14demerits
MERIDALE
7406 MERIDALE FOREST DRIVE, Charlotte, NC 28269
Seasonal Swimming Pool · NC permit/State ID 2060501443
Latest result14 demerits
Last inspectedApr 15, 2026
Inspections on record8
On record sinceMay 7, 2019
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 7, 2019Lower is betterApr 15, 2026
Inspections & violations
Apr 15, 2026 14 demerits · 4 violations
Inspector comments: - No Night Swimming
- Flow meter must Remain tiresomely. Flow required at 188 - 220 GPM to meet turnover
Confirmed:
- New pump installed. Hayward HCP 30703, 7.5 TPH
- Flow Vis flow meter installed and set to 188gpm.
- 4” pipe on main drain, skimmer lines
- 3” on return lines
- 2 Lawson MLD-SG-1212 drain north
- 6 Skimmers, Equalizers plugged.
- 2 Pentair TR104C filters
- 11 returns
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed slight pool debris present in bottom of pool. Clean as needed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed handrail loose. Tighten.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed 60ft rope. CDI - Cut to 48”
“
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed backwash discharged through an air break. Cut pipe above flood plane.
Apr 17, 2025 6 demerits · 1 violation
Inspector comments: No night swimming.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope tangled at beginning of inspection, untangled during inspection.
May 1, 2024 0 demerits · 0 violations
No violations were recorded for this inspection.
Apr 12, 2023 6 demerits · 1 violation
Inspector comments: No night swimming requested.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed safety rope at 58ft. Per pool requirements, rope shall be 48ft. CDI - Operator reduce rope size to 48ft.
Apr 26, 2022 0 demerits · 0 violations
Inspector comments: No Demerits. Permit Issued
No violations were recorded for this inspection.
Apr 9, 2021 0 demerits · 0 violations
Inspector comments: PDSC verified
No violations were recorded for this inspection.
Apr 13, 2020 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
front gate not self latching, repaired during inspection
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
water dripping from sink, toilets were being repaired, mirrors to be of shatterproof construction
May 7, 2019 0 demerits · 0 violations
Inspector comments: Observed no non-compliant conditions.
Verified PDSC improved.
No violations were recorded for this inspection.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “MERIDALE” or State ID 2060501443). Inspection type (routine vs. follow-up) is not published in the county's data.