16demerits
PROVIDENCE COURT APARTMENTS
8110 PROVIDENCE COURT LN, Charlotte, NC 28270
Seasonal Swimming Pool · NC permit/State ID 2060501474
Latest result16 demerits
Last inspectedJul 1, 2026
Inspections on record7
On record sinceMay 13, 2020
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 13, 2020Lower is betterJul 1, 2026
Inspections & violations
Jul 1, 2026 16 demerits · 3 violations
Inspector comments: No night swimming.
Permit Restriction - Flow meter must remain operable. Flow not to exceed 119 gpm due to drain cover flow restriction. Suction Hazard.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pool pH at 7.0. CDI - pH was adjusted to 7.2
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed 2 gates not self-latching. One is blocked by gutter spout. Needs to be self-closing, self-latching. CDI - Gates were fixed to be self-closing, self-latching.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed incorrect pool phone number posted. CDI - Correct pool number was posted.
Jun 4, 2025 6 demerits · 1 violation
Inspector comments: Pool inspection completed with CPO Jermey Hill
Equalizer covers expire 11/25 and must be replaced to be permitted before 2026 pool inspection.
Flow meter observed operable.
Flow meters not to exceed 119 GPM.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed rope length at 44 ft.
CDI - Extremely Large knot untied and allowed to make rope 45ft long.
May 15, 2024 4 demerits · 1 violation
Inspector comments: Keep pool clean
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Keep inside pool clean
Aug 8, 2023 0 demerits · 0 violations
Inspector comments: Pool is open for 2023 season. No night swimming permit. The pump/drains/equalizers meet the PDSC form.
No violations were recorded for this inspection.
May 17, 2022 26 demerits · 7 violations
Inspector comments: Night swimming is not approved. Contact your local health department for approval.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Observed debris in skimmers. CDI- CPO cleaned skimmers.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. - Observed throw rope to be 47ft. CDI- CPO provided rope at 45ft.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. - Observed 3 gates not self closing and self latching. CDI- CPO corrected gates to be self closing and self latching.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. - Observed no power to emergency phone. CDI- CPO provide power to emergency phone by the end of the inspection. EHS was able to use and verify all emergency phone info.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. - Observed standing water in pump room. No pipes were leaking during inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(k) Provide shatterproof mirrors. - CPO and EHS unable to verify mirrors are shatterproof.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. - Observed all hose bibs within 50 feet of pool deck without proper back flow devices.
May 13, 2021 26 demerits · 6 violations
Inspector comments: Item was corrected during inspection
#3 · Water quality: pool water pH −6
raised Ph to 7.7 during inspection
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
weir was stuck and clean basket in the skimmer
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
A new throw rope needed. The rope is in failing conduction and needs to be 45ft
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
3 gates are not self closing. 1 stays open, 2 gates do not close because of small tree limb and pipe from gutter blocking gate
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
flow meter stuck
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
showers not working.
May 13, 2020 20 demerits · 4 violations
Inspector comments: PERMIT ISSUED. STICKER ISSUED. POOL IS NOT APPROVED FOR NIGHT SWIMMING. IF NIGHT SWIMMING IS DESIRED, A NIGHT SWIMMING EVALUATION MUST BE PERFORMED. CONTACT C. ELMORE AT 704-507-6814 FOR THIS EVALUATION IF NIGHT SWIMMING IS DESIRED.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
POOL HAS AQUASTAR A10RCFR EQ LINE COVERS. THESE COVERS EXPIRE SEPTEMBER 2020. WHEN THE CURRENT COVERS EXPIRE, NEW COVERS MUST BE RATED FOR THE REQUIRED FLOW RATE OF THE CIRCULATION SYSTEM.
NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING
C. ELMORE VERIFIED THAT THE DECK LIGHTS IN QUESTION FROM THE LAST VISIT BY K. RUDISILL WERE REMOVED AND THAT BOTH BATHROOMS IN THE LEASING BUILDING WERE SUPPLIED WITH HOSE BIBBS WITH BACKFLOW PREVENTERS.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed 1 weir missing, weir was replaced. -CDI
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed no body hook pole when Inspector Elmore returned to this pool after performing lower pool inspection to evaluate gate corrections. Previously present body hook pole, which was correct, was no longer present at this pool. A new correct body hook pole was required to be obtained as one could not be found on the property except for the correct one now at the lower pool.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence gaps greater than 4 inches in some places. No permit action taken. Fence was built prior to 2010.
Observed some gates not fully self closing and not fully self latching. Gates were corrected. -CDI
#22 · Premises: emergency telephone provided −6
Observed posted phone number not correct at the Kings III box. Proper number 704-845-5781 was verified with local 911, verifed by call back, and correctly posted.