8demerits

LEGACY CORNELIUS

8335 LAKE PINES DR, Cornelius, NC 28031
Seasonal Swimming Pool · NC permit/State ID 2060501268
Latest result8 demerits
Last inspectedApr 23, 2026
Inspections on record13
On record sinceMar 26, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01734 Mar 26, 2014: 4Mar 23, 2015: 2Apr 11, 2016: 2May 3, 2017: 4Apr 24, 2018: 12May 3, 2019: 6May 22, 2020: 34May 20, 2021: 0Jun 2, 2022: 0May 23, 2023: 0Apr 9, 2024: 0Apr 24, 2025: 0Apr 23, 2026: 8
Mar 26, 2014Lower is betterApr 23, 2026

Inspections & violations

Apr 23, 2026 8 demerits · 3 violations
Inspector comments: Inspection completed with CPO, Jesse Corum All permit compliance items corrected during inspection Interlock tested and operational CPO log records begin today NIGHT SWIMMING NOT ALLOWED Permit Restriction - Flow meter must remain operable. Flow shall not exceed 100gpm due to pipe size flow restriction. Flow greater than 150gpm exceeds the main drain flow. Suction Hazard Permit issued
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. .2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Observed an audible alarm detached from one inside window. CDI - Alarm was reattached during inspection. Observed one ground level door (far side office room) without an audible alarm. CDI - Door was permanently locked until an alarm can be installed. All other windows and doors contain and audible alarm or permanently screwed shut.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed broken ventilation system in the pump room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(i) Water in restrooms shall not exceed 110 F. .2526(k) Provide shatterproof mirrors. Observed 115 degree water in the restroom sinks. Observed glass mirrors in the restrooms.

View this inspection on the county portal ›

Apr 24, 2025 0 demerits · 0 violations
Inspector comments: No violations noted during inspection No night swimming

No violations were recorded for this inspection.

View this inspection on the county portal ›

Apr 9, 2024 0 demerits · 0 violations
Inspector comments: No violations noted during inspection

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 23, 2023 0 demerits · 0 violations
Inspector comments: EHS verified all PDSC information, pumps, drain covers, equalizer covers and flow meter restrictions- all in compliance during inspection. NO night swimming, according to CPO Jesse Corum. Permit issued.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Jun 2, 2022 0 demerits · 0 violations
Inspector comments: Jesse Corum present during the inspection. Verified the following: Permit Restriction Pump required set at 3110 RPM with flow meter not to exceed +/-10% of 100 gpm due to pipe sizing. Pump Pentair Intelliflo VSF 011056 Blue White flow meter with 2” pipe. Measured pipe before the flow meter and after the flow meter. Observed the required at least 10” on inlet and 4” on outlet. Observed the flow meter reading 100 gpm after the pool has backwashed the filter. Record the flow on the inspection. Main drain, skimmer and return line all 3” pipe (2) Aquastar 1216xxx drain covers (3) Aquastar 6HPxxx equalizer line covers (1) Pentair TR140C filter (6) returns either on floor or wall (3) skimmers Night swimming NOT permitted.

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 20, 2021 0 demerits · 0 violations
Inspector comments: No demerits noted on this inspection. Depth markers have been repaired to express depths in “FT”. This information from May 20, 2021 was entered into inspection system today, June 9, 2021, due to an error in reporting previously. Inspection information was entered under the wrong facility.

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 22, 2020 34 demerits · 7 violations
Inspector comments: Inspection conducted with Eddy Dixon. Due to COVID-19 precautions, inspection was not signed by the operator. Contact Will Harrison (704-507-6824) to field verify items when they have been fixed. Permit issued. No night swimming. “Issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
One screw missing from each of the main drains. .2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7 and installed per manufacturer's instructions. Will verify completion next week.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Plaster etching on sunshelf. Operator plans to replaster before next year.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
4" depth marker in the shallow end of the pool. .2523(c) Depth markers shall include the word "feet" or symbol "ft". This will need to be corrected prior to 2021 operational permit being issued.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope too long. .2530(a) Provide USCG approved ring buoy with 33 foot throw rope. Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Magnetic gate latches < 45", creating a foothold. .2528(a) Maintain 45" between bottom horizontal and next horizontal on fence and/or gate (post-May 2010). Operator will install 45 degree angled metal to be verified next week. Thumbscrews removed from windows in fitness center and some of the windows in the clubhouse. .2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Will verify next week.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs too close to pool edge. .2522(a) Provide 6 ft of clear walking space around the pool at all times. Corrected. Holes in the deck from missing lift. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Operator will install the lift prior to opening the pool.
#22 · Premises: emergency telephone provided −6
Incorrect phone number posted for emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Corrected.

View this inspection on the county portal ›

May 3, 2019 6 demerits · 2 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed loose handrail. Corrected during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed lounge chair within 6 ft of pool. Corrected during inspection.

View this inspection on the county portal ›

Apr 24, 2018 12 demerits · 2 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed missing cover on vacuum port. CDI-self closing cover placed on port.
#22 · Premises: emergency telephone provided −6
Observed incorrect phone number posted for emergency phone number. CDI-changed to correct phone number.

View this inspection on the county portal ›

May 3, 2017 4 demerits · 1 violation
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One of the gates would not self close. Corrected during inspection.

View this inspection on the county portal ›

Apr 11, 2016 2 demerits · 1 violation
Inspector comments: Pool passed pre-inspection Report received by Bill Euton
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Floors should be slip resistant

View this inspection on the county portal ›

Mar 23, 2015 2 demerits · 1 violation
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Floors should be slip resistant

View this inspection on the county portal ›

Mar 26, 2014 4 demerits · 1 violation
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from clubhouse to pool deck was not self closing or latching today- repaired during inspection to correct.

View this inspection on the county portal ›