0demerits
FLATS AT BALLANTYNE, THE
9550 COMMUNITY COMMONS LN, Charlotte, NC 28277
Seasonal Swimming Pool · NC permit/State ID 2060501370
Latest result0 demerits
Last inspectedJun 5, 2026
Inspections on record10
On record sinceMay 15, 2017
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 15, 2017Lower is betterJun 5, 2026
Inspections & violations
Jun 5, 2026 0 demerits · 0 violations
Inspector comments: No violations observed. Night swimming not permitted. No permit restrictions. Newly installed main drains verified during inspection.
No violations were recorded for this inspection.
Apr 22, 2025 6 demerits · 1 violation
Inspector comments: Permit issued. All violations corrected. Pool may open at owners discretion.
Inspection completed with Lamin Coneth.
Back up battery operational.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed rope for ring buoy at 33ft. CDI - PIC shortened rope to required 30ft.
Apr 24, 2024 4 demerits · 1 violation
Inspector comments: Inspection completed with Lamin Coneth
Back up battery operational
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. Observed gap near latch, that is less than 54”, where someone can stick their arm in to open the latch. CDI operator moved steel mesh to close the gap and prevent easy access to pool.
Apr 18, 2023 10 demerits · 3 violations
Inspector comments: Ensure that vacuum port is maintained closed. It was recently in use but was closed during the inspection. Operator is aware a tool is needed to operate port.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed some debris inside of surface skimmers.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Observed one ladder greater than 6 inches from the pool wall. Retighten to prevent possible entrapment hazard.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Observed some areas under the fence with up to 5 inches or more free clearance under the fence where mulch has been moved.
Apr 14, 2022 6 demerits · 1 violation
Inspector comments: Observed eon be loose tile on deck of pool near large entrance to pool. Pool operator stated this one tile will be repaired. No night swimming requested.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. Observed open vacuum port at beginning of inspection. Per pool operator, this port requires a tool to open. CDI - Pool operator closed port and stated maintenance just vacuumed pool. EHS advised pool operator of post-May 2010 requirement to have self-closure on vacuum port that requires a tool to open. Cap is spring loaded. Cap remained closed after pool operator closed. -6-
Apr 7, 2021 4 demerits · 1 violation
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater light is not secured to wall. CDI light was secured to wall.
Apr 22, 2020 6 demerits · 1 violation
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Ring rope 50' when 30' required. Operator adjusted rope to 30' as required in field book.
Apr 3, 2019 6 demerits · 1 violation
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Replace ring buoy before 2020 permit. Starting to dry-rot.
Apr 27, 2018 0 demerits · 0 violations
No violations were recorded for this inspection.
May 15, 2017 6 demerits · 2 violations
Inspector comments: Pre-permit inspection passed. Permit issued.
Permit shall be posted visible upon entrance to the pool.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One gate not self-closing. Repaired during inspection.
Fence <48" in one location due to landscaping. Corrected during inspection.
Fencing at patios corrected to 48" with 45" in between horizontals with 2" or less. Permit Restriction - Window limiters must remain on windows so that windows do not open greater than 4" on to pool deck.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Corrected during inspection.