YUGO CHARLOTTE COLLEGE DOWNS
1505 MONUMENT HILL RD, Charlotte, NC 28213
Seasonal Swimming Pool · NC permit/State ID 2060501340
Latest result4 demerits
Last inspectedApr 24, 2026
Inspections on record14
On record sinceJun 16, 2015
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 16, 2015Lower is betterApr 24, 2026
Inspections & violations
Apr 24, 2026 4 demerits · 1 violation
Inspector comments: PERMIT RESTRICTIONS: Flow meter must remain operable. Flow required at least 179 gpm to 212 gpm to meet turnover and flow restriction on filter flow.
NIGHT SWIMMING NOT PERMITTED
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Adults should not swim alone." in 1" lettering. Observed required signage was not posted at the time of inspection. Issue was corrected during the inspection. Signage was posted and proper height was verified by EHS.
May 23, 2025 4 demerits · 1 violation
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Where grout transitions to brick at sun shelf entrance, brick is roughly cut and has a sharp protrusion on side of pool. CDI - operator covered protrusion with pool grout to smooth transition until protrusion can be ground down.
May 9, 2025 12 demerits · 3 violations
Inspector comments: Permit denied for pool deck, skimmer baskets, signage, and filter backwash.
Inspection conducted with Patrick Sigley.
No night swimming.
Facility is using valve on backwash line to stop water. THIS MUST BE CORRECTED PRIOR TO PERMIT ISSUANCE.
Pump has been replaced and field verification of following items has been completed.
• Flow meter within required range.
• Pump model verified - SuperfloVST 342002.
• Blue-white flow meter installed.
• Main drain 6” pipe, return line 4” pipe.
• Aquastar WAV18WRxxx 2017 main drains.
• Skimmers with EQ lines plugged.
• Pentair TR140 filters.
* 14 floor returns (item differs from verification checklist but is still compliant).
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing or damaged skimmer basket. Two skimmer baskets were damaged.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Where grout transitions to brick at sun shelf entrance, brick is roughly cut and has a sharp protrusion on side of pool. Protrusion must be cut off or ground down until transition is smooth.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering. Sign has required wording at 1/2” height.
.2530(c) Provide "Adults should not swim alone." in 1" lettering. Sign has required wording at 1/2” height.
May 16, 2024 6 demerits · 1 violation
#22 · Premises: emergency telephone provided −6
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. Observed kings III rerouting wrong address to 911. Permit issued. But will follow up with Kings III.
Apr 25, 2024 20 demerits · 4 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing or damaged skimmer basket. Observed damaged baskets at the pool. CDI. Baskets replaced.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy that is not USCG approved. CDI. PIC replaced.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed incorrect phone address on emergency phone during time of inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Install flow meter on return line per manufacturer instructions. Observed flow meter in disrepair.
May 25, 2023 4 demerits · 1 violation
Inspector comments: .2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Observed 4" of space under fence. CDI- Areas filled
9-11 does not have address or phone number on file.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept in good repair. Observed holes in deck area. Get repaired.
Apr 13, 2022 16 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris in skimmer baskets.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length at 60ft. Corrected during inspection to 50 feet.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed incorrect phone number on emergency phone during time of inspection. CDI, phone number that 911 has was posted and EHS verified that the number called back to the emergency phone.
Apr 1, 2021 10 demerits · 2 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope less than 50 feet long. Actual length 48ft. Pool operator corrected the issue by providing a rope that was 50 feet long.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(b) Horizontals shall not be located less than 45" in height. Provide no external handholds or footholds within 45" of fence height. Observed a ladder leaning against the fence. Pool operator removed ladder form location. Observed a small electrical box within 41 inches of the fence height. Pool operator cut off zip ties, and re-positioned electrical box. To meet 45" requirement.
Apr 24, 2020 10 demerits · 3 violations
Inspector comments: Due to COVID19 no signature occurred.
CPO Gary Miller was present during inspection.
Permit Conditions to be inserted on permit.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 - Maintain rails and ladders shall be maintained in good repair. Observed rails on 3ft end of pool in need of tightening.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope 48 ft. CDI- PIC provided 50 ft rope.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. - Observed standing water in pump room.
Apr 2, 2019 6 demerits · 2 violations
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2626(a) Post a shower sign visible upon entrance to the pool.
Apr 10, 2018 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Restroom mirrors should be shatterproof.
GENERAL COMMENT: PERMIT ISSUED State permit number 18-600531
Apr 20, 2017 4 demerits · 1 violation
Inspector comments: resubmit PDSC forms with correct pump information.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Maintain an 8 foot walkway around the pool deck. Observed pool furniture within 8 feet of the pool deck. CDI
Apr 15, 2016 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
KEEP HAND SOAP ACCESSIBLE IN RESTROOMS
Jun 16, 2015 8 demerits · 2 violations
Inspector comments: Permit will be available online at Meckpools.charmeck.org within 3 business days.Print permit and post a copy of the permit in the pool area.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weirs not functioning properly. Water level over the skimmers. Autofill incorrectly adjusted. Operator unable to adjust autofill. Autofill turned off until corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gaps > 2" under fence. Fence cannot have any gaps > 2" under fence. Corrected by operator.Back right gate does not readily close on its own. Gates shall be self-closing and self-latchingCorrected by operator.