4demerits
FARM AT BACK CREEK, THE
1630 DAMASCUS ST, Charlotte, NC 28215
Seasonal Swimming Pool · NC permit/State ID 2060501243
Latest result4 demerits
Last inspectedMay 20, 2026
Inspections on record13
On record sinceMay 27, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 27, 2014Lower is betterMay 20, 2026
Inspections & violations
May 20, 2026 4 demerits · 2 violations
Inspector comments: Night Swimming is NOT permitted.
Note: Observed one (1) gate at rear side of fence. Key to latch was not available and fence latch appears to have been permanently disabled so as to prevent entry.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed one (1) ladder with one of two safety caps missing at point facing wall. Replace as needed.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Observed two (2) boxes of liquid muriatic acid stored on top of buckets of chlorine tablets.
May 27, 2025 14 demerits · 3 violations
Inspector comments: Permit restrictions.
- No night swimming.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris in skimmers.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed ring buoy rope at 60”. CDI. PIC cut to the required length.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Observed one of the fence unable to self latch. CDI. PIC repaired.
May 31, 2024 0 demerits · 0 violations
Inspector comments: CPO Mike Henson present at the time of inspection.
No violations were recorded for this inspection.
Jun 9, 2023 4 demerits · 1 violation
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed slight leaf debris on pool floor
Apr 22, 2022 2 demerits · 1 violation
Inspector comments: No night swimming.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Observed mechanical ventilation fan not working in chemical storage room.
Apr 22, 2021 12 demerits · 4 violations
Inspector comments: CPO Pat was present during the pool inspection. No signature occurred due to covid19 pandemic. Issuance of the pool permit does not negate meeting requirements of executive order 195 or subsequent orders in effect unless such orders are rescinded or suspended by another applicable order. No night swimming shall occur until another visit is made by the regulatory authority for approval.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - Observed pool surface and pool floor with dirt and leaf debris. CDI- CPO cleaned pool floor and surface. EHS was able to see and verify all parts of main drains and pool floor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Observed debris in skimmers. CDI- CPO cleaned pool skimmers.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526 DRESSING AND SANITARY FACILITIES. Paper towels and toilet paper shall be provided. Observed no paper towels or toilet paper in bathroom. PIC provided both items.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed no back flow prevention device on hose bib on/near pool deck.
Apr 22, 2020 0 demerits · 0 violations
Inspector comments: No violations were observed during today's inspection.
Taylor Mastin of AquaTech was present during today's inspection.
No violations were recorded for this inspection.
Apr 11, 2019 8 demerits · 2 violations
Inspector comments: PDSC form correct. Facility does not want night swimming.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. - Observed 2 loose handrails and a loose ladder; CDI (corrected during inspection) items were tightened.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed buoy rope length at 50FT. CDI - rope was cut to 42FT.
Apr 3, 2018 12 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
(.2530/.2537) Observed throw rope 60ft in length. CDI- Pool operator cut throw rope to 42ft.
#22 · Premises: emergency telephone provided −6
(.2530) Observed no emergency phone sign with correct dialing instruction. CDI- Pool operator constructed and mounted an emergency phone sign with dialing instructions near the phone.
Pool Operator Ashton Williams was present during the inspection.
Meck county permit number: 18-601067
Apr 26, 2017 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Ventilation fan not working during inspection. Should have either cross ventilation or forced ventilation in pump/chemical room.
Jun 8, 2016 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED
No violations were recorded for this inspection.
Jun 8, 2015 0 demerits · 0 violations
No violations were recorded for this inspection.
May 27, 2014 0 demerits · 0 violations
Inspector comments: Note: Gate at parking lot remains locked at all times. Gate is not self closing and self latching.
No violations were recorded for this inspection.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “FARM AT BACK CREEK, THE” or State ID 2060501243). Inspection type (routine vs. follow-up) is not published in the county's data.