ›