2demerits
HYATT PLACE
7900 FOREST POINT BLVD, Charlotte, NC 28273
Seasonal Swimming Pool · NC permit/State ID 2060501508
Latest result2 demerits
Last inspectedMay 15, 2026
Inspections on record6
On record sinceJun 2, 2021
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 2, 2021Lower is betterMay 15, 2026
Inspections & violations
May 15, 2026 2 demerits · 1 violation
Inspector comments: Re-inspection with night inspection verification conducted. Permit issued.
Establishment is approved for night swimming with all three over head lights and pool-wall lights on between dusk and dawn.
Emergency phone line now operable.
NOTE: Pump flow was observed at 110GPM upon arrival. Flow restriction necessitates 53-74GPM range. Flow corrected by decreasing power to motor.
Motor must be maintained between 2000-2050RPM to meet flow restrictions.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Observed ventilation in pump room not operational. Repair.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Observed one jug of liquid chlorine on ground in pump room. Bring all chemicals off the ground for storage.
May 13, 2026 14 demerits · 4 violations
Inspector comments: Permit Restriction: Pool flow must be at least 53gpm for turnover and cannot exceed 74gpm for filter limitation. A 5% accurate flow meter must remain operational Pump max flow should not exceed drain cover limitation of 119gpm. Suction hazard.
Inspection accompanied by CPO, Mark Caison.
Permit denied due to inoperable emergency phone. Repair prior to re-inspection.
Interlock tested and operable. Field verification conducted. 5% accurate Blue White F-300 flow meter observed at return line.
Night swimming approval requested: onsite visit after sunset or before dawn required. EHS will discuss with CPO prior to re-inspection.
Before re-inspection CPO should contact main office at 980-314-1620 to pay $100 re-inspection fee.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.
Observed primary gate into pool deck unable to close.
Corrected- CPO repaired during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system.
Observed emergency phone line only able to reach main office, but allowing no other outgoing calls.
CPO contacts Spectrum during inspection. Repair prior to re-inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Observed inoperable ventilation in pump room. Repair.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Post a shower sign visible upon entrance to the pool.
Observed no shower signage on pool deck. Provide signage direction swimmers to shower prior to entering pool.
May 30, 2025 8 demerits · 3 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed cracked depth markers on deck. Replace.
.2537(2) Decks shall be kept in good repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed mechanical ventilation not functioning in chemical storage room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Observed no shower sign posted.
.2526(a) Post a shower sign visible upon entrance to the pool.
May 23, 2025 28 demerits · 6 violations
Inspector comments: Permit Restriction: Pool pump flow must be at least 63gpm for turnover can cannot exceed 98gpm for filter limitation. Flow meter must remain operational.
Permit not issued for the following items. Repair prior to requesting a return inspection.
Call Chris Sells at 704 576 8678.
G.S. 130A-2(3) Chlorine added directly to swimming pool. Chlorination must occur through chlorinator. Eliminate direct hazard to public.
.2537 Plug equalizers per state requirements in skimmer and on wall.
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present.
.2518(g) Keep flow meter operational.
.2530(a) Provide at least 12 ft. long pole with body hook securely attached.
#2 · Water quality: disinfectant residual provided by −6
Observed
G.S. 130A-2(3) Chlorine added directly to swimming pool. Chlorination must occur through chlorinator. Eliminate direct hazard to public.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Equalizers not plugged in skimmer, on wall only.
Plug equalizers per state requirements in skimmer and on wall.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed 2 5’ depth markers cracked. One not slip resistant. Replace
.2523(c) Depth markers shall be slip resistant.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed no bolt in body hook. Provide 12’ non telescoping pole with at least one bolt in the body hook.
.2530(a) Provide at least 12 ft. long pole with body hook securely attached.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gate not self closing.
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter not functioning. Permit restriction requires function at all times.
.2518(g) Keep flow meter operational.
Jun 8, 2022 14 demerits · 4 violations
Inspector comments: .2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed faded “NO DIVING” stenciling on pool deck. Needs repainting before 2023 permit
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed paint on walls/steps deteriorating.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed dry-rotted ring buoy. CDI-new ring buoy acquired
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed leak at pump, needs repair/new gasket.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(i) Water in restrooms shall not exceed 110 F. Observed hot water in bathrooms >110F.
Jun 2, 2021 26 demerits · 7 violations
Inspector comments: Issued permit. Lights not verified. No Night Swimming.
Pool heater no longer being used.
Changed to "A" Open for Business.
Inspection with Rodney Anderson
No signature due to COVID
#1 · Water quality: water clear enough to clearly see bottom of pool and pool drain −6
Some sediment on pool bottom and main drain at time of inspection, could not clearly see main drains in good repair. .2535(2) Main drains must be clearly visible from the pool deck. Operator cleaned drains and corrected.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No records at time of inspection. Pool has been closed.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Operator recorded all required readings and corrected.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One inlet fitting at time of inspection. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Operator replaced and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Horizontals on fencing less than 45", 41". Pool and fence built 1996.
.2528(b) Horizontals shall not be located less than 45" in height.
Back gate has been bolted closed to be part of fence.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Cracks in deck by 5' end larger than 1/2" near ladder. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Operator filled cracks with dirt to seal and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping in pump room. Chemicals stored in pump room. Water on floor of pump room. Pool built '96. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. 2533(d) Pump room floor shall be kept dry and free of standing water.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap at sink in women's restroom. .2526(j) Provide soap and soap dispenser, no glass, at each sink.