4demerits
WINDYRUSH COUNTRY CLUB
6441 WINDYRUSH RD, Charlotte, NC 28226
Seasonal Swimming Pool · NC permit/State ID 2060501264
Latest result4 demerits
Last inspectedMay 5, 2026
Inspections on record13
On record sinceMay 8, 2014
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 8, 2014Lower is betterMay 5, 2026
Inspections & violations
May 5, 2026 4 demerits · 1 violation
Inspector comments: Night swimming approved based off of 2024 visit.
In-field plan review.
One depth marker on deck at step entry loose. Secure to deck. Light at 4 ft. and at 12 ft, not flush to wall. Secure to wall to ensure 1/2" or less gaps.
EHS checked above items and all were in compliance.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed one gate not self-colsing/self-latching. CDI - Gate was repaired during inspection.
Apr 28, 2025 2 demerits · 1 violation
Inspector comments: Phyllis Smith present during inspection
REHS verified pool lighting is functional during inspection. Pool approved for night swimming in 2024, approved for 2025.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed loose handrails and ladders -2-
Apr 30, 2024 12 demerits · 3 violations
Inspector comments: Inspection conducted with CPO, Phyllis Smith and WIlliam Hill Smith IV present. PDSC information verified onsite.
General Comments:
*Observed chlorine to be over 10. Recommend to reduce chlorine to avoid skin irritation.
Pool and deck lighting observed to be operable during inspection.
Approved for night swimming.
Permit issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 3 of 12 skimmers missing their weirs. CPO provided receipt of 12 additional weirs purchased with ETA of 5/3/24. -4-
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed two loose hand rails. -2-
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope exceeding 50’. CDI by CPO. -6-
May 9, 2023 0 demerits · 0 violations
Inspector comments: Pool is approved for 2023 season. Night swimming is approved as well (inspection in 2022). New PDSC form on file.
No violations were recorded for this inspection.
May 2, 2022 8 demerits · 3 violations
Inspector comments: PDSC form verified.
Night swimming - verified all lighting was functional and matched drawing.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder was loose. It was secured during inspection.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. Sign was missing. It was provided during the inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(i) Water in restrooms shall not exceed 110 F. Water in both restrooms was 126F. Water heater was turned down to its lowest setting during the inspection.
Apr 29, 2021 6 demerits · 1 violation
#2 · Water quality: disinfectant residual provided by −6
Cl level was .8 when tested CDI Cl was turned up and retested at 3.0.
May 12, 2020 0 demerits · 0 violations
Inspector comments: Observed Hayward pump removed from system, plumbing removed.
Pump wired in pump room, padlock on disconnect in the off position.
Verified PDSC information
Observed no non-complaint conditions.
Phyllis Smith present during inspection.
No signature due to COVID-19 Social distancing requirements.
No violations were recorded for this inspection.
May 31, 2019 24 demerits · 7 violations
Inspector comments: Unapproved booster pump on filtration system for slide.
Pump line is broken. Pump must remain not operational until suction hazards are addressed and update PDSC form must be submitted and approved prior to using the slide pump
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed debris in skimmers. Observed one weir in deep end stuck.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
.2518(k) Replace missing/damaged weirs.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Observed safety ropes not installed.
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint.
Corrected during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders loose.
.2521 Install ladders per manufacturer instructions.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed only one body hook. Corrected during inspection.
.2530(b) Two units of lifesaving equipment (or two lifeguards) must be provided for pools that exceed 3,000 sq. ft. surface area.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed holes is deck for volleyball posts.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
Corrected during inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed pump on return line for slide. Disabled because of damaged line.
Pump must remain not connected until pump installation is approved and a PDSC form is submitted and approved.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed mirrors not shatterproof. Removed during inspection.
.2626(k) Provide shatterproof mirrors.
Apr 17, 2018 14 demerits · 4 violations
Inspector comments: Permit Restrictions: No night swimming.
Lighting for night swimming will be verified at a later date.
PDSC information verified during inspection.
Per operator, pool will be lifeguarded at all hours of operation.
16) .2537(b) All gates and doors shall be self-closing, self-latching. Observed one section of fence where bottom is bowing away from posts, causing the gap to widen. Monitor fence to ensure that gap does not exceed 2".
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed debris on pool floor obscuring leftmost main drain. CDI: Debris cleared from drains and pool cleaned.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed three missing weirs on skimmers throughout deck. CDI: All weirs replaced during inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed several skimmers filled with debris. CDI: Skimmers cleared.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed three ladders loose from deck. CDI: Operator tightened all three ladders during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed one gate connecting wading pool and main pool deck unable to self close and self latch. CDI: Operator permanently bound gate with cord, as the properly functioning gate will be used as the only point of entry to pool.
May 9, 2017 12 demerits · 3 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Heavy debris covering all main drains. CDI Debris moved off of main drains.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed debris on skimmer by slide. CDI Debris removed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
2 loose ladders. CDI Ladders tightened.
May 12, 2016 0 demerits · 0 violations
No violations were recorded for this inspection.
May 7, 2015 4 demerits · 1 violation
Inspector comments: 21. Observed some pool lighting fixtures working. If night swimming occurs ensure all light fixtures are in good repair. Permit will be available on county website in 3 days.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed skimmer baskets soiled with debris and one weir near lifegaurd chair. Keep skimmer baskets clean and in good repair.
May 8, 2014 20 demerits · 5 violations
Inspector comments: #16: Suggest placing spring on gate to wading pool for added safety.
#23: Check flow meter frequently to ensure proper operation.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Missing equalizer covers (2). Items were corrected during inspection. CDI
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Need to have extra hair/lent basket. Also note3d a couple of the weirs were not free floating.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
ensure that all ladders and handrails are tight and secure. Check frequently.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Replace ring buoys. Rope was fraying. Buoy must be in good condition to be USCG approved. Corrected
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Provide vacuum breaker on all hose bibs.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “WINDYRUSH COUNTRY CLUB” or State ID 2060501264). Inspection type (routine vs. follow-up) is not published in the county's data.