‹ Back to search

10demerits

RESERVE, THE

8725 KODY MARIE CT, Charlotte, NC 28210
Seasonal Swimming Pool · NC permit/State ID 2060501575
Latest result10 demerits
Last inspectedApr 30, 2026
Inspections on record5
On record sinceApr 14, 2023

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01632 Apr 14, 2023: 32Jun 8, 2023: 8May 28, 2024: 14Apr 30, 2025: 4Apr 30, 2026: 10
Apr 14, 2023Lower is betterApr 30, 2026

Inspections & violations

Apr 30, 2026 10 demerits · 2 violations
Inspector comments: Night swimming is not permitted. Permit Restriction: Flow meter must remain operable. Flow shall not exceed 106 gpm due to filter flow restriction. Flow greater than 119 gpm exceeds the main drain flow. Suction Hazard. Turnover not met due to flow restriction of the filter.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. One skimmer observed with debris build up. Operator cleaned out basket during inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. No body hook on pole at pool deck. Operator placed a body hook securely attached to pole during inspection.

View this inspection on the county portal ›

Apr 30, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with CPO, Phillip Hall All permit compliance items corrected during inspection Interlock tested and operational CPO log records begin today Clubhouse is occupied during all open hours. Both doors leading onto the deck are self closing with audible alarms. Windows do not open. NO NIGHT SWIMMING ALLOWED Permit Restriction: Flow meter must remain operable with max flow of 106GPM +/-5% due to filter restriction. Mass speed exceeds drain Cover Flow. Observed 100gpm flow today set at 3450rpm. Permit issued
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(a) Provide correct depth markers on pool walls and pool deck next to the swimming pool. Observed “3 1/2 1/2” and “4 1/2 1/2” depth markers due to stickers being replaced. CDI - CPO spray painted the extra “1/2” markers black during inspection.

View this inspection on the county portal ›

May 28, 2024 14 demerits · 4 violations
Inspector comments: Inspection conducted with CPO, Jimmy present. PDSC information and restrictions verified onsite: Flow meter operable. Flow observed at 103 GPM+/- 5%. General Comments: *Observed chlorine to be over 10. Recommend to reduce chlorine to avoid skin irritation. Pool is not permitted for night swimming. Permit sticker issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed 1 of 2 bumper caps missing from pool ladder. -2-
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed throw rope exceeding requirement of 45 ft. CDI - CPO corrected by replacing rope measuring at 45 ft. -6-
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed opening measuring over 5” between vertices in part of fencing. Pre-2010 construction. -4-
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap at backwash. -2-

View this inspection on the county portal ›

Jun 8, 2023 8 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed bumpers missing from ladders.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Observed opening measuring over 5” between vertices in part of fencing. Pre-2010 construction.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap at backwash.

View this inspection on the county portal ›

Apr 14, 2023 32 demerits · 8 violations
Inspector comments: Permit Denied. Facility failed pre-permit inspection. Contact main office at 980-314-1620 to pay re-inspection fee. Contact EHS at 704-621-2294 to schedule re-inspection.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine testing 0ppm.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background. .2523(d) No Diving markers shall be provided in all areas of the pool less than five feet deep. .2523(d) The distance between no diving markers shall be no more than 25 feet perimeter or as the crow flies. Observed no “NO DIVING” markers present. .2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. .2523(c) Depth markers shall include the word "feet" or symbol "ft". .2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed depth markers not 4” in height in some markers and some did not include the word “feet” or “ft”.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed rubber caps missing from bottom feet of ladder.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed side door leading to pool deck near gym not self-latching and not child protected by audible alarm.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide required clearance of walking space around the pool at all times. Observed pool furniture 4 ft. 6 inches from edge of pool deck.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed Kings III phone number posted not audibly ringing back to the emergency phone and phone not answering once phone number is dialed. Goes to message stating Verizon wireless call could not be completed.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter not working when tested and not reading permit restriction requirements. Flow meter must remain operable with max flow of 106 gpa +/-5% due to filter size restriction.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap at backwash line.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “RESERVE, THE” or State ID 2060501575). Inspection type (routine vs. follow-up) is not published in the county's data.