22demerits
VILLAGES OF EASTOVER GLEN
2520 CRANBROOK LN, Charlotte, NC 28207
Seasonal Swimming Pool · NC permit/State ID 2060501245
Latest result22 demerits
Last inspectedJun 25, 2026
Inspections on record13
On record sinceApr 30, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 30, 2014Lower is betterJun 25, 2026
Inspections & violations
Jun 25, 2026 22 demerits · 5 violations
Inspector comments: NO PERMIT RESTRICTIONS.
NO NIGHT SWIMMING.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH measuring 8.4.
CPO corrected during inspection and EHS observed pH was now measuring 7.5.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris.
Observed debris on pool floors.
CPO stated they are planning on vacuuming today prior to opening on saturday.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions.
Observed missing endcaps on ladder.
Replace missing endcaps to prevent damaging pool wall.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
Observed lounge chairs stored less than 6 ft from pool perimeter.
CPO corrected during inspection so that there is a clear 6 ft of walking space around pool.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Observed posted sign with address of pool was incorrect. Emergency operator stated address on file was actually 2520 Cranbrook Ln, not 2500 Cranbrook Ln.
CPO corrected during inspection so address on file matched address on posted sign.
Apr 12, 2024 0 demerits · 0 violations
Inspector comments: No violations noted at time of visit. Permit and sticker provided. Pool may open at owner’s discretion.
No violations were recorded for this inspection.
May 11, 2023 10 demerits · 3 violations
Inspector comments: No night swimming. Pool closing at 8:30pm. Night swimming prohibited.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine levels at 0.4ppm. Corrected to 1.0ppm.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed two end caps missing on 1 ladder. Replaced during inspection.,
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. Restrooms mirrors not shatterproof.
May 12, 2022 4 demerits · 1 violation
Inspector comments: Signage at fountain states “FOUNTAIN ONLY. NO SWIMMING”. No night swimming.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Pre-2010 built fence has a foot hold around the handicapped entry ramp. The brick fence that extends along this ramp is 26 inches high, with a metal rail extending from it. However, the metal rail is 3 inches from the edge of the brick, and is elevated 2 inches off of the top of the brick, allowing a foot hold. Points deducted but no permit action taken as allowed under 15A NCAC 18A .2528 (c) "Public swimming pools permitted prior to April 1, 2010 with existing fences that do not comply with the dimensional requirements of Subparagraphs (a)(1) through (a)(6) and (b)(1) through (b)(2) shall not be denied an operation permit solely due to the preexisting non-compliance.
Apr 26, 2022 10 demerits · 2 violations
Inspector comments: Maintain access to all gates and doors during operating season.
Provide sign that states “FOUNTAIN ONLY. NO SWIMMING.” For fountain space.
EHS confirmed pump is a Sta-Rite P2RA5FL per pump book photo and horse power on motor (THP is 1.65). Pump does not have ID tag present.
Per conversation with C. Sells, facility must schedule a re-inspection due to address issue. No fee to be paid due to conversation. If address issue is not corrected when re-inspection is conducted, facility will incur a $100 re-inspection fee.
No Night Swimming.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Pre-2010 built fence has a foot hold around the handicapped entry ramp. The brick fence that extends along this ramp is 26 inches high, with a metal rail extending from it. However, the metal rail is 3 inches from the edge of the brick, and is elevated 2 inches off of the top of the brick, allowing a foot hold. Points deducted but no permit action taken as allowed under 15A NCAC 18A .2528 (c) "Public swimming pools permitted prior to April 1, 2010 with existing fences that do not comply with the
dimensional requirements of Subparagraphs (a)(1) through (a)(6) and (b)(1) through (b)(2) shall not be denied an operation permit solely due to the preexisting non-compliance
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. Address for the pool is incorrect with 911 system. 911 has “2504 Cranbrook Ln”. Correct address for pool is “2520 Cranbrook Ln” per Polaris3G/GIS.
May 13, 2021 4 demerits · 1 violation
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Observed pool deck chairs less than 5 ft from pool edge. CDI - Deck chairs were moved.
Jun 11, 2020 8 demerits · 2 violations
Inspector comments: Verified PDSC information.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed brick, a part of fencing, providing foothold <45” from top of iron fence. *No permit action due to pre-2010 construction*
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed decking and tile siding in need of repair throughout pool areas. Observed concrete lifting; trip hazard. Repair/replace as necessary.
Apr 30, 2019 10 demerits · 2 violations
Inspector comments: No night swimming
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
1 weir was broken but fixed during inspection
#22 · Premises: emergency telephone provided −6
phone had incorrect number
the correct number was placed above the phone and the old one marked out
Apr 30, 2018 4 demerits · 1 violation
Inspector comments: 6. EHS was able to verify function of the emergency phone, but audio was not 100% clear, some interference is present. EHS recommends replacing the phone unit.
13. Observed slight paint fading on the contrasting color bands of the steps into the pool. Bands are still visible.
Signage for the fountain feature was present, stating "FOUNTAIN ONLY NO SWIMMING".
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Pre-2010 built fence has a foot hold around the handicapped entry ramp. The brick fence that extends along this ramp is 26 inches high, with a metal rail extending from it. However, the metal rail is 3 inches from the edge of the brick, and is elevated 2 inches off of the top of the brick, allowing a foot hold. Points deducted but no permit action taken as allowed under 15A NCAC 18A .2528 (c) "Public swimming pools permitted prior to April 1, 2010 with existing fences that do not comply with the
dimensional requirements of Subparagraphs (a)(1) through (a)(6) and (b)(1) through (b)(2) shall not be denied an
operation permit solely due to the preexisting non-compliance.
Apr 20, 2017 10 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed plaster damage to the floor of the pool. Damage was puttied over by operator during inspection. Observed to be repaired by EHS before leaving.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder endcap missing at beginning of inspection. Replaced by operator
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed pool chair placed within 5 feet of pool, moved by operator to the minimum 6 feet from the pool edge.
Apr 21, 2016 0 demerits · 0 violations
Inspector comments: Secondary pump on the feature that is no longer a fountain. Exact same type as the pool pump, but the feature pump is 1HP instead of 2HP.
No violations were recorded for this inspection.
Apr 17, 2015 10 demerits · 2 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck furniture is within 10 foot of edge of pool. Space is limited and chaise lounge chairs are being used.
#22 · Premises: emergency telephone provided −6
.2530 Emergency call box did not function properly. When call box is activated 911 Emergency is notified and they can hear this end but they cannot be heard. A phone was connected into the box line and 911 was available. Via telephone. Operator will have box repaired or replaced and call to notify it is done. Corrected during inspection.
Apr 30, 2014 18 demerits · 6 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Greater than 25' distance between depth markers around fountain. Provide 3' depth markers at side of fountain near stairs. Provide 3' depth marker at blue fountain tile near stairs. Greater than 25' distance between no diving markers. Add a no diving marker in front of fountain at deck.INTNET TO SUSPEND ISSUED FOR THIS VIOLATION. MUST BE COMPELTED WITHIN 30 DAYS.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fencing with footholds (horizontal bars/bricks within 30"). Eliminate footholds. Make horizontal bars greater than 30".
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Damaged fountain bricks. Repair. (not a trip hazard).
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No cross ventilation. Provide cross ventilation or forced ventilation.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap on backwash/discharge line. Provide an air gap above the grade of floor.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Glass mirrors. Provide shatterproof mirrors.Roger Rockholt present.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “VILLAGES OF EASTOVER GLEN” or State ID 2060501245). Inspection type (routine vs. follow-up) is not published in the county's data.