6demerits
ASHFORD GREEN
230 BARTON CREEK DR, Charlotte, NC 28262
Seasonal Swimming Pool · NC permit/State ID 2060501547
Latest result6 demerits
Last inspectedMay 21, 2026
Inspections on record5
On record sinceMay 13, 2022
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 13, 2022Lower is betterMay 21, 2026
Inspections & violations
May 21, 2026 6 demerits · 2 violations
Inspector comments: Pump was set to 2350 RPM and flow meter read 80 GPM at beginning of inspection. Operator changed speed to 3450 RPM, as pear permit conditions, and then flow reading went up to 140 GPM
No night swimming permitted
Pump and drain covers verified via PDSC form during inspection
Permit issued
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Log did not have column for checking drain covers. CDI - Operator added column to check drain covers each day.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Pipe to backwash pit has no air gap.
May 9, 2025 0 demerits · 0 violations
Inspector comments: Pump required at 3450 RPM to meet turnover at 139 GPM. Flow meter must remain operable. Flow shall not exceed 150 GPM due to drain cover flow restriction.
Note: No violations were observed during the inspection.
No violations were recorded for this inspection.
May 22, 2024 16 demerits · 3 violations
Inspector comments: .2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Observed multiple area of fence with more than 2 inches under it. PO will purchase mulch and rocks today to fill in the gaps. PO will send EHS a picture or corrections within 24 hrs.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed buoy rope greater than required 50 ft. CDI PO cut rope at 50ft.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door from clubhouse to pool not self latching. CDI PO adjusted hinge so that door self latches.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed 2 different phone numbers posted at emergency phone. CDI PO covered up the incorrect phone number.
Apr 20, 2023 0 demerits · 0 violations
Inspector comments: .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed pool fence by upper deck with a height less than 40” and height between horizontals is 24”. Observed foothold outside of pool that makes easy access to enter pool outside of using gate.
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed areas of fence with gaps of at most 4”.
Pool was built in 1996.
No violations were recorded for this inspection.
May 13, 2022 18 demerits · 5 violations
Inspector comments: Inspection conducted with Oscar Deleon.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed previous records for last season and the past couple weeks where CA not checked. PIC stated he does not check CA often. Ensure TA and CA are checked weekly.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length that was less than 50ft. CDI CPO purchased new rope at proper length and attached to ring buoy.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed pool fence by upper deck with a height less than 40” and height between horizontals is 24”. Observed foothold outside of pool that makes easy access to enter pool outside of using gate.
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). Observed areas of fence with gaps of at most 7”.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(b) Provide sufficient lighting in pump room. Observed no lighting available in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. Observed hose bib in bathroom and on pool deck without backflow prevention device.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Observed no color or labels to identify pipes in pump room.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “ASHFORD GREEN” or State ID 2060501547). Inspection type (routine vs. follow-up) is not published in the county's data.