14demerits

MAA AYRSLEY

9005 LENOX POINTE DR, Charlotte, NC 28273
Seasonal Swimming Pool · NC permit/State ID 2060501324
Latest result14 demerits
Last inspectedApr 21, 2026
Inspections on record12
On record sinceApr 7, 2015

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0918 Apr 7, 2015: 16May 3, 2016: 8Apr 24, 2017: 18May 2, 2018: 12May 3, 2019: 4May 8, 2020: 6Apr 22, 2021: 0Jul 1, 2022: 6May 8, 2023: 0May 16, 2024: 4May 6, 2025: 8Apr 21, 2026: 14
Apr 7, 2015Lower is betterApr 21, 2026

Inspections & violations

Apr 21, 2026 14 demerits · 3 violations
Inspector comments: Inspection conducted with CPO, Chris Johnson. No permit restrictions. Permit issued. Field verification of flow not conducted due to meter reading at maximum capacity. CPO must replace with accurate flow meter within 10 days or an Intent to Suspend will be issued. Contact EHS to schedule verification. Interlock tested and operable. Night swimming not allowed.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy rope exceeding 50 feet. Corrected- CPO trims to required 42 feet.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed restroom door through leasing office onto pool deck not self latching.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate. Observed flow meter maxed out at 120GPM, and maximum flow of pump listed at 148GMP. Accurate reading cannot be taken during inspection. CPO must replace with an accurate flow meter within 10 days or Intent to Suspend will be issued. Research out to EHS for verification. *Note, new flow meter must measure 1.5x design flow rate; do not replace like-for-like, as present meter is undersized.

View this inspection on the county portal ›

May 6, 2025 8 demerits · 2 violations
Inspector comments: 120 GPM Inspection Conducted with Christopher Johnson, CPO present. PDSC information verified. No permit restrictions. All non-compliant items corrected during inspection by CPO. Not permitted for night swimming. Permit issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Debris found in skimmers throughout pool during permit. CDI
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool chairs that were closer than 6 ft to pool edge. CDI

View this inspection on the county portal ›

May 16, 2024 4 demerits · 1 violation
Inspector comments: No night swimming permitted. 90 GPM Pool will be open from dawn til dusk.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris (leaves) in skimmers at time of inspection.

View this inspection on the county portal ›

May 8, 2023 0 demerits · 0 violations
Inspector comments: No Violations noted. No Night Swimming Permitted.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Jul 1, 2022 6 demerits · 2 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2514(c) Pool finish shall be white or light colored. Observed light algae growth. Maintain pool free of algae. Do not open pool if pool chemistry is not correct or algaecides are present.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed one rubber foot fell off ladder.

View this inspection on the county portal ›

Apr 22, 2021 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED

No violations were recorded for this inspection.

View this inspection on the county portal ›

May 8, 2020 6 demerits · 1 violation
Inspector comments: very slight deck damage noted near the rear step ladder, does not consitute a trip hazard but should be repaired in off season.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope observed at 60 feet, shortened to required length during inspection.

View this inspection on the county portal ›

May 3, 2019 4 demerits · 1 violation
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Horizontals between fence measured less than 45 inches (36 inches). Pool built prior to 2010.

View this inspection on the county portal ›

May 2, 2018 12 demerits · 4 violations
Inspector comments: 11. Observed 2 loose ladders. Pool operator informed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed 2 loose ladders. Pool operator informed.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
-Observed the space under a 5". (Constructed 2008). -Observed an opening between the fence posts at 5 inches in one area. CDI- Extra bar that was added lessen the space to less than 2 inches.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed lounge chair less than 6 feet from the pool edge. CDI- Relocated the chair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed the pump room floor wet and water coming from by the handle of where the backwash gets turned on. No Night Swimming. Permit issued: 18-600636 (county); 2060501324 (state) Report emailed to tracy.pryor@maac.com

View this inspection on the county portal ›

Apr 24, 2017 18 demerits · 5 violations
Inspector comments: Please allow up to 3 business days to access your permit at meckpools.charmeck.org. Ensure that permit is visible at pool. New motor installed per operator as of 1 week prior to inspection. Motor is 2.25 HP, US Motors. Pump has not been changed out per operator.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Various floating debris in baskets, two damaged baskets. Operator cleared out, replaced baskets. Maintain clear.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Loose entry ladder on far right side of pool near shallow end of pool; loose ladder at main steps near underwater bench. Tighten/ repair ladders.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool chairs on far right side of pool within 6FT of clearance of pool. Operator relocated chairs.
#22 · Premises: emergency telephone provided −6
Initial phone number provided/ uncovered was 704-583-0024 and 704-449 number was covered with tape. Operator advised that he had been advised to cover the 704-449 number. 911 operator only confirmed the 704-449 number. Tape was removed from correct number.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Directional lines not provided on piping at pump equipment. Provide directional flow lines on pump equipment lines.

View this inspection on the county portal ›

May 3, 2016 8 demerits · 2 violations
Inspector comments: #29: General Comment: Tighten fixture in female restroom (loose)
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Missing ladder bumber. Replace to prevent damageing pool wall.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy not approved due to fraying line. Buoy was corrected during inspection.

View this inspection on the county portal ›

Apr 7, 2015 16 demerits · 5 violations
Inspector comments: Correction to L. Boyes (EHS) 3/11/15 inspection & the inspection before this conducted by K. Wilson (Sr. EHS); Since the pool barrier was constructed prior to 5/1/10 & the horizontal members of the barrier/ fence are not <30", the barrier is allowed to vary from .2528(a)(4). SEASONAL POOL PERMIT CAN BE ISSUED.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Pool records indicate that cyanuric acid levels are only being recorded one time per month. ** Check & record at least one time per week.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose at stairs (cabana end of pool). ** Secure. Two ladders ~6.5" to 7" from pool wall. ** Clearance should only be 3" to 6"; however, problem cannot be corrected without raising ladders due to slope of pool wall.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Damaged coping near 1' marker & sunken bricks at autofill. ** Repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Multi-port valve handle broken off at one filter. ** Replace broken parts.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals being stored in equipment room. ** Store in chemcial room provded. Forced air vent in equipment room inoperable. ** Repair.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “MAA AYRSLEY” or State ID 2060501324). Inspection type (routine vs. follow-up) is not published in the county's data.