PRESERVE AT PROSPERITY CHURCH

8451 SUMMERFORD DR., Charlotte, NC 28262
Seasonal Swimming Pool · NC permit/State ID 2060501229
Latest result10 demerits
Last inspectedApr 30, 2026
Inspections on record14
On record sinceApr 22, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01020 Apr 22, 2014: 6Jun 25, 2015: 6May 10, 2016: 12Apr 17, 2017: 10Apr 5, 2018: 10Apr 3, 2019: 10Apr 22, 2020: 10May 26, 2020: 0May 28, 2021: 0Apr 19, 2022: 14Apr 5, 2023: 6Jun 5, 2024: 20May 1, 2025: 8Apr 30, 2026: 10
Apr 22, 2014Lower is betterApr 30, 2026

Inspections & violations

Apr 30, 2026 10 demerits · 2 violations
Inspector comments: No permit restrictions. No Night Swimming.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed one missing weir. CDI - Weir replaced.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed 60 ft rope. CDI - Cut to 36ft.

View this inspection on the county portal ›

May 1, 2025 8 demerits · 2 violations
Inspector comments: Night swimming not permitted. Verified new PDSC form information. Equalizers plugged in skimmers. Variable speed set at 3450.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Door leading to pool deck was not self closing and latching. Repaired by operator during inspection. .2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. One window leading onto pool deck was missing alarm. Replaced by operator during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Several deck chairs closer than 6’, moved during inspection

View this inspection on the county portal ›

Jun 5, 2024 20 demerits · 4 violations
Inspector comments: NO NIGHT SWIMMING. Pump Filtration: Pentair Superflo VST 342002, set at 3450rpm Filtration Piping : 4” skimmer & main drain, 3” return Filter: Pentair TR100
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. Observed hook was not secure attached. CDI
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed windows opening into enclosure opening > 4”. CDI
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Signage was illegible for emergency phone. CDI *Old emergency phone sign removed as old phone is no longer operable.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter stuck. CDI

View this inspection on the county portal ›

Apr 5, 2023 6 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Observed mirrors in restrooms not shatterproof.

View this inspection on the county portal ›

Apr 19, 2022 14 demerits · 5 violations
Inspector comments: 22. covered old phone call box & signage 24. variable speed pump observed to be set at 3450 rpm
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
replaced missing weir during inspection
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
installed 2 additional window alarms during inspection
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
fan not in working order; ventilation is required
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
mirrors to be of shatter-proof construction; shower not in working order
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
floors to be slip-resistant

View this inspection on the county portal ›

May 28, 2021 0 demerits · 0 violations
Inspector comments: No violations.

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 26, 2020 0 demerits · 0 violations
Inspector comments: no night swimming permit issued

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 22, 2020 10 demerits · 2 violations
Inspector comments: No night swimming
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed a broken autofill cover. CDI- Pool operator replaced cover during the inspection
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed phone number on the dialing instruction on the emergency phone to be incorrect. CDI- Pool operator corrected number during the expection.

View this inspection on the county portal ›

Apr 3, 2019 10 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Skimmer baskets filled with debris. Cleaning underway while on site.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Four ground level windows opened fully onto deck. Alarms installed while on site.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. No cross ventilation in pump / chemical room.

View this inspection on the county portal ›

Apr 5, 2018 10 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmer baskets that was filled with debris.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed windows on deck that were able to open fully. CDI PIC, Jen Mullis, was able to decrease opening to 2".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical room. Observed forced ventilation not operable in chemical and pump room and no cross ventilation available.

View this inspection on the county portal ›

Apr 17, 2017 10 demerits · 4 violations
Inspector comments: Pool passed pre-inspection
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working - fixed during inspection
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Natural cross or continuous forced ventilation required in equipment/chemical room
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors should be shatterproof
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Floors should be slip-resistant

View this inspection on the county portal ›

May 10, 2016 12 demerits · 4 violations
Inspector comments: PDSC form information verified today and all items are correct.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed handles of hand rail and ladder to be slightly loose. Repair.
#22 · Premises: emergency telephone provided −6
Observed facilty has emergency dial box that is not operational and a working emergency phone. Box had previously been taped over as to not allow use, however tape was coming off and phone to be sitting on window ledge near box. Phone was secured to wall under emergency phone sign and box was re-taped over to allow for less confusion in the time of need.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed mechanical vent is not operational and no cross ventilation present. Provide ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed mirrors in men and women's restroom to not be shatter resistant.

View this inspection on the county portal ›

Jun 25, 2015 6 demerits · 2 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Maintain all required info on daily records, Ca and Acid readings min. once every 7 days. Observed some weeks missing Ca and Acid readings.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Bags of CaCl and soda ash observed stored on floor of pump room. Store chemicals up off the floor.Need forced or cross ventilation in chemical storage room. Ceiling exhaust fans appear not working. Need to run continuous.

View this inspection on the county portal ›

Apr 22, 2014 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
No more than 4" gap in fence allowed. Observed missing fence posts in two areas leaving gaps larger than 4". One post fixed during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Need forced or cross ventilation in chemical storage room. Ceiling exhaust fans are not working. Need to run continuous.GENERAL COMMENT: Permit Issued

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “PRESERVE AT PROSPERITY CHURCH” or State ID 2060501229). Inspection type (routine vs. follow-up) is not published in the county's data.