4demerits
SAGE HIGHLAND CREEK
9246 HIGHLAND CREEK PY, Charlotte, NC 28269
Seasonal Swimming Pool · NC permit/State ID 2060501512
Latest result4 demerits
Last inspectedJun 5, 2026
Inspections on record8
On record sinceApr 14, 2021
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 14, 2021Lower is betterJun 5, 2026
Inspections & violations
Jun 5, 2026 4 demerits · 1 violation
Inspector comments: PERMIT RESTRICTIONS:
1). Flow meter must remain operable. Flow required at 152 GPM to 196 GPM to meet turnover and flow restriction of the filters. Flow
greater than 289 GPM is a suction hazard.
2). Plexiglas must remain in place on all stone columns to eliminate footholds.
- NIGHT SWIMMING IS NOT PERMITTED.
- CPO: Delmar Evans present during permit inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010).
- Observed space under fence of the opposite site from pump room measured at 3’’ and little more inches, space about 2.5” under couple of gates leading to pool deck. Issues fixed with more mulching and rocks to fill the space up at the time of inspection.
.2537(b) All gates and doors shall be self-closing, self-latching.- Observed three of the gates are not working properly. Fixed at the time of inspection.
Jun 3, 2026 14 demerits · 3 violations
Inspector comments: PERMIT RESTRICTIONS:
1). Flow meter must remain operable. Flow required at 152 GPM to 196 GPM to meet turnover and flow restriction of the filters. Flow greater than 289 GPM is a suction hazard.
2). Plexiglas must remain in place on all stone columns to eliminate footholds.
NOTE:
-This pool ID# 501512 permit denied today due to following noted items on the inspection sheet.
- All items shall be repaired/replaced, and ensure it is in good working condition.
- Please Contact the department office at 980-314-1620 to request and pay for the return visit prior to re-inspection. The return visit fee is $100.
- If you have any questions call EHS: 704-617-9777 or email to obtain the operational permit.
- The pool shall remain closed until permit is issued.
- NIGHT SWIMMING IS NOT PERMITTED.
- CPO: Delmar Evans present during permit inspection.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.- Observed pH measured 7.0.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.- Observed several gates around pool deck leading out from resident home are not latching and self-closed. Repair needed.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2519(k) Provide operational pressure gauge on filter.- Observed one of two pressure gauge on sand filter is not working needs repair or replace.
May 24, 2025 0 demerits · 0 violations
Inspector comments: Walked with Manager Christine. Permit was granted Flow was 185
Flow meter must remain operable. Flow required at 152gpm to 196 gpm to meet turnover and flow restriction of the filters. Flow greater than 289 gpm is a suction hazard.
New pump Pentair WhisperfloXF VS 022035, 5 hp pump
Blue white flow meter reading the flow range above.
Main drain and skimmer line 4” ; return line 3” (all coming out of the pump room floor).
(2) Waterway 2008 640-479x drain covers
(2) Pentair TR100C filters
(10) returns
(5) skimmers with equalizer lines plugged per State requirement.
All restrictions were met.
No violations were recorded for this inspection.
May 16, 2025 8 demerits · 2 violations
Inspector comments: PERMIT denied. Pump and breakers have been changed out without prior approval. Will need in field plan review speak with Chris or Katie along with electrical inspection Walked With Mike. Electrical inspection number is E764825. Spoke with Chris to confirm EHS is following all guidelines.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed pool floor with debris. CDI.. Pool was being cleaned.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(h) Provide approved pump in good repair. Observed pump has been changed out without approval. PER senior Will approval is needed by Chris or Katie along with in field review along with electrical inspection due to breakers being changed out.
May 13, 2024 12 demerits · 3 violations
Inspector comments: Night swimming not approved.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. - Observed minor debris in floor wall junctions of the pool. CDI- CPO started to clean pool floor. EHS was able to verify pool floor and main drain covers.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Observed minor debris in skimmer baskets. CDI- CPO cleaned skimmer baskets.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. - Observed two gates not self latching. CDI- CPO made adjustments to gates and EHS observed the gates self latching.
Apr 20, 2023 4 demerits · 1 violation
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed deck chairs less than 6ft from pool edge.
May 5, 2022 0 demerits · 0 violations
Inspector comments: EHS verified plexiglass in place on stone column to eliminate footholds.
PDSC form updated. All other issues mentioned on denial letter were fixed.
No violations were recorded for this inspection.
Apr 14, 2021 12 demerits · 3 violations
Inspector comments: Inspection conducted with GC Andy McAllister and CPO Ron Maynard. Due to COVID-19 precautions, inspection was not signed by the operator.
Verified items from construction inspection have been corrected.
Liquid chlorine tanks have been moved to the chemical storage room.
Hayward HCP30301, 3 HP pump with (2) Lawson MLD-SG-0909 drain covers. EQ lines plugged in skimmer, capped on underside.
Pool Width - 48 ft.
Rope Length - 50 ft.
Ma Depth - 5 ft.
Permit issued with the following conditions:
Plexiglass must remain in place on all stone columns to eliminate footholds.
No Night Swimming
“Executive Order No. 141 or subsequent Orders are in effect unless such Orders are rescinded or superseded by another applicable Order.”
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One skimmer basket with leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Right door to the fitness center not self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Corrected.
#18 · Premises: lifeguards present or warning signs posted −4
One of the rules signs with required signage visible from four of the common area pool entrances recently blew down. .2530(c) All pool signage shall be visible upon entrance to the pool and permanently affixed. - Corrected by operator.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “SAGE HIGHLAND CREEK” or State ID 2060501512). Inspection type (routine vs. follow-up) is not published in the county's data.